Technical data July 2021 MTL fieldbus networks EPS MBx Rev 5 FCS-MBx-SG Megablock range* Passive hubs for general purpose, Zone 2 & Division 2 fieldbus networks Megablocks are DIN-rail mounted passive hubs for Foundation™ Connections to the Megablock are made using pluggable, screw- fieldbus networks. They connect several field devices to the network terminal type connectors. This allows wire terminations to be made to trunk cable and provide short circuit protection to the segment. the individual connectors which are then plugged into the Megablock. Megablocks minimize hand wiring and allow individual devices to be Devices can then be connected and disconnected easily during added to and removed from the segment without disrupting network commissioning. After commissioning, retaining screws are tightened communication. to secure each connector to the Megablock. A green power LED on each unit indicates whether at least 9V dc is Trunk connections for the fieldbus home-run/trunk cable are easily present. Megablocks are available in four, eight, ten and twelve drop identified by their black connectors. Separate numbered connections versions. Multiple Megablocks are easily wired to one another to allow are provided for each spur drop. larger segments to be constructed. SpurGuard™ is a device-port, short circuit protection technique Megablocks are available with an integral terminator making that minimizes susceptibility to single points of failure. The FCS-MBx- them ideal for a star or "chickenfoot" topology, where several devices SG Megablocks range has built-in SpurGuard™ protectors that prevent are connected at a single field junction box. Separate Megablock a short circuit in any of the individual transmitters or spur cable runs, Terminators are also available, which may be wired easily to any from bringing down the entire fieldbus segment. A red LED near each Megablock. Megablocks having a built-in terminator are clearly marked spur connection indicates when a spur is shorted and hence in "over- ('T') for easy identification by field personnel. current" mode. Eaton Electric Limited, Great Marlings, Butterfield, Luton Beds, LU2 8DL, UK. Tel: + 44 (0)1582 723633 Fax: + 44 (0)1582 422283 E-mail: mtlenquiry@eaton.com www.mtl-inst.com © 2021 Eaton All Rights Reserved Publication No. EPS MBx Rev 5 July 2021
MTL FCS-MBx-SG July 2021 INSTALLATION SPECIFICATIONS Megablocks can be mounted vertically or horizontally using 35 mm DIN Mounting requirements rail within a suitable enclosure, such as a field junction box. Megablocks 35mm DIN rail are removed from the DIN rail using a flat blade screwdriver to release Wire capacity the mounting platform. Use of DIN rail end stops is recommended to 0.14 to 2.5mm2 prevent sliding in vertical installations. FCS-MBx range Megablocks Case material have labeling areas so that segments can be easily identified according Lexan polycarbonate to plant standards. Temperature range MTL have a wide range of standard junction box designs for use with Operating –45º to +70ºC Megablocks. See the data sheet for the range of Process JBs. Storage –50º to +85ºC Voltage required to activate power LED 9.2V dc minimum Minimum input voltage 10.5V (See Note 1 below) Maximum input voltage see certification ratings Maximum input current see certification ratings Trunk-to-trunk voltage drop 0.1V maximum FCS-MBx-SG, F118 & F215 Megablock with SpurGuard™ Unloaded current consumption No. of Ports 4 8 10 12 mA 4.1 4.3 4.4 4.5 Spur device current 46mA maximum (recommend one device per spur) Spur short-circuit current 60mA maximum Trunk-to-trunk voltage drop 0.1V maximum Trunk-to-spur voltage drop 1.1V maximum PHYSICAL NETWORK IEC 61158-2 Foundation™ fieldbus H1 Profibus PA Note 1: The minimum input voltage guarantees that the spur output under full load will be at least 9.3V so that the device will see at least 9.0V. Shown above is an example of a common Fieldbus segment topology. Twelve field devices are connected to a twelve-drop Megablock, which is mounted in a field junction box. The trunk connector on the Megablock is wired to the segment trunk cable that leads to the control room or marshalling panel where the power supply and second terminator are located. GROUNDING To prevent ground loops, a fieldbus segment should only be grounded at one point. This is usually done by grounding the cable shield at the control room end of the segment. If a permanent segment ground connection in the field is desired, this can be achieved by wiring the shield terminal on one of the Megablock trunk connectors to a suitable earth ground instead of wiring it to the shield terminal on the Megablock Terminator. Fieldbus Connection System (FCS) wiring blocks are protected by U.S. Patents 6,366,437, 6,369,997 and 6,519,125.
MTL FCS-MBx-SG July 2021 CASE DIMENSIONS 4-WAY - FCS-MB4-SG(-T) FCS-MB4-SG Trunk 2 Power 1 3 www.mtl-fieldbus.com Trunk 4 Red Light Indicates Spur in Short Circuit Mode 8-WAY - FCS-MB8-SG(-T) 10-WAY - F118, FCS-MB10-SG(-T) FCS-MB10- FCS-MB8-SG SG-T Trunk Trunk 4 Power Power 5 1 5 1 6 2 6 2 7 www.mtl-fieldbus.com 3 7 www.mtl-fieldbus.com 3 8 Trunk 8 Red Light Indicates Spur in Short Circuit Mode 4 9 Trunk 10 Red Light Indicates Spur in Short Circuit Mode Note: Different Megablock versions have minor variations in labelling.
MTL FCS-MBx-SG July 2021 CASE DIMENSIONS (cont) 12-WAY MEGABLOCKS FCS-MB12-SG(-T) F215 FCS-MB12-SG-T Trunk F215 Trunk Power 6 Power 6 1 7 1 7 2 8 2 8 www.mtl-fieldbus.com www.mtl-fieldbus.com 7.16” 7.16” 3 9 182 mm 3 9 182 mm 4 10 4 10 5 11 5 11 Trunk Trunk 12 12 Red Light Indicates Red Light Indicates Spur in Short Circuit Mode Spur in Short Circuit Mode 1.98” 1.98” 50.4 mm 50.4 mm
MTL FCS-MBx-SG July 2021 APPROVALS - for full certification information visit www.mtl-inst.com/support/certificates/ MODELS - F118, F215, FCS-MB4-SG-[T], FCS-MB8-SG-[T], FCS-MB10-SG-[T], FCS-MB12-SG-[T] Country Europe USA Canada ATEX Authority FM FM FMc FMc (Category 3) Standard EN 60079-0 3600 1998 3600 1998 CSA C22.2 No. 213 :1987 CSA C22.2 No. 213 :1987 EN 60079-15 3611 1999 3611 1999 CSA E60079-0: 2002 CSA E60079-0: 2002 3810 1989 3810 1989 CSA E60079-15: 2002 CSA E60079-15: 2002 CSA C22.2 No.1010.1:1992 CSA C22.2 No.1010.1:1992 + Amendment 2 1997 + Amendment 2 1997 Approved E II 3 G NI/I/2/ABCD/T4 Ta=70ºC NI-ANI/I/2/ABCD/T4 Ta=70ºC NI-ANI/I/2/ABCD/T4 Ta=70ºC NI/I/2/ABCD/T4 Ta=70ºC for Ex nA IIC T4 Gc I / 2 / IIC / T4 Ta=70ºC NI-ANI/I/2/IIC/T4 Ta=70ºC Ex nA [nL] IIC T4 Ta=70ºC Ex nA IIC T4 Ta=70ºC Certificate RELC07A- 3013269 3013852 3039092C 3039410C no. TEX1001X Apparatus Non-arcing Non-arcing Non-arcing Non-arcing Non-arcing parameters (Trunk) Cable Non-arcing Non-arcing Non-incendive Non-incendive Non-arcing parameters Voc = 32V Voc = 32V (Spur) Isc = 60mA Isc = 60mA Ca = 85nF Ca = 85nF La = 0.26mH La = 0.26mH ORDERING INFORMATION With SpurGuard™ short-circuit protection General Purpose and Zone/Division 2 Megablocks 4 way FCS-MB4-SG 4 way with internal Terminator FCS-MB4-SG-T 8 way FCS-MB8-SG 8 way with internal Terminator FCS-MB8-SG-T 10 way FCS-MB10-SG 10 way with internal Terminator FCS-MB10-SG-T 10 way with switched Terminator F118 12 way FCS-MB12-SG 12 way with internal terminator FCS-MB12-SG-T 12 way with switched Terminator F215 See Fieldbus Terminators datasheet for details of separate, DIN-rail mounted terminators ACCESSORIES Description Part Number Heavy Duty DIN rail end stop ETL7000 35mm DIN Rail, 1 metre length THR7000 Process JB stainless steel‡ FCS-96XX ‡ See Process JB data sheets for further details Eaton Electric Limited, EUROPE (EMEA): The given data is only intended as a product Great Marlings, Butterfield, Luton +44 (0)1582 723633 description and should not be regarded as a legal warranty of properties or guarantee. In the interest Beds, LU2 8DL, UK. mtlenquiry@eaton.com of further technical developments, we reserve the Tel: + 44 (0)1582 723633 Fax: + 44 (0)1582 422283 right to make design changes. THE AMERICAS: E-mail: mtlenquiry@eaton.com +1 800 835 7075 www.mtl-inst.com mtl-us-info@eaton.com © 2021 Eaton All Rights Reserved ASIA-PACIFIC: Publication No. EPS MBx Rev 5 200721 +65 6 645 9888 July 2021 sales.mtlsing@eaton.com