TruONE ATS Automatic transfer switches - Replacement of mechanism and spare parts

Page created by Daniel Montgomery
 
CONTINUE READING
TruONE ATS Automatic transfer switches - Replacement of mechanism and spare parts
—
S ERVI C E I N ST R U C T I O N ; MECHANI SM, F R AME, P OWER AND CON TR OL MODULES

TruONE® ATS Automatic transfer switches
Replacement of mechanism and spare parts

                                                                                      TruONE® ATS Automatic transfer switches
                                                                                      34OX_MECH_ rev. B / 1SCC303018M0201
                                                                                      —
TruONE ATS Automatic transfer switches - Replacement of mechanism and spare parts
2                     A U T O M AT I C T R A N S F E R S W I T C H E S , R E P L A C E M E N T O F S PA R E PA R T S

Additional information
We reserve the right to make technical
changes or modify the contents of this
document without prior notice. With
regard to purchase orders, the agreed
particulars shall prevail. ABB does not
accept any responsibility whatsoever for
potential errors or possible lack of infor-
mation in this document.

We reserve all rights in this document
and in the subject matter and illustra-
tions contained therein. Any reproduc-
tion, disclosure to third parties or
utilization of its contents – in whole or
in parts – is forbidden without prior
written consent of ABB.
TruONE ATS Automatic transfer switches - Replacement of mechanism and spare parts
3 4 OX _ M E C H _ R E V. B , 1 S C C 3 0 3 0 1 8 M 0 2 0 1                                     3

—
Read these safety instructions carefully
before starting work!

                    Warning

• Detailed descriptions of standard proce-                     • This manual is written for qualified per-
  dures for installation, use, maintenance                       sonnel only and is not intended as a sub-
  and principles for safe operation are not                      stitute for a proper course, or experience
  included. It is important to note that this                    about safety procedures for this device.
  document contains safety and precaution                      • For the products equipped with commu-
  instructions, against certain methods (of                      nication, the purchaser, the installer or
  installation, use and maintenance) that                        the final customer is responsible for ap-
  could cause harm to personnel, damage                          plying all the IT security measures neces-
  devices, or make them unsafe.                                  sary in order to prevent risks deriving
• These warnings and alarms do not in-                           from connection to communication net-
  clude all conceivable ways to make instal-                     works; such risks include, among other
  lation, use and maintenance recom-                             things, the use of the product by unau-
  mended by ABB or not, that may be made,                        thorized persons, alteration of its normal
  or possible consequences and complica-                         functionality, accessing and modifying
  tions of each conceivable way, nor shall                       the information.
  ABB investigate all those ways.                              • The purchaser, installer or end user is re-
• Anyone using maintenance procedures or                         sponsible for ensuring that notices and
  devices, recommended by ABB or not,                            safety signs are posted and that all ac-
  must check thoroughly that neither per-                        cess points and switching devices are
  sonal safety nor the safety devices are                        locked securely when the switchgear is
  endangered by mode of installation, use,                       left unattended, even momentarily.
  maintenance or the instruments used.                         • All the information contained in this doc-
  For more information, questions or spe-                        ument reflects the latest product infor-
  cific problems contact your nearest ABB                        mation available at the time of printing.
  representative.                                                We reserve the right to edit the document
                                                                 at any time and without notice.
TruONE ATS Automatic transfer switches - Replacement of mechanism and spare parts
4              A U T O M AT I C T R A N S F E R S W I T C H E S , R E P L A C E M E N T O F S PA R E PA R T S

—
Risk of electric shock or accident!

                 Hazard

Before proceeding with any maintenance                   The maintenance operations must be car-
operation, it is mandatory to:                           ried out by skilled personnel:
• Disconnect the power supply to the                     • An electrical skilled personnel (IEV 195-
  power circuit and auxiliary circuits and                 04-01: person with relevant education
  visibly ground the terminals on both the                 and experience to enable him or her to
  supply side and load side.                               perceive risks and to avoid hazards which
• Use adequate personal protection equip-                  electricity can create).
  ment, ensure that the apparatus is in a                • ABB declines all liability for damage to
  safe condition and proceed in accordance                 persons or property caused by failure to
  with the Laws in force.                                  comply with the instructions in this docu-
                                                           ment.

—
Tools needed

                              Torx 20, long,
                              min. 140 mm
TruONE ATS Automatic transfer switches - Replacement of mechanism and spare parts
3 4 OX _ M E C H _ R E V. B , 1 S C C 3 0 3 0 1 8 M 0 2 0 1                               5

                                        —
                                        Service instruction
                                        Automatic transfer

                                                                                              1
                                        switches, TruONE® ATS

                                                                                              2
                                        1. 	 Removing the complete mechanism
                                             from the switch, OX_30...1600_              6

                                        2. 	 Replacing of complete mechanism
                                             with electronics, OX_30...1600_             9

                                                                                              3
                                        3. 	 OX_30...400_ | Removing of frame,
                                             control and power modules                   14

                                              REMARK! See also Chapter 1: Removing
                                              complete mechanism from the switch

                                                                                              4
                                        4.    OX_30...400_ | Replacing of frame,
                                              power and control modules                  18

                                              REMARK! See also Chapter 2: Replacing of
                                              complete mechanism with electronics             5

                                        5. 	 OX_400U...1600 | Removing of frame,
                                             control and power modules                   23
                                             REMARK! See also Chapter 1: Removing
                                             complete mechanism from the switch

                                        6.    OX_400U...1600 | Replacing of frame,
                                              power and control modules                  27
                                                                                              6

                                              REMARK! See also Chapter 2: Replacing of
                                              complete mechanism with electronics
TruONE ATS Automatic transfer switches - Replacement of mechanism and spare parts
6     A U T O M AT I C T R A N S F E R S W I T C H E S , R E P L A C E M E N T O F S PA R E PA R T S

    —
    Removing the complete mechanism
    from the switch, OX_30...1600_
1

                                     !
TruONE ATS Automatic transfer switches - Replacement of mechanism and spare parts
3 4 OX _ M E C H _ R E V. B , 1 S C C 3 0 3 0 1 8 M 0 2 0 1   7

                                                                  1
TruONE ATS Automatic transfer switches - Replacement of mechanism and spare parts
8                 A U T O M AT I C T R A N S F E R S W I T C H E S , R E P L A C E M E N T O F S PA R E PA R T S
1

                                                                                                                                 OXA400X3X3QBM
        IEC 60947-6-1                       Ie 400A 50...60Hz         480VAC 400A        Automatic Transfer Switch
                                                                                                                     Suitable for use    OZXA400 or
                                                                                         for use Emergency or

                                                                                                                                                                      A
          Class PC                          415V 400A AC-31B                             Standby Systems             with terminal kit   OZXA400L
                                            415V 400A AC-33B
                                            Uimp 6 kV
                                                                                         Minimum enclosure:          Use Cu-Al conductors
                                            Icw 30kA /100ms                              height mm
                                                                                                     400A
                                                                                                     1180
                                                                                                                     60˚C Wire only
                                            Icm 36kA                                     width mm    560
                                                                                                                     4x2-600 MCM
                                                                                                                     Terminal torque 500 lb-in
                                                                      TRANSFER SWITCH    depth mm    217
        Short-circuit current ratings:                                                                               Short-time current ratings:

           RMS                       FUSE CLASS or                                                                      RMS
         SYMM AMPS       VOLTAGE     CIRCUIT BREAKER           AMPS      RMS                                          SYMM AMPS       VOLTAGE      TIME DURATION
                           MAX       MANUFACTURER/ TYPE        MAX     SYMM AMPS    VOLTAGE     TIME DURATION           X1000            MAX            Sec.
           X1000
                                                                         X1000          MAX          Sec.
            100            480                   J             600                                                      30               480           0.1
            50             480           ABB / Tmax T5L, T5V   400        50            480          0.03                                              0.3
            100            415                   gG            800        40            480          0.06                                              0.5

                                                                                                                                                    MADE IN FINLAND
TruONE ATS Automatic transfer switches - Replacement of mechanism and spare parts
3 4 OX _ M E C H _ R E V. B , 1 S C C 3 0 3 0 1 8 M 0 2 0 1                                           9

—
Replacing of complete mechanism with
electronics, OX_30...1600_ / OX_MECH_

                                                        Complete mechanism with
                                                        electronics (without HMI)
                                                        • Open transition (I - II)

                                                                                                              2
                                                          -- Level 2: OXAMECH-2-L2,
                                                             OXAMECH-3-L2, OXAMECH-4-L2
                                                          -- Level 3: OXAMECH-2-L3,
                                                             OXAMECH-3-L3, OXAMECH-4-L3
                                                          -- Level 4: OXAMECH-2-L4,
                                                             OXAMECH-3-L4, OXAMECH-4-L4
                                                        • Delayed transition (I - O - II or II - O - I)
                                                          -- Level 2: OXBMECH-2-L2,
                                                             OXBMECH-3-L2, OXBMECH-4-L2
                                                          -- Level 3: OXBMECH-2-L3,
                                           A                 OXBMECH-3-L3, OXBMECH-4-L3
                                                          -- Level 4: OXBMECH-2-L4,
                                                             OXBMECH-3-L4, OXBMECH-4-L4

                                                        Check the handle position in the new
                                                        mechanism is same as the indication in
                                                        the switch! Use the handle if needed!

                           !
TruONE ATS Automatic transfer switches - Replacement of mechanism and spare parts
10   A U T O M AT I C T R A N S F E R S W I T C H E S , R E P L A C E M E N T O F S PA R E PA R T S
2

                                                   1 Nm / 8.75 lb.in
3 4 OX _ M E C H _ R E V. B , 1 S C C 3 0 3 0 1 8 M 0 2 0 1                             11

                                                                                             2
                                                              Configuration with Ekip
                                                              Programming -module by
                                                              using Ekip Connect
                                                              -software.
12   A U T O M AT I C T R A N S F E R S W I T C H E S , R E P L A C E M E N T O F S PA R E PA R T S

                                                                                     Click
2
3 4 OX _ M E C H _ R E V. B , 1 S C C 3 0 3 0 1 8 M 0 2 0 1          13

                                                                          2
                                                              !
                                                              AUTO
14        A U T O M AT I C T R A N S F E R S W I T C H E S , R E P L A C E M E N T O F S PA R E PA R T S

    —
    OX_30...400_ | Removing of frame,
    control and power modules

    See Chapter 1 to remove the
    mechanism from the switch.

                                                                                  1
3

                                                                                                   2

                                                                                                       3
3 4 OX _ M E C H _ R E V. B , 1 S C C 3 0 3 0 1 8 M 0 2 0 1                                                                                                                                                                                                                                                                 15

Removing of control module
                                                                     Adecuado para transferencia completa        Cuando esté protegida con un

                                   !
                                         DANGER/                     cuando la carga de tungsteno no exceda interruptor automático de un
                                                                     30 por ciento del valor nominal del equipo. fabricante en específico, del tipo y
                                         PELIGRO                     La corriente continua de la carga no
                                                                                                                 corriente nominal como se muestra
                                                                                                                 a continuación, esta transferencia
                                                                     debe exceder 100 por ciento del valor       es adecuada para utilizarse en un
                                 HAZARDOUS                           nominal del equipo.                         circuito capaz de liberar la corriente
                                 VOLTAGE                                                                         de cortocircuito a la tensioón
                                                                     AGUANTE DE CORTOCIRCUITO/CORRIENTES máxima marcada.
                                 Will cause death, burn or
                                 serious injury.                     NOMINALES DE CIERRE Y CORTA DURACIÓN
                                                                     CUANDO SE UTILIZAN INTERRUPTORES            SI el interruptor automático tiene
                                 WARNING                             AUTOMÁTICOS ESPECÍFICOS.                    una respuesta de corta duración,
                                 - more than one                                                                 debe coordinarse con la corriente
                                 live circuit-disconnect all                                                     nominal de corta duración de la
                                 sources of supply before                                                        transferencia mostrada a
                                 servicing.                                                                      continuación.

                                 HAUTE                                                                           AGUANTE DE CORTOCIRCUITO/VALOR
                                 TENSION                                                                         NOMINAL DE CIERRE CUANDO SE
                                 Danger de mort brûlures                                                         PROTEGE CON FUSIBLES.
                                 ou de blessures graves.
                                 AVERTISSEMENT                                                                   Cuando esté protegida con un
                                                                                                                 fusible de la clase específica y
                                 - Plus d´un circuit sous tension-                                               corriente nominal máxima como se
                                 débrancher toutes les                                                           muestra a continuación, esta
                                 sources d´alimentation                                                          transferencia es adecuada para
                                 avant d´entreprendre le                                                         utilizarse en un circuito capaz de
                                 dépannage.                                                                      liberar la corriente de contocircuito
                                                                                                                 a la tensión máxima marcada.
                                 TENSION
                                 PELIGROSA
                                 Causa muerte, incendio
                                 o accidentes graves.
                                 ADVERTENCIA                                                   Convient à la commutation de la charge totale ď un
                                                                                               circuit si la charge de tungsten ne dépasse pas de
                                 - Más de un circuito vivo-                                    30 pourcent le couranr nominal du commutateur.
                                 Desconecte todas las fuentes de
                                 suministro antes de servicio.                                 Le courant de charge continu ne doit pas dépasser
                                                                                               de 100 pourcent le courant nominal du commutateur.
                                 Suitable for total system transfer where the
                                 tungsten load does not exceed 30 percent of
                                 the switch rating.
                                                                                               AVERTISSEMENT
                                                                                               - Vérifier l´état de la source
                                 Continuous load current not to exceed 100                     d´alimentation avant un transfert manuel.
                                 percent of switch rating.                                     Une opération manuelle peut entraîner un transfert
                                                                                               déphasé si les deux sources sont sous tension.

                                                                                                                                                                                                                                                                                                                        Torx 20
                                 WARNING
                                 - Verify the condition of power source prior
                                                                                               COURANTS NOMINAUX DE RÉSISTANCE AU
                                 to manually tranferring.                                      COURT-CIRCUIT ET DE FERMETURE DE CIRCUIT
                                 Manual operation may result in out-of-phase                   ET COURANTS NOMINAUX DE COURTE DURÉE
                                 transfer when both sources are energized.                     POUR DES DISJONCTEURS SPÉCIFIQUES.

                                 For periodic testing and adjusting transfer                   De commutateur, s´il est protégé par un disjoncteur
                                 voltage, transfer frequence and transfer                      dont le nom du fabricant, le type et le courant
                                 delay time, see the instructional manual.                     nominal sont indiqués plus bas, convient à des
                                                                                               circuits capables d�acheminer un courant de court-
                                 SHORT-CIRCUIT WITHSTAND/CLOSING                               circuit à la tension maximale indiquée plus bas.
                                 AND SHORT-TIME CURRENT RATINGS
                                 WHEN USING SPECIFIC CIRCUIT                                   Si le disjoncteur est à déclenchement rapide, le
                                                                                               déclenchement doit êntre coordonné au de
                                 BREAKERS OR PROTECTED BY FUSES                                courte durée du commutateur indigué plus bas.
                                 When protected by a specific circuit breaker
                                 or by a fuse of the specific fuse class as                    COURANTS NOMINAUX DE RÉSISTANCE AU
                                 marked below, this transfer switch is                         COURT-CIRCUIT ET DE FERMETURE DE CIRCUIT
                                 suitable for use in circuits capable of                       SI LA PROTECTION EST ASSURÉE PAR DES
                                 delivering the short-circuit current at the                   FUSIBLES.
                                 maximum voltage marked.
                                                                                               Ce commutateur, ś�il est protégé par un fusible dont
                                 When the circuit breaker has a short-time                     la classe et le courant nominal sont indiqués plus
                                 response, it shall be coordinated with the                    bas, convient à un circuit capable d�acheminer le
                                 short-time current rating of the transfer                     courant de court-circuit à la tension maximale
                                 switch shown below.                                           indiquée.

                                                                                                                                                                                                                                                                                  !                                                    3
                                                                                                                                                                                                                                                                                  OX_CONTROL-400-L_

                                                                                                                                                                                                                                                                                   OXA400X3X3QBM
                                                                                                                                                          IEC 60947-6-1                       Ie 400A 50...60Hz         480VAC 400A        Automatic Transfer Switch
                                                                                                                                                                                                                                                                       Suitable for use    OZXA400 or
                                                                                                                                                                                                                                           for use Emergency or
                                                                                                                                                            Class PC                          415V 400A AC-31B                             Standby Systems             with terminal kit   OZXA400L
                                                                                                                                                                                              415V 400A AC-33B
                                                                                                                                                                                              Uimp 6 kV
                                                                                                                                                                                                                                           Minimum enclosure:          Use Cu-Al conductors
                                                                                                                                                                                              Icw 30kA /100ms                              height mm
                                                                                                                                                                                                                                                       400A
                                                                                                                                                                                                                                                       1180
                                                                                                                                                                                                                                                                       60˚C Wire only
                                                                                                                                                                                              Icm 36kA                                     width mm    560
                                                                                                                                                                                                                                                                       4x2-600 MCM
                                                                                                                                                                                                                                                                       Terminal torque 500 lb-in
                                                                                                                                                                                                                        TRANSFER SWITCH    depth mm    217
                                                                                                                                                          Short-circuit current ratings:                                                                               Short-time current ratings:

                                                                                                                                                             RMS                       FUSE CLASS or                                                                      RMS
                                                                                                                                                           SYMM AMPS       VOLTAGE     CIRCUIT BREAKER           AMPS      RMS                                          SYMM AMPS       VOLTAGE      TIME DURATION
                                                                                                                                                                             MAX       MANUFACTURER/ TYPE        MAX     SYMM AMPS    VOLTAGE     TIME DURATION           X1000            MAX            Sec.
                                                                                                                                                             X1000
                                                                                                                                                                                                                           X1000          MAX          Sec.
                                                                                                                                                              100            480                   J             600                                                      30               480           0.1
                                                                                                                                                              50             480           ABB / Tmax T5L, T5V   400        50            480          0.03                                              0.3
                                                                                                                                                              100            415                   gG            800        40            480          0.06                                              0.5

                                                                                                                                                                                                                                                                                                      MADE IN FINLAND
16       A U T O M AT I C T R A N S F E R S W I T C H E S , R E P L A C E M E N T O F S PA R E PA R T S

                                                                     Hazard
                                                                     Wait at least 60 seconds after
                                                                     removing the mechanism before
                                                                     disconnecting the connector to
                                                                     allow the capacitors to
                                                                     discharge.
3

    Removing of power module

                                                           Torx 20
3 4 OX _ M E C H _ R E V. B , 1 S C C 3 0 3 0 1 8 M 0 2 0 1   17

                                                                   3
18              A U T O M AT I C T R A N S F E R S W I T C H E S , R E P L A C E M E N T O F S PA R E PA R T S

    —
    OX_30...400 | Replacing of frame, power
    and control modules

    Power module                                              Frame module
4

    • Open transition (I - II) and delayed                    • Open transition (I - II)
      transition (I - O - I or II - O - I)                      -- OXAFRAME-2
      -- OXPOWER-400                                          • Delayed transition (I - O - II or II - O - I)
                                                                -- OXBFRAME-2
3 4 OX _ M E C H _ R E V. B , 1 S C C 3 0 3 0 1 8 M 0 2 0 1                       19

                                                                                       4

                                                              Torx 20,
                                                              1 Nm / 8.75 lb.in
20                A U T O M AT I C T R A N S F E R S W I T C H E S , R E P L A C E M E N T O F S PA R E PA R T S

    Control module

    • Open transition (I - II)
      -- Level 2: OXACONTROL-400-L2
      -- Level 3: OXACONTROL-400-L3
      -- Level 4: OXACONTROL-400-L4
    • Delayed transition (I - O - II or II - O - I)
      -- Level 2: OXBCONTROL-400-L2
      -- Level 3: OXBCONTROL-400-L3
      -- Level 4: OXBCONTROL-400-L4

                                                                Apply warning label on top
                                                                of the closed connector.
4
3 4 OX _ M E C H _ R E V. B , 1 S C C 3 0 3 0 1 8 M 0 2 0 1                       21

                                                              Torx 20,
                                                              1 Nm / 8.75 lb.in

                                                                                       4
22   A U T O M AT I C T R A N S F E R S W I T C H E S , R E P L A C E M E N T O F S PA R E PA R T S
4
3 4 OX _ M E C H _ R E V. B , 1 S C C 3 0 3 0 1 8 M 0 2 0 1               23

—
OX_400U...1600 | Removing of frame,
control and power modules

See Chapter 1 to remove the
mechanism from the switch.

                                                                     1

                                                                         2
                                                                                      5

                                                                             3
24        A U T O M AT I C T R A N S F E R S W I T C H E S , R E P L A C E M E N T O F S PA R E PA R T S

    Removing of control module

                                                                                                                                                                                                                                                                                !
                                                                                                                                                                                                                                                                                OX_CONTROL-1600-L_

                                                                                                                                                                                                                                                                                 OXA400X3X3QBM
                                                                                                                                                        IEC 60947-6-1                       Ie 400A 50...60Hz         480VAC 400A        Automatic Transfer Switch
                                                                                                                                                                                                                                                                     Suitable for use    OZXA400 or
                                                                                                                                                                                                                                         for use Emergency or
                                                                                                                                                          Class PC                          415V 400A AC-31B                             Standby Systems             with terminal kit   OZXA400L
                                                                                                                                                                                            415V 400A AC-33B
                                                                                                                                                                                            Uimp 6 kV
                                                                                                                                                                                                                                         Minimum enclosure:          Use Cu-Al conductors
                                                                                                                                                                                            Icw 30kA /100ms                              height mm
                                                                                                                                                                                                                                                     400A
                                                                                                                                                                                                                                                     1180
                                                                                                                                                                                                                                                                     60˚C Wire only
                                                                                                                                                                                            Icm 36kA                                     width mm    560
                                                                                                                                                                                                                                                                     4x2-600 MCM
                                                                                                                                                                                                                                                                     Terminal torque 500 lb-in
                                                                                                                                                                                                                      TRANSFER SWITCH    depth mm    217
                                                                                                                                                        Short-circuit current ratings:                                                                               Short-time current ratings:

                                                                                                                                                           RMS                       FUSE CLASS or                                                                      RMS
                                                                                                                                                         SYMM AMPS       VOLTAGE     CIRCUIT BREAKER           AMPS      RMS                                          SYMM AMPS       VOLTAGE      TIME DURATION
                                                                                                                                                                           MAX       MANUFACTURER/ TYPE        MAX     SYMM AMPS    VOLTAGE     TIME DURATION           X1000            MAX            Sec.
                                                                                                                                                           X1000
                                                                                                                                                                                                                         X1000          MAX          Sec.
                                                                                                                                                            100            480                   J             600                                                      30               480           0.1
                                                                                                                                                            50             480           ABB / Tmax T5L, T5V   400        50            480          0.03                                              0.3
                                                                                                                                                            100            415                   gG            800        40            480          0.06                                              0.5

                                                                                                                                                                                                                                                                                                    MADE IN FINLAND

                                                                   Adecuado para transferencia completa        Cuando esté protegida con un

                                 !
                                       DANGER/                     cuando la carga de tungsteno no exceda interruptor automático de un
                                                                   30 por ciento del valor nominal del equipo. fabricante en específico, del tipo y
                                       PELIGRO                     La corriente continua de la carga no
                                                                                                               corriente nominal como se muestra
                                                                                                               a continuación, esta transferencia
                                                                   debe exceder 100 por ciento del valor       es adecuada para utilizarse en un
                               HAZARDOUS                           nominal del equipo.                         circuito capaz de liberar la corriente
                               VOLTAGE                                                                         de cortocircuito a la tensioón
                                                                   AGUANTE DE CORTOCIRCUITO/CORRIENTES máxima marcada.
                               Will cause death, burn or
                               serious injury.                     NOMINALES DE CIERRE Y CORTA DURACIÓN
                                                                   CUANDO SE UTILIZAN INTERRUPTORES            SI el interruptor automático tiene
                               WARNING                             AUTOMÁTICOS ESPECÍFICOS.                    una respuesta de corta duración,
                               - more than one                                                                 debe coordinarse con la corriente
                               live circuit-disconnect all                                                     nominal de corta duración de la
                               sources of supply before                                                        transferencia mostrada a
                               servicing.                                                                      continuación.

                               HAUTE                                                                           AGUANTE DE CORTOCIRCUITO/VALOR
                               TENSION                                                                         NOMINAL DE CIERRE CUANDO SE
                               Danger de mort brûlures                                                         PROTEGE CON FUSIBLES.
                               ou de blessures graves.

                         OR
                               AVERTISSEMENT                                                                   Cuando esté protegida con un
                                                                                                               fusible de la clase específica y
                               - Plus d´un circuit sous tension-                                               corriente nominal máxima como se
                               débrancher toutes les                                                           muestra a continuación, esta
                               sources d´alimentation                                                          transferencia es adecuada para
                               avant d´entreprendre le                                                         utilizarse en un circuito capaz de
                               dépannage.                                                                      liberar la corriente de contocircuito
                                                                                                               a la tensión máxima marcada.
                               TENSION

                                                                                                                                                                                                                                                                                                                      Torx 20
                               PELIGROSA
                               Causa muerte, incendio
                               o accidentes graves.
                               ADVERTENCIA                                                   Convient à la commutation de la charge totale ď un
                                                                                             circuit si la charge de tungsten ne dépasse pas de
                               - Más de un circuito vivo-                                    30 pourcent le couranr nominal du commutateur.
                               Desconecte todas las fuentes de
                               suministro antes de servicio.                                 Le courant de charge continu ne doit pas dépasser
                                                                                             de 100 pourcent le courant nominal du commutateur.
                               Suitable for total system transfer where the
                               tungsten load does not exceed 30 percent of
                               the switch rating.
                                                                                             AVERTISSEMENT
                                                                                             - Vérifier l´état de la source
                               Continuous load current not to exceed 100                     d´alimentation avant un transfert manuel.
                               percent of switch rating.                                     Une opération manuelle peut entraîner un transfert
                                                                                             déphasé si les deux sources sont sous tension.
                               WARNING
                               - Verify the condition of power source prior
                                                                                             COURANTS NOMINAUX DE RÉSISTANCE AU
                               to manually tranferring.                                      COURT-CIRCUIT ET DE FERMETURE DE CIRCUIT
                               Manual operation may result in out-of-phase                   ET COURANTS NOMINAUX DE COURTE DURÉE
                               transfer when both sources are energized.                     POUR DES DISJONCTEURS SPÉCIFIQUES.

                               For periodic testing and adjusting transfer                   De commutateur, s´il est protégé par un disjoncteur
                               voltage, transfer frequence and transfer                      dont le nom du fabricant, le type et le courant
                               delay time, see the instructional manual.                     nominal sont indiqués plus bas, convient à des
                                                                                             circuits capables d�acheminer un courant de court-
                               SHORT-CIRCUIT WITHSTAND/CLOSING                               circuit à la tension maximale indiquée plus bas.
                               AND SHORT-TIME CURRENT RATINGS
                               WHEN USING SPECIFIC CIRCUIT                                   Si le disjoncteur est à déclenchement rapide, le
                                                                                             déclenchement doit êntre coordonné au de
                               BREAKERS OR PROTECTED BY FUSES                                courte durée du commutateur indigué plus bas.
                                When protected by a specific circuit breaker
                                or by a fuse of the specific fuse class as                   COURANTS NOMINAUX DE RÉSISTANCE AU
                                marked below, this transfer switch is                        COURT-CIRCUIT ET DE FERMETURE DE CIRCUIT
                                suitable for use in circuits capable of                      SI LA PROTECTION EST ASSURÉE PAR DES
                                delivering the short-circuit current at the                  FUSIBLES.
                                maximum voltage marked.
                                                                                             Ce commutateur, ś�il est protégé par un fusible dont
                                When the circuit breaker has a short-time                    la classe et le courant nominal sont indiqués plus
                                response, it shall be coordinated with the                   bas, convient à un circuit capable d�acheminer le
                                short-time current rating of the transfer                    courant de court-circuit à la tension maximale
                                switch shown below.                                          indiquée.
5
3 4 OX _ M E C H _ R E V. B , 1 S C C 3 0 3 0 1 8 M 0 2 0 1   25

                                                                   5
26       A U T O M AT I C T R A N S F E R S W I T C H E S , R E P L A C E M E N T O F S PA R E PA R T S

    Removing of power module

                        Torx 20, long,
                        min. 140 mm
5
3 4 OX _ M E C H _ R E V. B , 1 S C C 3 0 3 0 1 8 M 0 2 0 1   27

—
OX_400U...1600 | Replacing of frame,
power and control modules

Frame module

• Open transition (I - II)
  -- OXAFRAME-3
  -- OXAFRAME-4
• Delayed transition (I - O - II or II - O - I)
  -- OXBFRAME-3
  -- OXBFRAME-4

Power module

• Open transition (I - II) and delayed
  transition (I - O - I or II - O - I)
  -- OXPOWER-1600

                                                                               6
28   A U T O M AT I C T R A N S F E R S W I T C H E S , R E P L A C E M E N T O F S PA R E PA R T S
6
3 4 OX _ M E C H _ R E V. B , 1 S C C 3 0 3 0 1 8 M 0 2 0 1   29

                              Torx 20, long,
                              min. 140 mm
                              1 Nm / 8.75 lb.in

Control module

• Open transition (I - II)
  -- Level 2: OXACONTROL-1600-L2
  -- Level 3: OXACONTROL-1600-L3
  -- Level 4: OXACONTROL-1600-L4
• Delayed transition (I - O - II or II - O - I)
  -- Level 2: OXBCONTROL-1600-L2
  -- Level 3: OXBCONTROL-1600-L3
  -- Level 4: OXBCONTROL-1600-L4
                                                                               6
30   A U T O M AT I C T R A N S F E R S W I T C H E S , R E P L A C E M E N T O F S PA R E PA R T S

                                                                                                                           Adecuado para transferencia completa        Cuando esté protegida con un

                                                                                         !
                                                                                               DANGER/                     cuando la carga de tungsteno no exceda interruptor automático de un
                                                                                                                           30 por ciento del valor nominal del equipo. fabricante en específico, del tipo y
                                                                                               PELIGRO                     La corriente continua de la carga no
                                                                                                                                                                       corriente nominal como se muestra
                                                                                                                                                                       a continuación, esta transferencia
                                                                                                                           debe exceder 100 por ciento del valor       es adecuada para utilizarse en un
                                                                                       HAZARDOUS                           nominal del equipo.                         circuito capaz de liberar la corriente
                                                                                       VOLTAGE                                                                         de cortocircuito a la tensioón
                                                                                                                           AGUANTE DE CORTOCIRCUITO/CORRIENTES máxima marcada.
                                                                                       Will cause death, burn or
                                                                                       serious injury.                     NOMINALES DE CIERRE Y CORTA DURACIÓN
                                                                                                                           CUANDO SE UTILIZAN INTERRUPTORES            SI el interruptor automático tiene
                                                                                       WARNING                             AUTOMÁTICOS ESPECÍFICOS.                    una respuesta de corta duración,
                                                                                       - more than one                                                                 debe coordinarse con la corriente
                                                                                       live circuit-disconnect all                                                     nominal de corta duración de la
                                                                                       sources of supply before                                                        transferencia mostrada a
                                                                                       servicing.                                                                      continuación.

                                                                                       HAUTE                                                                           AGUANTE DE CORTOCIRCUITO/VALOR
                                                                                       TENSION                                                                         NOMINAL DE CIERRE CUANDO SE
                                                                                       Danger de mort brûlures                                                         PROTEGE CON FUSIBLES.
                                                                                       ou de blessures graves.
                                                                                       AVERTISSEMENT                                                                   Cuando esté protegida con un
                                                                                                                                                                       fusible de la clase específica y
                                                                                       - Plus d´un circuit sous tension-                                               corriente nominal máxima como se
                                                                                       débrancher toutes les                                                           muestra a continuación, esta
                                                                                       sources d´alimentation                                                          transferencia es adecuada para
                                                                                       avant d´entreprendre le                                                         utilizarse en un circuito capaz de
                                                                                       dépannage.                                                                      liberar la corriente de contocircuito
                                                                                                                                                                       a la tensión máxima marcada.
                                                                                       TENSION
                                                                                       PELIGROSA
                                                                                       Causa muerte, incendio
                                                                                       o accidentes graves.
                                                                                       ADVERTENCIA                                                   Convient à la commutation de la charge totale ď un
                                                                                                                                                     circuit si la charge de tungsten ne dépasse pas de

                        Torx 20
                                                                                       - Más de un circuito vivo-                                    30 pourcent le couranr nominal du commutateur.
                                                                                       Desconecte todas las fuentes de
                                                                                       suministro antes de servicio.                                 Le courant de charge continu ne doit pas dépasser
                                                                                                                                                     de 100 pourcent le courant nominal du commutateur.
                                                                                       Suitable for total system transfer where the
                                                                                       tungsten load does not exceed 30 percent of
                                                                                       the switch rating.
                                                                                                                                                     AVERTISSEMENT
                                                                                                                                                     - Vérifier l´état de la source
                                                                                       Continuous load current not to exceed 100                     d´alimentation avant un transfert manuel.
                                                                                       percent of switch rating.                                     Une opération manuelle peut entraîner un transfert
                                                                                                                                                     déphasé si les deux sources sont sous tension.
                                                                                       WARNING
                                                                                       - Verify the condition of power source prior
                                                                                                                                                     COURANTS NOMINAUX DE RÉSISTANCE AU
                                                                                       to manually tranferring.                                      COURT-CIRCUIT ET DE FERMETURE DE CIRCUIT

                        1 Nm / 8.75 lb.in
                                                                                       Manual operation may result in out-of-phase                   ET COURANTS NOMINAUX DE COURTE DURÉE
                                                                                       transfer when both sources are energized.                     POUR DES DISJONCTEURS SPÉCIFIQUES.

                                                                                       For periodic testing and adjusting transfer                   De commutateur, s´il est protégé par un disjoncteur
                                                                                       voltage, transfer frequence and transfer                      dont le nom du fabricant, le type et le courant
                                                                                       delay time, see the instructional manual.                     nominal sont indiqués plus bas, convient à des
                                                                                                                                                     circuits capables d�acheminer un courant de court-
                                                                                       SHORT-CIRCUIT WITHSTAND/CLOSING                               circuit à la tension maximale indiquée plus bas.
                                                                                       AND SHORT-TIME CURRENT RATINGS
                                                                                       WHEN USING SPECIFIC CIRCUIT                                   Si le disjoncteur est à déclenchement rapide, le
                                                                                                                                                     déclenchement doit êntre coordonné au de
                                                                                       BREAKERS OR PROTECTED BY FUSES                                courte durée du commutateur indigué plus bas.
                                                                                       When protected by a specific circuit breaker
                                                                                       or by a fuse of the specific fuse class as                    COURANTS NOMINAUX DE RÉSISTANCE AU
                                                                                       marked below, this transfer switch is                         COURT-CIRCUIT ET DE FERMETURE DE CIRCUIT
                                                                                       suitable for use in circuits capable of                       SI LA PROTECTION EST ASSURÉE PAR DES
                                                                                       delivering the short-circuit current at the                   FUSIBLES.
                                                                                       maximum voltage marked.
                                                                                                                                                     Ce commutateur, ś�il est protégé par un fusible dont
                                                                                       When the circuit breaker has a short-time                     la classe et le courant nominal sont indiqués plus
                                                                                       response, it shall be coordinated with the                    bas, convient à un circuit capable d�acheminer le
                                                                                       short-time current rating of the transfer                     courant de court-circuit à la tension maximale
                                                                                       switch shown below.                                           indiquée.

                                                   See Chapter 2 to remount the
                                                   mechanism to the switch.
6
3 4 OX _ M E C H _ R E V. B , 1 S C C 3 0 3 0 1 8 M 0 2 0 1   31
—