Troubleshooting Guide - CUSTOM FIREPLACES - Copyright 2021 Travis Industries Certified Factory Training Program - Travis ...
←
→
Page content transcription
If your browser does not render page correctly, please read the page content below
CUSTOM FIREPLACES Troubleshooting Guide Copyright © 2021 Travis Industries Certified Factory Training Program
DaVinci Troubleshooting Guide Page 2 Table of Abbreviations ................................................................................................................................................. 3 Overview ...................................................................................................................................................................... 3 Sequence of Operation ................................................................................................................................................ 4 Sequence of Operation - Flow Chart ........................................................................................................................... 5 Troubleshooting Steps ................................................................................................................................................. 6 TouchSmart ............................................................................................................................................................... 10 GreenSmart Troubleshooting - Flow Chart ................................................................................................................ 11 GreenSmart Troubleshooting Cont. ........................................................................................................................... 13 Continuity Testing Gas Valve ................................................................................................................................. 13 Voltage Testing Gas Valve ..................................................................................................................................... 13 Gas Pressure Testing ............................................................................................................................................. 13 SIT Base IFC ............................................................................................................................................................. 14 DaVinci Parts ............................................................................................................................................................. 15 Power Distribution Board ........................................................................................................................................... 18 Where to look for cause of blown fuse(s) .................................................................................................................. 18 DaVinci Aux Power Board Indicators ......................................................................................................................... 19 User Interface Configuration ...................................................................................................................................... 20 Configuration .............................................................................................................................................................. 20 There are 2 configurations – each with its own operating instructions ...................................................................... 20 There are 2 Control Configurations ........................................................................................................................... 20 Wiring Diagram – Pre-TouchSmart............................................................................................................................ 21 Wiring Diagram - TouchSmart® - Pre-Master Power Switch ............................................................................... 22 Wiring Diagram - TouchSmart® - Power Switch .................................................................................................. 23 LED Wiring Diagram – Pre-TouchSmart.................................................................................................................... 24 17601900 - 6/9/21
DaVinci Troubleshooting Guide Page 3 Table of Abbreviations IFC Integrated Fireplace Control TS TouchSmart DPB Power Distribution Board (PDB) AUX Auxiliary Power Board (AUX) (Red (Green Board) Board) APS Air Pressure Switch REO Rheostat ODAM Exhaust Damper XMF Transformer IDAM Intake Damper Overview The DaVinci fireplace has been programmed to have the power exhaust fan purge the firebox when power is introduced to the unit. This purge will last 6 minutes. You do not have to wait for the purge to end to start the fireplace. The purge process will occur after the initial power up and after any power outage. The fireplace controls consist of a power distribution control board (PDB) and a base Integrated Fireplace Control (IFC) in addition to the power exhaust fan. Additionally, there are intake damper(s) and an exhaust damper that is controlled by the PDB. When the fireplace is turned on there is a 10-second delay followed by a 30-second pre- purge. The Flame Icon LED on newer TouchSmart® Wall Controls (TS) will pulse for approximately 50 seconds to show that the unit is in start-up mode. During the delay, the exhaust and intake dampers open followed by the power exhaust fan. During the pre-purge, the draft produced by the power exhaust fan will activate an air pressure switch (APS) signaling to PDB that the fan is operating. After the pre-purge, the IFC will send the signal to initiate the start-up sequence. The pilot and burner for this fireplace function the same as with all other GreenSmart™ 2 (GS2) appliances. A rheostat controls the speed of the power vent. For 30 seconds the rheostat is bypassed sending line voltage to the power exhaust fan. After the purge, the PDB sends the power through the rheostat lowering the speed of the power exhaust fan to normal operating speed. When the fireplace is turned off the burner and pilot turn off. The power exhaust fan, intake, and exhaust dampers remain engaged for 6 minutes (post-purge). After post-purge the power exhaust fan turns off, the intake and exhaust dampers close, and the APS switch opens. The dampers will remain closed until a start sequence is initiated or if power is lost and reinstated (goes into pre-purge then to ready state). In the event of a power failure, the exhaust damper will fail “OPEN”. 17601900 - 6/9/21
DaVinci Troubleshooting Guide Page 4 Sequence of Operation 1) Power Application a. Applying 120 volts to the system (plugging in, or return of power from an outage). 2) “Power Pre-Purge” (6-minute duration) a. 24 Volts applied to (1) exhaust damper and intake damper(s). b. Rheostat voltage is applied to the Power Exhaust Fan, Air Pressure Switch closes from pressure in the flue. 3) Post “Power Pre-Purge” (after 6 minute Pre Purge) a. Voltages removed from all Dampers and Fan(s), system in “Ready” mode (Green LED in the center of Power Distribution Board [PDB]). 4) Switch signal “ON” - Call for FLAME a. 24 Volts applied to Exhaust Damper and Intake Damper(s). b. The green LED light (in the center of the Power Distribution Board [PDB]) turns Yellow/Orange. c. After a 10 second delay, the rheostat shunt actuates for 30 seconds sending 120 volts to Power Exhaust Fan. d. Pressure Switch closes from Pressure in the flue. 5) On units with TouchSmart® controls, the Wall Control goes to sleep after 15 seconds. The flame icon LED will pulse for approximately 50 seconds on newer controls. 6) After 40 seconds the Rheostat kicks in and the Power Exhaust Fan is ramped down. 7) Spark at Pilot (15+ seconds) (Dampers/Fan continue to run) 8) Integrated Fireplace Control (IFC) allows gas to the Pilot 9) Flame at Pilot 10) IFC senses rectification of Pilot and allows gas to Burner 11) Flame at burner 12) Switch signal “OFF” (any point while burning) 13) Burner and Pilot flame turn off 14) Post-Purge (6 minutes) a. Exhaust Damper and Intake Damper(s) remain open. b. The Power Exhaust Fan continues to operate. 15) End of Post Purge (after 6 minutes) return to “Ready” state a. Voltages removed from all dampers and fans, b. Air Pressure Switch opens from lack of pressure (or draft) in the flue. c. The system is now in “Ready” mode. d. LED light (in the center of the Power Distribution Board [PDB]) is green. 17601900 - 6/9/21
DaVinci Troubleshooting Guide Page 5 Sequence of Operation - Flow Chart DaVinci Troubleshooting The DaVinci Fireplace is different from a naturally vented appliance, there are several processes that take place simultaneously. This is important to remember when troubleshooting these fireplaces. When the fireplace is switched on or the call for flame is made, these (3) things happen almost simultaneously: 1) Exhaust damper opens 2) Intake damper opens (if installed) 3) After 10 seconds the Power Exhaust Fan starts Next, the APS activates and approximately 40 seconds after the call for flame the rheostat takes control of the exhaust fan. 17601900 - 6/9/21
DaVinci Troubleshooting Guide Page 6 Troubleshooting Steps Is the GREEN “Ready Light” a. Is the main breaker on? on? b. Is the main power switch turned off? XMF Fuse c. Is there a service switch on the main power line? Is it on? d. Is the unit wired correctly? (Incoming power to power in, not power to power vent) Ready Light e. Check the transformer fuse (labeled XMF) on the PDB (see #1 on Diagram A, on page 18). Replace as needed (1 amp) f. Check input power to the transformer- Line Voltage g. Check output voltage from the transformer - 24 VAC a. Can you hear the fan or feel the vacuum? Does the Power Exhaust Fan (You will need someone at the Power Exhaust Fan to verify) come on at initial power up or b. Check the incoming power (see above). call for flame? c. Is ODAM light on? The fan may not initialize until resolved (see next page). d. Is the fan wired properly? REO Fuse FAN Fuse e. Check fuses on PDB labeled “FAN” or “REO”. Replace as needed (6.3 amp SLO-BLO). f. Check voltage to the Power Exhaust Fan - Should be Line voltage during purge. g. What color is the LED in the center of the PDB? Green = Ready Yellow/Orange = Call for Flame Red = Fault No light = No power or dead PDB, blown transformer fuse, or bad AC transformer. At initial power up or switch a. The pilot trying to light immediately upon powering up with or without the “ON”, Does the PILOT start exhaust fan operation typically means that there is a short in the junction sparking immediately? box. b. Pinched wire, short, reversed wiring, etc. c. The IFC is bad and will need to be replaced after the short is found. 17601900 - 6/9/21
DaVinci Troubleshooting Guide Page 7 a. Check fuses labeled ODAM & IDAM on the PDB (see diagram). These fuses are in series so a problem in either the intake or exhaust damper circuits could cause a fuse to blow. Replace as needed (1 Amp). b. Verify the damper blade operation. Check for obstruction in the vent blocking the damper blade. c. Disconnect the square Molex connector from the interior side of the electrical junction box. Check continuity between the RED and BLACK wires to the exhaust damper. If no continuity either the exhaust damper is closed, broken, damaged wiring, or the microswitch is bad. Jump the RED and BLACK wires and try starting the fireplace. If the fireplace operates properly the problem is outside the firebox. See the list of possible causes below*. *OTHER POSSIBLE CAUSES RED and BLACK wires reversed or shorted together, in the exhaust damper wiring harness causes the damper to open during pre-purge of the initial power on. At the end of the purge or end of burn if a call for flame was Is the ODAM light on the PDB initiated before the end of the pre- RED? purge the damper will close and This may keep the exhaust fan will not reopen unless power is from operating at startup. removed. With the 10 sec. delay the PDB, the damper will close during the delay and will not ODAM Fuse reopen unless power is removed. BROWN and BLACK wires IDAM Fuse reversed or shorted in the exhaust damper wiring harness causes ODAM Light the exhaust and/or intake damper fuses to blow. If 6.3 amp fuses are installed and the short still exists, the fireplace will not operate and the PDB may exhibit all LED lights blinking or some other random pattern. ODAM fault - If fuses are good, jump the RED and BLACK wires in the Exhaust Damper harness. If the fault continues check intake/exhaust damper fuses and replace them as necessary. If the fuses are okay, disconnect the intake damper wires (even if there is no intake damper in the system). If the fault goes away the problem is in the intake damper wires. Intermittent operation with 0-DAM Fault generally means a loose connection in the junction box of the Exhaust Fan/Damper or a loose pin in a Molex connection somewhere in the Exhaust Damper wiring harness circuit. 17601900 - 6/9/21
DaVinci Troubleshooting Guide Page 8 a. Turn up the speed of the fan. b. Is the Power Exhaust Fan operating? Can you feel a vacuum in the Is the APS LED light on the PDB fireplace? Do you feel air blown into the firebox? RED? c. Check continuity of the APS switch. d. Check for cracked, kinked, or missing hose from APS to copper tubing. e. Check for blocked or damaged copper tubing in the flue. f. Did copper tubing get inserted into venting above “T” or Plenum (if applicable). Not into flue collar? Is copper tubing kinked? APS Light g. Is the APS light on and is there is a green “ready state” light or red fault light or is just the red APS light on? The APS is sensing a draft when there is not supposed to be a draft. In other words, the fan is on when it should not be. h. Check continuity on the yellow and blue wires between the PDB and the APS. Replaces spades as needed. i. Check for 5 VDC - yellow and blue wires to APS and at PDB a. Are there lights on the PDB? (If not see the first section) b. Is the exhaust damper opening? c. Is the damper blade obstructed? d. Check fuses labeled ODAM and IDAM on the PDB (see #4 and #5 on diagram A on page 18). These fuses are in series and so a problem in The intake damper does not either the intake or exhaust damper circuits could cause a fuse to blow. open. Replace as needed (1 amp). e. Check voltage to the intake damper – 24 VAC. If the voltage is not correct, look for damage to the wires (for example a nail or staple through the harness). f. If the voltage is correct and the damper only opens with an assist, replace it. a. Is the Rheostat set at high? b. Check voltage to the Power Exhaust Fan? Does the Power Exhaust Fan never slow down at the end of o Does it adjust up or down? If no, replace rheostat. the startup purge? o Check PURPLE wire & ground – Line voltage o Check BLACK wire and ground – rheostat output c. Is intake duct sized right? a. Is the Rheostat turned off? b. Check fuses on PDB labeled REO and FAN (see #2 & #3 on Diagram A Does the Power Exhaust Fan page 18). (6.3 amp). turn off 30/40 seconds after the c. Check voltage from PDB to Rheostat. If no voltage then replace PDB. call for flame? PURPLE wire & ground – Line voltage d. Check voltage to the Power Exhaust Fan? If no voltage then replace rheostat. BLACK wire and ground – rheostat output a. Wrong size fuse (probably the 6.3 amp) installed in the intake or exhaust Do all the lights flash or are all damper slot on the PDB. the lights on the PDB? b. Short in wiring to intake or exhaust damper or crossed wire in harness (see Other Possible Causes). If the transformer fuse continues to blow after being replaced there is probably a short in the exhaust damper or intake damper wiring. Is the Transformer Fuse blown? Disconnect both harnesses, replace the fuse, and then plug either one back in. If the fuse blows, the problem is in that circuit. If the fuse doesn’t blow, repeat with the other circuit. 17601900 - 6/9/21
DaVinci Troubleshooting Guide Page 9 a. PRE-TOUCHSMART - Check voltage at the on/off switch. 5VDC. If no voltage present the Over Heat snap disc has opened or failed. TOUCHSMART - Is the flame icon lit? If yes, check the AUX. board for a green light indicating a call for flame. Check the “Ready” light on the PDB. If the “Ready” light is GREEN and the “Flame Relay” light on the AUX. Does the unit burn normally and Board is lit, check continuity of the RED wire between the 2 boards. No then suddenly shut down continuity = check the snap disc. (typically after 2 hours or more), b. Is there too much media on the burner and media trays? Is it the correct or is the Glass Overheating? media? Is it placed properly? c. Is the Intake Damper Open? d. Is the intake duct restricted or crushed? e. Is the exhaust restricted? f. Can you turn the rheostat up to increase the fan speed? a. Is there a green LED light on the LED power supply/ transformer? If no check incoming power to the unit and transformer. b. Check the voltage out of the transformer – black and white wire 24 VDC. Do the LED lights work? c. Check voltage at the wall switch? Heavier gauge Red and Black wires – 24 Slide Controls? VDC d. Check voltage from lighter gauge wire between BLACK and RED, BLUE, GREEN – 24 VDC e. Check individual Molex connections on LED strips. a. Is there a green LED light on the LED power supply/transformer? If no, check incoming power to the unit and transformer. Do the LED lights work? b. Check the voltage out of the transformer – GREEN and RED wire 24 VDC. TouchSmart c. Are the Touch Pad and Aux Board communicating? Quick green communication Status Light (see page 24) d. Verify connections at Aux Board, Junction Box, and LED Strips. If the unit sparks and there are no fault codes see the GreenSmart Troubleshooting steps on the following pages. 17601900 - 6/9/21
DaVinci Troubleshooting Guide Page 10 TouchSmart Notes: A RED flashing light on the Auxiliary Board and the back of the Wall Control or User Interface is a good thing. This means that the two boards are operating properly. All white LEDs that cannot be changed, indicate that the Auxiliary Board does not have power. 1. Check the fuse on the Auxiliary Board (6.3 Amp) 2. Verify power to the Auxiliary Board. See page 19 for additional diagnostic lights. Transient Voltage Do all lights on the TouchSmart wall control blink and does the Ready light on PDB turn GREEN? Add transient voltage suppressor (250-05407) to system No Lights on TouchSmart Control See above Check CAT cable between wall control and Aux. Board. Aux. Boards and TouchSmart Controllers must be compatible versions. Auxiliary Board Firmware Versions Firmware Versions 1.0 to 1.3 (obsolete) 1.5 and Higher Firmware Versions TouchSmart Not Compatible Controller 1.0 to 2.2 Firmware Versions 2.3 or Higher Not Compatible Serial Number Range for Control Versions Version Notes SN Range Analog Use the switch and LED slider 3501-000000 TouchSmart V1a Controller “wakes up” when touched without changing settings (unless it is a long touch) 3501-001433 TouchSmart V1b Controller flashes when touched and will continue to flash during the startup cycle 3501-002989 17601900 - 9/1/21
DaVinci Troubleshooting Guide Page 11 GreenSmart Troubleshooting - Flow Chart 17601900 - 6/9/21
DaVinci Troubleshooting Guide Page 12 17601900 - 6/9/21
DaVinci Troubleshooting Guide Page 13 GreenSmart Troubleshooting Cont. Continuity Testing Gas Valve Disconnect wires for continuity test 340 +/- 15 Ω Diagram B Voltage Testing Gas Valve A = Pilot Coil B = Burner Coil 5v .9v 5 volts for 1 sec. Stabilizes at about 0.9volts B A A&B Diagram C Gas Pressure Testing Manifold Pressure Test Port Incoming Diagram C Pressure Test Port 17601900 - 6/9/21
DaVinci Troubleshooting Guide Page 14 SIT Base IFC 3.15A F USE Diagram E 17601900 - 6/9/21
DaVinci Troubleshooting Guide Page 15 DaVinci Parts TouchSmart® Service Kit 94400042 Master Power On/Off Main 250-05502 Harness SIT Base IFC 250-05257 Power 250-03402 Distribution Board Valve, DaVinci NG 250-03400 Transformer 250-03403 17601900 - 6/9/21
DaVinci Troubleshooting Guide Page 16 Air Pressure Switch 250-03405 Maestro (36x48, 36x58, and 48x48) 250-04275 Pilot Assembly 250-04275 Snap Disc 250-03415 Fuse 6.3 amp 250-03576 Fuse 1 amp 250-03982 LED control switch 250-03577 Decora Switch 250-00778 LP Regulator 250-00778 Natural Gas 250-04490 Regulator 17601900 - 6/9/21
DaVinci Troubleshooting Guide Page 17 Rheostat 250-03401 LED Power 250-04942 Supply/Transformer Auxiliary Control 250-05158 Board CUSTOM FIREPLACES TM CUSTOM FIREPLACES TM White Heat H O U H O U Exchanger Wall 250-05154 R S R S Control White Timer Wall 250-05156 Control Lights Color Heat Lights Color Timer CUSTOM FIREPLACES TM CUSTOM FIREPLACES TM Black Heat H O U H O U Exchanger Wall 250-05155 R S R S Control Black Timer Wall 250-05157 Control Lights Color Heat Lights Color Timer Transient Voltage 250-05407 Suppressor 17601900 - 6/9/21
DaVinci Troubleshooting Guide Page 18 Power Distribution Board FUSES LED LIGHTS XMF Transformer (1 amp) APS Air Pressure Switch REO Rheostat (6.3 amp Slow Blow) ODAM Exhaust Damper FAN Power Exhaust Fan (6.3 amp Slow Blow) FAN-OD Power Exhaust Fan/Exhaust Damper ODAM Exhaust Damper (1 amp) FLAME Flame GREEN = Ready IDAM Intake Damper (1 amp) READY Red = Fault Yellow/Orange = Call for Flame Where to look for the cause of blown fuse(s) Fuse Size Where to look Aux. Board 6.3 amp Overhead lights Dehumidifier Heat Xchanger Main Power Fan* 6.3 amp Wired Incorrectly Main Power Possibly Bad Fan Rheostat* 6.3 amp Wired Incorrectly Main Power Possibly Bad Fan Intake Damper** 1 amp Short in wiring Bad Motor Wires connected together Exhaust 1 amp Short in wiring Bad Motor Damper** Short in wiring to Bad AC Transformer 1 amp intake or exhaust Bad Damper Motor Transformer damper * Remember the Fan and Rheostat fuses are in series ** Remember the Intake and Exhaust Damper fuses are in series 17601900 - 6/9/21
DaVinci Troubleshooting Guide Page 19 DaVinci Aux Power Board Indicators PCB Rev A01 Doc Rev 101 17601900 - 6/9/21
DaVinci Troubleshooting Guide Page 20 User Interface Configuration Configuration With the UI face down, locate the configuration terminals as shown below. The placement of jumpers on these terminals will change the function of the controls on the board. Function Open Jumped Notes A Timer / Heat Exch Timer Heat Exchanger Jumper is factory installed. B Overhead Lights Overhead Lights No Lights May need to install/remove jumper. C Not Used Examples: This configuration is for a heat This configuration is for a timer with This configuration is for a timer with exchanger with overhead lights no overhead lights. overhead lights. A A A B B B C C C There are 2 configurations – each with its own operating instructions The DaVinci fireplace has gone through several configurations. Give this instruction sheet to the end-user and review fireplace operation with the end-user to make sure they are familiar with all the features. There are 2 Control Configurations YES Is Jumper B NO in Place? Version 1 Control Overhead Light Configuration Configuration 17601900 - 6/9/21
DaVinci Troubleshooting Guide Page 21 Wiring Diagram – Pre-TouchSmart Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. Warning: Do not disconnect or alter the air pressure switch wiring. This is a safety component that is critical to the safety of this fireplace. 17601900 - 6/9/21
DaVinci Troubleshooting Guide Page 22 Wiring Diagram - TouchSmart® - Pre-Master Power Switch Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. Warning: Do not disconnect or alter the air pressure switch wiring. This is a safety component that is critical to the safety of this fireplace. 17601900 - 6/9/21
DaVinci Troubleshooting Guide Page 23 Wiring Diagram - TouchSmart® - Power Switch Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. 120 VAC 120 VAC Main Power M Power In Power In Green White Switch Black 120 VAC Power 3.15A F USE (several components inside fireplace) Primary Flame Spark Rod Base Detect Integrated Fireplace Control (IFC) Intake Dampers Black Yellow / Green Black Power In 120 VAC Air Category 2 Gray White 24 Volt AC Pressure Switch Orange Transformer 3.15A F USE Yellow Green B la ck Whi te Fuses* Secondary Base Brown (see below) Blue Yellow Integrated Fireplace Wh ite Gr ee n B la ck Blue Blue Blue F-OUT Control (IFC) Black F-IN Blue Black Power Dist. Board Pu rple Wh ite Red (Green Board) * Fuse Layout Exhaust Damper (6.3 Amp.Sl.Bl.) (6. 3 Amp.Sl.Bl.) Power Exhaust (1 Amp) Ex. Rheostat T ransformer (1 Amp) Fireplace Junction Box Intake Damper Bla ck (1 Amp) Re d Bl ac k Red Blue Wh ite Black Brown Exhaust Fireplace Junction Box Exhaust Damper Exhaust Blower Damper Thermodisk Wire Harness Junction Box Capacitor Optional 120 VAC Heat Exchanger Power In Optional De-Humidifier 24 Volt DC CUSTOM FIREPLACES TM Gre en Optional Bla ck Bla ck Transformer Blu e H Bla ck Overhead Lights Red Pin k O U R S Bla ck Black Wh ite Gre e n Wh ite Gre e n Auxiliary Board LED Power (Red Board) Light Lights Color Tim er Exhaust Blower Exhaust 120 VAC Strips Touch Junction Box Power In Screen 17601900 - 6/9/21
DaVinci Troubleshooting Guide Page 24 LED Wiring Diagram – Pre-TouchSmart 17601900 - 6/9/21
DaVinci Troubleshooting Guide Page 25 NOTES 17601900 - 6/9/21
DaVinci Troubleshooting Guide Page 26 NOTES 17601900 - 6/9/21
You can also read