Air Cooler/Brine Model DDB Unit Cooler Model DDX 61217 Directions for use Asarums Industri AB Tel: +46 454 334 00 Södra Industrivägen 2 – 4 Fax:+46 454 320 295 SE – 374 50 Asarum Sweden 1
Air Cooler/Brine Model DDB Unit Cooler Model DDX Declaration by the Manufacturer, Annex II B As defined by the EC Machinery Directive (MD) 98/37/EC, the Low Voltage Directive (LVD) 2006/95/EC and the EMC Directive 2004/108/EC. Type of machinery Heat Exchangers supplied with direct cranking fans Productdescription Unit Coolers Antarctic, EVFI, EVDL, DDX Air cooled Condensers CPS, CPM, DCP Air Coolers Antarctic, CBFI, CBDL, DDB Dry Coolers XPS, XPM, XP, DXP developed and designed in accordance with the MD 98/37/EC, LVD 2006/95/EC and EMC Directive 2004/108/EC on the own responsibility of: Company Asarums Industri AB S. Industrivägen 2-4 SE 374 50 ASARUM Sweden Harmonized Standards: EN ISO 12100-1:2003 EN 61000-6-1 EN ISO 12100-2:2003 EN 61000-6-2 EN ISO 13857:2008 EN 61000-6-3 EN 60204-1:2006 EN 61000-6-4 EN ISO 4871 The product is not allowed to put in operation until the machine or system, which it is to be incorporated or which it is to be a part of, is in accordance with the Machinery Directive 98/37/EC. The compliance with EMC Directive 2004/95/EC is valid if the product is connected directly to the main supply. If the product is integrated in a system or combined with other products (e.g. other controllers) the system manufacturer is responsible for compliance with EMC Directive 2004/95/EC for the complete system. Date : 2008-12-04 Signed by : Tord Engberg Title: R&D Manager Asarums Industri AB Tel: +46 454 334 00 Södra Industrivägen 2 – 4 Fax:+46 454 320 295 SE – 374 50 Asarum 2 Sweden
Air Cooler/Brine Model DDB Unit Cooler Model DDX INDEX P Summary Description 4 Receiving of Goods 5 Designation System 6 Installation 7 Maintenance 11 Asarums Industri AB Tel: +46 454 334 00 Södra Industrivägen 2 – 4 Fax:+46 454 320 295 SE – 374 50 Asarum Sweden 3
Air Cooler/Brine Model DDB Unit Cooler Model DDX Summary description General description The product is suitable for cold-storage rooms in industrial plants. The cooler is designed to be mounted close to the ceiling This will reduce the risk of icing on the upper side of the product. The coolers is provided with axial fans, and the casing is made of plain plastic protected aluminium plate. Electric heating rods, drip pan coils are 1-phase 230 V and 2-phase 400 V. Important! Avoid unnecessary opening of doors to cold-storage rooms. Hot air flowing into the room can cause icing on the finned coils. Free air circulation within the cold-storage room is necessary in order to obtain maximum cooling effect. The finned surfaces should be clean and free from dust and ice. 6 1 2 6 5 4 3 3 Pos Description Pos Description 1 Bracket 4 Junction box (fan) 2 Cooling coil 5 Axial fan 3 Drip pan 6 Assembly pan for condensate water Asarums Industri AB Tel: +46 454 334 00 Södra Industrivägen 2 – 4 Fax:+46 454 320 295 SE – 374 50 Asarum 4 Sweden
Air Cooler/Brine Model DDB Unit Cooler Model DDX Receiving of Goods and Mounting Before leaving the factory the product went through a thorough control of quality and serviceability. If the product, in spite of this control, should be defective or damaged due to transportation, the sales and transporter representative should be contacted immediately. 1 2 The product should be transported to and placed in its designated place before removing the straps. Cut off the stripes (1) and remove the lid (2) of the packing. Lift up the product onto the enclosed pallet with the intended hoist (3). Mount the product in the factory-assembled brackets (4). 4 Lower the pallet (packing) with the hoist (3). 3 Asarums Industri AB Tel: +46 454 334 00 Södra Industrivägen 2 – 4 Fax:+46 454 320 295 SE – 374 50 Asarum Sweden 5
Air Cooler/Brine Model DDB Unit Cooler Model DDX Designation System DDB 45 2 A 3F 1400 2 X DDX Standard optional extras Circuits Fan speed Fin pitch - 4/7 Number of rows in deep Module typ Number of modules Fan diameter Model code Asarums Industri AB Tel: +46 454 334 00 Södra Industrivägen 2 – 4 Fax:+46 454 320 295 SE – 374 50 Asarum 6 Sweden
Air Cooler/Brine Model DDB Unit Cooler Model DDX Installation The installation instructions below should be read together with the brochure containing the technical description. Location of coolers It is very important to place the product according to the minimum measures below. This is due to air circulation and the possibility to maintain service. N.B. Remember to remove the protective plastic from all products prior to starting. To be able to change the electric heating rods a minimum distance of E + 200 mm must be kept. E E + 200 mm 2000 750 Air direction Air direction Asarums Industri AB Tel: +46 454 334 00 Södra Industrivägen 2 – 4 Fax:+46 454 320 295 SE – 374 50 Asarum Sweden 7
Air Cooler/Brine Model DDB Unit Cooler Model DDX Assembly of Droplet Guard The droplet guard is only delivered with models performing 1400 rpm (4P/4DY). The droplet guard is delivered retracted. Remove the bolts (1). Loosen the bolt (2) and lower the droplet guard. Tighten the bolts when the droplet guard is in position (3). 2 1 3 3 Asarums Industri AB Tel: +46 454 334 00 Södra Industrivägen 2 – 4 Fax:+46 454 320 295 SE – 374 50 Asarum 8 Sweden
Air Cooler/Brine Model DDB Unit Cooler Model DDX Installation The installation should only be carried out by authorised personnel according to national standards. Connection of fan 1 DDB/DDX is connected as follows: 2 Remove the screws (1) with a screw driver and remove 3 the cap (2). Cable is connected through fitting (3) on the bottom side of the cover. Connect according to attached electrical wiring diagram Fit the cable as the pictures. 4 Connection of electric heating DDB/DDX has screws (4) on the hatch. Insert the cable at the upper edge on the long side and connect the electric heating I to the junction box. 1.0 Setting of overload protection The diagram shows the setting of overload at different room temperatures. Motor rating data 0.9 according to product sign at -30°C. E.g. at a room temperature of 0°C. 0.8 The setting of the engine guard –30 –10 +10 °C = 0,9 x I rating data –20 0 Asarums Industri AB Tel: +46 454 334 00 Södra Industrivägen 2 – 4 Fax:+46 454 320 295 SE – 374 50 Asarum Sweden 9
Air Cooler/Brine Model DDB Unit Cooler Model DDX Installation Pipework installation of DDB 1 The cooler should be filled with correct type 3 and quantity of freezing coolant recommended by the installation engineer. The connection pipes are placed on one of the short sides. Open the hatch, see page 9. Air vents are placed on the high point of the collecting pipe (1). 2 Connect in-coming flow on pipe (2). Connect return flow on pipe (3). Make sure that the drain pipe is connected to the assembly pan before ventilation of the pipe system is carried out. Pipework installation of DDX 5 4 The product should be filled with the quantity and kind of refrigerant stated by the installation engineer. The connection tubes are situated on one of the short sides. Open the hatch see page 9. Connect expansion valve on pipe (5). Connect suction gas on pipe (6). 6 Schrader valve for reading evaporator pressure. 7 Connection of drain tray DDX/DDB module A Connect the condensate hoses (7) to the plain connections (8) with hose clamps. Specified dimensions see the technical brochure. Connection of drain tray DDX/DDB module B/C. 8 Connect the condensate hose (7) to 9 connection (9). Specified dimensions see the technical brochure. 7 . Asarums Industri AB Tel: +46 454 334 00 Södra Industrivägen 2 – 4 Fax:+46 454 320 295 SE – 374 50 Asarum 10 Sweden
Air Cooler/Brine Model DDB Unit Cooler Model DDX Maintenance Caution! Make sure the current is 2 switched off. Dismounting the fan 3 Disconnect the electric connection in the 1 junction box on the fan. Remove the bolts (1) (4 ea) including washers and unfasten the fan (2). Standstill In case of a longer standstill the fans should Mounting the fan be run at least once a month. The fans Put in the screws loosely including the should be run until the motor has reached washers in all four holes (3). Tighten operating temperature - approximately the screws. 15 minutes. N.B. There is a fan-shaped washer between envelope and fan grille. Electric defrosting of DDB/DDX Change of drip pan heating Electric heating rods and drip pan coils Disconnect the electric cables from the are 1-phase 230 V and connected to box. Remove the junction box on the side of the cooler plates (6) which hold the heating coil. according to separate wiring diagram. Assemble the heating coil in reverse order. The electric rods are made of stainless steel. Change of electric heating rod Change of assembly pan heating Disconnect the electric cables from Disconnect the electric cables from the the junction box. Remove the junction box. lock washer (4) and pull out the heating Remove the screws to the aluminium rod (5). Assemble the heating plate which hold the heating coil. rod in reverse order. Assemble in reverse order. 4 6 5 Asarums Industri AB Tel: +46 454 334 00 Södra Industrivägen 2 – 4 Fax:+46 454 320 295 SE – 374 50 Asarum Sweden 11
Air Cooler/Brine Model DDB Unit Cooler Model DDX Maintenance Caution! Make sure the current is switched off Cleaning of cooling element/coil Loosen the bolts (M6) in the shackle lock and pull out the shackles and lower the drip pan and the drip plate. Clean the drip pan, the drip plate and the cooling element with water and non-polluting detergent which does not corrode aluminium or copper. Check that the drain pipe is not clogged. Rinse and leave to dry. Assembly of drip pan and drip plate Push up the drip pan and insert the shackle locks in the notch and fasten them. Caution! Always use protective gloves when cleaning or working with the fin surface. Asarums Industri AB Tel: +46 454 334 00 2009-02-10 Södra Industrivägen 2 – 4 Fax:+46 454 320 295 SE – 374 50 Asarum 12 Sweden