PLH Aria Jellyfish cod. A.JF Bluetooth controllable, Casambi enabled, 4 input 4 output interface, with feedback led and multivoltage power supply. It can be connected, only by qualified professionals. Can be controlled via PLH Aria keypads, and with Casambi app available for iOs (iPhone 4S or later, iPad 3 or later, iPod Touch 5th gen or later) and Android devices (Android 4.4 KitKat or later devices produced after 2013 with full Bluetooth 4.0 support). Drawings and measures Technical specifications Electrical input specs Firmware: Voltage range and frequency AC | DC: 90 - 250V (0,5 VA) | 12-30V DC (1W) 5081 Output: 4 Switch (relais bistable) - 0 Push button (relais monostable) Input: 4 dry contact Input Dry contact 4 NO to ground and pass through 5082 Output: 3 Switch (relais bistable) - 1 Push button (relais monostable) Output Input: 4 dry contact Transistor 4 (100mA and 30V DC max); open-collector to ground; control of inductive load allowed 5083 Output: 2 Switch (relais bistable) - (with relays) 2 Push button (relais monostable) Input: 4 dry contact Feedback 5084 Output: 1 Switch (relais bistable) - Led white (output) and blue (input) on board 3 Push button (relais monostable) Input: 4 dry contact Radio transceiver Maximum output power: 2,4...2,483 Ghz +4 dBm 5085 Output: 0 Switch (relais bistable) - Ambient temperature, ta: -20...+45 °C 4 Push button (relais monostable) Max. case temperature, tc: +65 °C Input: 4 dry contact Max. relative humidity: 0...80%, non-cond. Range (depending on the surrondings) up to 15 m 5975 Output: 4 Pwm Input: 4 dry contact Wiring Wire range, solid & stranded: interface si provided with precutted 5 cm wires 0,5 mm2 16 AWG Mechanical data Dimensions: 50,0 x 50,0 x 40,0 mm Weight: 50 g Degree of protection: IP67 © 2017 - epic srl - All rights reserved - Subject to technical change - Check periodically the website Doc. DS_A.JF rev. 1.0
Installation Make sure that the mains voltage is switched off when making any connections. Use right connectors or seal butt slice to join the jellyfish interface to the electric wires of the plant.. If you install the interface into a heat sensitive environment (i.e. inside a luminaire or in a ceiling outlet box above a luminaire), make sure that the ambient temperature does not exceed the specified maximum value. Wiring Insulate the not used wires. Use the right connectors for the connections, not included, like Perma-Seal Butt Slice (Molex 19164-0013) or Wago 221, 243 or 2273 series. Common (-) 3a 4a Common (-) Output 4 3b 4b Input 4 Output 3 3c 4c Input 3 Output 2 3d 4d Input 2 Output 1 3e 4e Input 1 Common (+) 3f Input 1 2a Input 2 2b Input 3 2c Input 4 2d Common (-) 2e 90-250V AC Neutral 1a 90-250V AC Phase 1b Perma-Seal Butt Slice Molex 6a Max 30V DC (+) 6b Max 30V DC (-) Wago 221 Warning! ! Hazardous voltages. Risk of electric shock or fire. Only qualified professionals should make the connections in accordance with the local regulations and rules. Disconnect the mains power supply and verify its absence prior to installation. © 2017 - epic srl - All rights reserved - Subject to technical change - Check periodically the website Doc. DS_A.JF rev. 1.0
Example 1: connection with BUS dry contact interface Gira 1119 00 Konnex interface In this solution you can control directly, using a PLH Aria keypad or a smartphone, a KNX bus system via a bus dry contact interface. Power supply need to be granted (230V AC or maximum 30V DC using the right wires) Refer to Gira Interface specification document for any further information http://download.gira.com/data3/11193290.pdf Firmware 5085 PLH Jellyfish A1/E1 A2/E2 com E3 E4 - + GN RD GY PK YE KNX Bus 90-250V AC Neutral 1a 90-250V AC Phase 1b 6a Max 30V DC (+) 6b Max 30V DC (-) Warning! ! Hazardous voltages. Risk of electric shock or fire. Only qualified professionals should make the connections in accordance with the local regulations and rules. Disconnect the mains power supply and verify its absence prior to installation. © 2017 - epic srl - All rights reserved - Subject to technical change - Check periodically the website Doc. DS_A.JF rev. 1.0
Example 2: connection with BUS dry contact interface Philips LCU2070 DALI interface In this solution you can control directly, using a PLH Aria keypad or a smartphone, a Dali bus system via a bus dry contact interface. Power supply need to be granted (230V AC or maximum 30V DC using the right wires) Refer to Philips Interface specification document for any further information http://www.assets.lighting.philips.com/is/content/PhilipsLighting/a7f5741c4ff54b2c90e4a68f00b8c881 Firmware 5085 PLH Jellyfish DA+ DA - DALI Bus 1 LCU2070/00 2 9137 003 35103 3 4 Made in E.U. 5 PFT yyww 6 90-250V AC Neutral 1a 90-250V AC Phase 1b 6a Max 30V DC (+) 6b Max 30V DC (-) Warning! ! Hazardous voltages. Risk of electric shock or fire. Only qualified professionals should make the connections in accordance with the local regulations and rules. Disconnect the mains power supply and verify its absence prior to installation. © 2017 - epic srl - All rights reserved - Subject to technical change - Check periodically the website Doc. DS_A.JF rev. 1.0
Example 3: connection with BUS dry contact interface C2N-UNI8IO Crestron interface In this solution you can control directly, using a PLH Aria keypad or a smartphone, a Cresnet bus system via a dry contact interface. Power supply need to be granted (230V AC or maximum 30V DC using the right wires) Refer to Crestron Interface specification document for any further information https://www.crestron.com/getmedia/41ce847e-5535-492f-a1df-298812b77537/ss_c2n-uni8io_1 Firmware 5085 PLH Jellyfish 5V 1 2 3 4 5 6 7 8 24V GG 1 2 3 4 5 6 7 8 OUTPUT INPUT Cresnet Bus 90-250V AC Neutral 1a 90-250V AC Phase 1b 6a Max 30V DC (+) 6b Max 30V DC (-) Warning! ! Hazardous voltages. Risk of electric shock or fire. Only qualified professionals should make the connections in accordance with the local regulations and rules. Disconnect the mains power supply and verify its absence prior to installation. © 2017 - epic srl - All rights reserved - Subject to technical change - Check periodically the website Doc. DS_A.JF rev. 1.0
Example 4: connection with BUS dry contact interface QSE-CI-WCI Lutron interface In this solution you can control directly, using a PLH Aria keypad or a smartphone, a Lutron bus system via a dry contact interface. Power supply need to be granted (230V AC or maximum 30V DC using the right wires) Refer to Lutron Interface specification document for any further information http://www.lutron.com/TechnicalDocumentLibrary/369681a.pdf Firmware 5085 PLH Jellyfish QS LINK wiring 12345678 LEDs Contact Closure Inputs 2 (Orange) 3 (Yellow ) 6 (Purple) 4 (Green) 9 (Blac k ) 7 (Gray) 5 (Blue) 1 (Red) 8 90-250V AC Neutral 1a 90-250V AC Phase 1b 6a Max 30V DC (+) 6b Max 30V DC (-) Warning! ! Hazardous voltages. Risk of electric shock or fire. Only qualified professionals should make the connections in accordance with the local regulations and rules. Disconnect the mains power supply and verify its absence prior to installation. © 2017 - epic srl - All rights reserved - Subject to technical change - Check periodically the website Doc. DS_A.JF rev. 1.0
Example 5: connection with relays bistable In this solution you can control directly, using a PLH Aria keypad or a smartphone or a local normally open push buttons (4 in this scheme), relays with coil in extra low tension and contact in 230V (for example Finder 46 series) and 24 V leds. Power supply need to be granted (230V AC or maximum 30V DC using the right wires) Firmware 5083 k1 k2 230V AC Neutral 1a 230V AC Phase 1b 6a 24V DC (+) 6b 24V DC (-) 230V AC Phase k1 k2 load load 230V 230V Finder 46 series 230V AC Neutral Warning! ! Hazardous voltages. Risk of electric shock or fire. Only qualified professionals should make the connections in accordance with the local regulations and rules. Disconnect the mains power supply and verify its absence prior to installation. © 2017 - epic srl - All rights reserved - Subject to technical change - Check periodically the website Doc. DS_A.JF rev. 1.0
Example 6: control of curtains In this solution you can control 2 curtain in 230V AC directly, using a PLH Aria keypad or a smartphone or a local normally open push buttons (4 in this scheme), relays with mechanical interlock with coil in extra low tension and contact in 230V. Power supply need to be granted (230V AC or maximum 30V DC using the right wires) Firmware 5085 k1 down k2 up k3 down k4 up 230V AC Neutral 1a 230V AC Phase 1b 6a 24V DC (+) 6b 24V DC (-) 230V AC Phase M M 1 1 UP DOWN UP DOWN k2 k4 6 3 6 3 6 3 6 3 k1 k3 5 7 4 2 5 7 4 2 5 7 4 2 5 7 4 2 Finder 46 series 230V AC Neutral Warning! ! Hazardous voltages. Risk of electric shock or fire. Only qualified professionals should make the connections in accordance with the local regulations and rules. Disconnect the mains power supply and verify its absence prior to installation. © 2017 - epic srl - All rights reserved - Subject to technical change - Check periodically the website Doc. DS_A.JF rev. 1.0
Example7: control of single channel D-PWM ballast In this solution you can control, using a PLH Aria keypad or a smartphone, a PWM dimmer led. Power supply need to be granted (230V AC or maximum 30V DC using the right wires) Refer to Dalcnet specification document for any further information http://www.dalcnet.com/wp-content/uploads/DLA1248_1CH_ita.pdf Firmware 5975 PLH Jellyfish DC In 12-48V DC (+) DC In 12-48V DC (-) LED 90-250V AC Neutral 1a 90-250V AC Phase 1b 6a Max 30V DC (+) 6b Max 30V DC (-) Warning! ! Hazardous voltages. Risk of electric shock or fire. Only qualified professionals should make the connections in accordance with the local regulations and rules. Disconnect the mains power supply and verify its absence prior to installation. © 2017 - epic srl - All rights reserved - Subject to technical change - Check periodically the website Doc. DS_A.JF rev. 1.0
Example8: control of multi channel D-PWM ballast In this solution you can control, using a PLH Aria keypad or a smartphone, a PWM multi dimmer led. Power supply need to be granted (230V AC or maximum 30V DC using the right wires) Refer to Dalcnet specification document for any further information http://www.dalcnet.com/wp-content/uploads/DLA1224_4CH_ita.pdf Firmware 5975 PLH Jellyfish IN PWM LED BOOSTER DC IN OUT 12-24V DC (+) SINGLE COLOR LED 12-24V DC (-) TUNEBLE WHITE RGBW RGB 6a Max 30V DC (+) 6b Max 30V DC (-) 90-250V AC Neutral 1a 90-250V AC Phase 1b Warning! ! Hazardous voltages. Risk of electric shock or fire. Only qualified professionals should make the connections in accordance with the local regulations and rules. Disconnect the mains power supply and verify its absence prior to installation. © 2017 - epic srl - All rights reserved - Subject to technical change - Check periodically the website Doc. DS_A.JF rev. 1.0