PLH Aria Jellyfish                                                                                                                            cod. A.JF

Bluetooth controllable, Casambi enabled, 4 input 4 output interface, with feedback led and multivoltage power supply. It can be
connected, only by qualified professionals. Can be controlled via PLH Aria keypads, and with Casambi app available for iOs (iPhone 4S
or later, iPad 3 or later, iPod Touch 5th gen or later) and Android devices (Android 4.4 KitKat or later devices produced after 2013 with
full Bluetooth 4.0 support).

Drawings and measures

 Technical specifications

 Electrical input specs                                                                                      Firmware:
 Voltage range and frequency AC | DC:                  90 - 250V (0,5 VA) | 12-30V DC (1W)                   5081       Output: 4 Switch (relais bistable) -
                                                                                                             0 Push button (relais monostable)
                                                                                                             Input: 4 dry contact
 Input
 Dry contact                                           4 NO to ground and pass through                       5082       Output: 3 Switch (relais bistable) -
                                                                                                             1 Push button (relais monostable)
 Output                                                                                                      Input: 4 dry contact
 Transistor                                            4 (100mA and 30V DC max); open-collector
                                                       to ground; control of inductive load allowed          5083       Output: 2 Switch (relais bistable) -
                                                       (with relays)                                         2 Push button (relais monostable)
                                                                                                             Input: 4 dry contact
 Feedback
                                                                                                             5084       Output: 1 Switch (relais bistable) -
 Led                                                   white (output) and blue (input) on board
                                                                                                             3 Push button (relais monostable)
                                                                                                             Input: 4 dry contact
 Radio transceiver
 Maximum output power:                                 2,4...2,483 Ghz +4 dBm                                5085       Output: 0 Switch (relais bistable) -
 Ambient temperature, ta:                              -20...+45 °C                                          4 Push button (relais monostable)
 Max. case temperature, tc:                            +65 °C                                                Input: 4 dry contact
 Max. relative humidity:                               0...80%, non-cond.
 Range (depending on the surrondings)                  up to 15 m                                            5975       Output: 4 Pwm       Input: 4 dry
                                                                                                             contact
 Wiring
 Wire range, solid & stranded:                         interface si provided with precutted 5 cm
                                                       wires 0,5 mm2 16 AWG

 Mechanical data
 Dimensions:                                           50,0 x 50,0 x 40,0 mm
 Weight:                                               50 g
 Degree of protection:                                 IP67

© 2017 - epic srl - All rights reserved - Subject to technical change - Check periodically the website   Doc. DS_A.JF rev. 1.0
Installation
Make sure that the mains voltage is switched off when making any connections. Use right connectors or seal butt slice to join the jellyfish interface to the
electric wires of the plant..
If you install the interface into a heat sensitive environment (i.e. inside a luminaire or in a ceiling outlet box above a luminaire), make sure that the ambient
temperature does not exceed the specified maximum value.

Wiring
Insulate the not used wires. Use the right connectors for the connections, not included, like Perma-Seal Butt Slice (Molex 19164-0013) or Wago 221, 243 or
2273 series.

                                       Common (-) 3a                                                         4a Common (-)
                                         Output 4 3b                                                         4b Input 4
                                          Output 3 3c                                                        4c Input 3
                                         Output 2 3d                                                         4d Input 2
                                         Output 1 3e                                                         4e Input 1
                                       Common (+) 3f

                                          Input 1 2a
                                          Input 2 2b
                                          Input 3 2c
                                          Input 4 2d
                                       Common (-) 2e

                                90-250V AC Neutral 1a
                                 90-250V AC Phase 1b                                                                                 Perma-Seal Butt Slice
                                                                                                                                             Molex

                                                                         6a Max 30V DC (+)
                                                                         6b Max 30V DC (-)

                                                                                                                                            Wago 221

                       Warning!
           !           Hazardous voltages. Risk of electric shock or fire. Only qualified professionals should make the
                       connections in accordance with the local regulations and rules. Disconnect the mains power
                       supply and verify its absence prior to installation.

© 2017 - epic srl - All rights reserved - Subject to technical change - Check periodically the website           Doc. DS_A.JF rev. 1.0
Example 1: connection with BUS dry contact interface Gira 1119 00 Konnex interface
In this solution you can control directly, using a PLH Aria keypad or a smartphone, a KNX bus system via a bus dry contact interface. Power supply need to be
granted (230V AC or maximum 30V DC using the right wires)
Refer to Gira Interface specification document for any further information
http://download.gira.com/data3/11193290.pdf
Firmware 5085 PLH Jellyfish

                                                                                A1/E1
                                                                                A2/E2

                                                                                 com
                                                                                   E3
                                                                                   E4
                                                             -   +
                                                                                GN
                                                                                RD

                                                                                GY
                                                                                PK
                                                                                YE

                                                          KNX Bus

                                           90-250V AC Neutral 1a
                                            90-250V AC Phase 1b

                                                                                  6a Max 30V DC (+)
                                                                                  6b Max 30V DC (-)

                      Warning!
          !           Hazardous voltages. Risk of electric shock or fire. Only qualified professionals should make the
                      connections in accordance with the local regulations and rules. Disconnect the mains power
                      supply and verify its absence prior to installation.

© 2017 - epic srl - All rights reserved - Subject to technical change - Check periodically the website   Doc. DS_A.JF rev. 1.0
Example 2: connection with BUS dry contact interface Philips LCU2070 DALI interface
In this solution you can control directly, using a PLH Aria keypad or a smartphone, a Dali bus system via a bus dry contact interface. Power supply need to be
granted (230V AC or maximum 30V DC using the right wires)
Refer to Philips Interface specification document for any further information
http://www.assets.lighting.philips.com/is/content/PhilipsLighting/a7f5741c4ff54b2c90e4a68f00b8c881
Firmware 5085 PLH Jellyfish

                                                         DA+
                                                         DA -                          DALI Bus
                                                           1
                                        LCU2070/00         2
                                        9137 003 35103     3
                                                           4
                                        Made in E.U.       5
                                        PFT yyww           6

                                       90-250V AC Neutral 1a
                                        90-250V AC Phase 1b

                                                                                6a Max 30V DC (+)
                                                                                6b Max 30V DC (-)

                      Warning!
           !          Hazardous voltages. Risk of electric shock or fire. Only qualified professionals should make the
                      connections in accordance with the local regulations and rules. Disconnect the mains power
                      supply and verify its absence prior to installation.

© 2017 - epic srl - All rights reserved - Subject to technical change - Check periodically the website    Doc. DS_A.JF rev. 1.0
Example 3: connection with BUS dry contact interface C2N-UNI8IO Crestron interface
In this solution you can control directly, using a PLH Aria keypad or a smartphone, a Cresnet bus system via a dry contact interface. Power supply need to be
granted (230V AC or maximum 30V DC using the right wires)
Refer to Crestron Interface specification document for any further information
https://www.crestron.com/getmedia/41ce847e-5535-492f-a1df-298812b77537/ss_c2n-uni8io_1
Firmware 5085 PLH Jellyfish
                                            5V 1 2 3 4 5 6 7 8 24V

                                                                                      GG 1 2 3 4 5 6 7 8
                                                               OUTPUT

                                                                              INPUT

                                                                     Cresnet Bus

                                          90-250V AC Neutral 1a
                                           90-250V AC Phase 1b

                                                                                                           6a Max 30V DC (+)
                                                                                                           6b Max 30V DC (-)

                      Warning!
          !           Hazardous voltages. Risk of electric shock or fire. Only qualified professionals should make the
                      connections in accordance with the local regulations and rules. Disconnect the mains power
                      supply and verify its absence prior to installation.

© 2017 - epic srl - All rights reserved - Subject to technical change - Check periodically the website                         Doc. DS_A.JF rev. 1.0
Example 4: connection with BUS dry contact interface QSE-CI-WCI Lutron interface
In this solution you can control directly, using a PLH Aria keypad or a smartphone, a Lutron bus system via a dry contact interface. Power supply need to be
granted (230V AC or maximum 30V DC using the right wires)
Refer to Lutron Interface specification document for any further information
http://www.lutron.com/TechnicalDocumentLibrary/369681a.pdf
Firmware 5085 PLH Jellyfish

                                                   QS LINK wiring

                                                                               12345678

                                                                                 LEDs

                                                                     Contact Closure Inputs
                                                                         2 (Orange)
                                                                         3 (Yellow )

                                                                         6 (Purple)
                                                                         4 (Green)

                                                                         9 (Blac k )
                                                                         7 (Gray)
                                                                         5 (Blue)
                                                                         1 (Red)

                                                                         8

                                      90-250V AC Neutral 1a
                                       90-250V AC Phase 1b

                                                                                6a Max 30V DC (+)
                                                                                6b Max 30V DC (-)

                      Warning!
          !           Hazardous voltages. Risk of electric shock or fire. Only qualified professionals should make the
                      connections in accordance with the local regulations and rules. Disconnect the mains power
                      supply and verify its absence prior to installation.

© 2017 - epic srl - All rights reserved - Subject to technical change - Check periodically the website    Doc. DS_A.JF rev. 1.0
Example 5: connection with relays bistable
In this solution you can control directly, using a PLH Aria keypad or a smartphone or a local normally open push buttons (4 in this scheme), relays with coil in
extra low tension and contact in 230V (for example Finder 46 series) and 24 V leds. Power supply need to be granted (230V AC or maximum 30V DC using
the right wires)
Firmware 5083

                                                               k1            k2

                                                            230V AC Neutral 1a
                                                             230V AC Phase 1b

                               6a 24V DC (+)
                               6b 24V DC (-)

                              230V AC Phase

                                                k1                  k2

                                                     load            load
                                                     230V            230V                                              Finder 46 series

                             230V AC Neutral

                      Warning!
           !          Hazardous voltages. Risk of electric shock or fire. Only qualified professionals should make the
                      connections in accordance with the local regulations and rules. Disconnect the mains power
                      supply and verify its absence prior to installation.

© 2017 - epic srl - All rights reserved - Subject to technical change - Check periodically the website      Doc. DS_A.JF rev. 1.0
Example 6: control of curtains
In this solution you can control 2 curtain in 230V AC directly, using a PLH Aria keypad or a smartphone or a local normally open push buttons (4 in this
scheme), relays with mechanical interlock with coil in extra low tension and contact in 230V. Power supply need to be granted (230V AC or maximum 30V DC
using the right wires)
Firmware 5085

                          k1 down               k2 up                 k3 down            k4 up

                                                            230V AC Neutral 1a
                                                             230V AC Phase 1b

                 6a 24V DC (+)
                 6b 24V DC (-)

                230V AC Phase

                                                             M                                                          M
                                                            1                                                          1
                                                      UP          DOWN                                            UP        DOWN

                                                                            k2                                                      k4
                                        6               3               6            3               6             3            6            3
                                            k1                                                           k3
                                    5       7     4          2    5         7    4       2       5       7    4        2    5       7    4       2

                                                                                                                                                                         Finder 46 series

               230V AC Neutral

                           Warning!
           !               Hazardous voltages. Risk of electric shock or fire. Only qualified professionals should make the
                           connections in accordance with the local regulations and rules. Disconnect the mains power
                           supply and verify its absence prior to installation.

© 2017 - epic srl - All rights reserved - Subject to technical change - Check periodically the website                                           Doc. DS_A.JF rev. 1.0
Example7: control of single channel D-PWM ballast
In this solution you can control, using a PLH Aria keypad or a smartphone, a PWM dimmer led. Power supply need to be granted (230V AC or maximum 30V
DC using the right wires)
Refer to Dalcnet specification document for any further information
http://www.dalcnet.com/wp-content/uploads/DLA1248_1CH_ita.pdf
Firmware 5975 PLH Jellyfish

                                    DC In 12-48V DC (+)
                                    DC In 12-48V DC (-)
                                                                  LED

                                        90-250V AC Neutral 1a
                                         90-250V AC Phase 1b

                                                                               6a Max 30V DC (+)
                                                                               6b Max 30V DC (-)

                      Warning!
           !          Hazardous voltages. Risk of electric shock or fire. Only qualified professionals should make the
                      connections in accordance with the local regulations and rules. Disconnect the mains power
                      supply and verify its absence prior to installation.

© 2017 - epic srl - All rights reserved - Subject to technical change - Check periodically the website   Doc. DS_A.JF rev. 1.0
Example8: control of multi channel D-PWM ballast
In this solution you can control, using a PLH Aria keypad or a smartphone, a PWM multi dimmer led. Power supply need to be granted (230V AC or maximum
30V DC using the right wires)
Refer to Dalcnet specification document for any further information
http://www.dalcnet.com/wp-content/uploads/DLA1224_4CH_ita.pdf
Firmware 5975 PLH Jellyfish

                                                  IN PWM
                                                           LED BOOSTER

                                     DC IN         OUT

               12-24V DC (+)
                                                                         SINGLE COLOR LED
               12-24V DC (-)

                                                                         TUNEBLE WHITE

                                                                         RGBW

                                                                         RGB

                                                                                                         6a Max 30V DC (+)
                                                                                                         6b Max 30V DC (-)

                                                                         90-250V AC Neutral 1a
                                                                          90-250V AC Phase 1b

                      Warning!
          !           Hazardous voltages. Risk of electric shock or fire. Only qualified professionals should make the
                      connections in accordance with the local regulations and rules. Disconnect the mains power
                      supply and verify its absence prior to installation.

© 2017 - epic srl - All rights reserved - Subject to technical change - Check periodically the website    Doc. DS_A.JF rev. 1.0
You can also read