AIR-TO-WATER REVERSIBLE HEAT PUMPS CXAF 290 - 700 KW - Trane

Page created by Judith Hamilton
 
CONTINUE READING
AIR-TO-WATER REVERSIBLE HEAT PUMPS CXAF 290 - 700 KW - Trane
AIR-TO-WATER
REVERSIBLE HEAT PUMPS
CXAF
290 – 700 KW
AIR-TO-WATER REVERSIBLE HEAT PUMPS CXAF 290 - 700 KW - Trane
H IS FOR HEATING: THE WARM SIDE OF
                                                                TRANE

CXAF joins Trane’s growing family of heating solutions.
At Trane, we believe in electrification of heating as an important global
contributor to mitigate climate change and reduce carbon footprint.

                                                                                  Air‐to‐water
                                                                                  Scroll heat pumps
                                                                                  CXAF
                                                                                  280‐700 kW

                                                                            290
AIR-TO-WATER REVERSIBLE HEAT PUMPS CXAF 290 - 700 KW - Trane
SINTESIS™ FAMILY: PERFORMANCE &
                                                                FLEXIBILITY

CXAF joins Trane’s Sintesis™ air‐cooled chiller and heat pump portfolio.
Trane Sintesis™ represents industry leading performance and flexibility.
Always striving for a perfect fit, not only to your building and application
requirements but also to your sustainability and budget targets.
AIR-TO-WATER REVERSIBLE HEAT PUMPS CXAF 290 - 700 KW - Trane
WHY SINTESIS™
                                                                                               CXAF?
CONFIGURABILITY                       RELIABILITY                           EFFICIENCY                     SUSTAINABILITY

Every building application has    Reliability is a Trane guarantee.   Low consumption, reliable            At Trane, we believe in
specific needs. That’s why        CXAF have undergone years of        performance and comfort are          electrification of heating
CXAF is built off a modular       performance testing, even in        our key design criteria. Trane       as an important global
platform which allows you to      severe weather conditions, to       Engineering has optimized the        contributor to mitigate
configure a unit to your needs    ensure that every single            defrost management and               climate change and reduce
without significantly impacting   component is built to last. All     redesigned the refrigeration         carbon footprint.
delivery time.                    units are tested prior to leaving   circuit to achieve best‐in‐class
                                  the factory.                        performance.
                                                                                                           •   Air‐sourced renewable
•   Efficiency level              •   Proven Sintesis™                •   Up to 20% improved                   technology
•   Acoustic packages                 components                          efficiency vs. legacy products   •   Lower carbon footprint
•   Fan technology                •   3 R&D facilities                •   Class A or B in heating              compared to fossil fuel
•   hydraulic modules             •   Factory compliant with          •   Exceeding ErP 2016                   technologies
•   Heat recovery                     latest ISO standards                requirements in heating          •   Less equipment
                                  •   Eurovent certification          •   Already compliant with ErP           needed to heat or cool
                                                                          2021 in cooling                      a building
AIR-TO-WATER REVERSIBLE HEAT PUMPS CXAF 290 - 700 KW - Trane
KEY CXAF
                                                                                                                    FEATURES
                                                                                                                    Multi‐speed outdoor fans
                                                                                                                    Available with AC, EC and EC
CXAF is built on Trane’s well‐known Sintesis™ platform, which means it re‐uses many of the                          Axitop technologies
same components and technologies with a proven reliability record. This guarantees a smooth
operation and reliable comfort for your building users, while also facilitating the life of service
technicians and keeping maintenance costs to a minimum.                                                             Brazed plate heat exchanger
                                                                                                                    Compact and proven design,
    Fin & Tube heat exchanger                                                                                       used on CGAF platform
    Modular design in ‘V’ shape for
    maximum performance in a                                                                                        Variable volume DSH scroll
    small footprint                                                                                                 compressors
                                                                                                                    Optimized for higher
    Hydraulic module                                                                                                seasonal efficiency
    Fully integrated for easy
    transportation and installation

                                                                                                      CXAF
    Tracer UC800
    Reliable controller platform with
    proven algorithms to ensure smooth
    operations and optimum defrost
    control
                                                                     Hat Booster
                                                                     Dedicated refrigerant circuit fully designed
                                                                     and manufactured by Trane for superior
                                                                     heating performance
AIR-TO-WATER REVERSIBLE HEAT PUMPS CXAF 290 - 700 KW - Trane
CXAF PRODUCT LINE-UP
                                                                               SE AND HEAT VERSIONS

276 – 425 kW                                        480 – 543 kW                         602 – 700 kW

   080               090         110         130      140            150         165            180            190

                 Length         4520 mm                     Length     5645 mm                Length         6770 mm
                 Width          2200 mm                     Width      2200 mm                Width          2200 mm
                 Height         2526 mm                     Height     2526 mm                Height         2526 mm

                           080         090    100    110     130       140        150     165          180      190
Number of circuits          2           2      2     2        2            2       2      2            2         2
Compressors per circuit    2            2      2     2        2            3       3      3            3         3
Number of fans             8            8      8     8        8        10         10      10           12        12

                                                                                 10 base models, 3 cabinet sizes
AIR-TO-WATER REVERSIBLE HEAT PUMPS CXAF 290 - 700 KW - Trane
CXAF CONFIGURATIONS

Efficiency      Fan         Ambient       Application      Sound          Hydraulics

   SE            AC         Standard        Comfort          SN             Without

                           Low ambient
  HEat           EC                         Process          LN          Single pump
                             cooling

   XE*       EC + Axitop     Nordic*         PHR*           XLN           Dual pump

                                              HT*           NNSB          Buffer tank

                                                                     * Available Summer 2019

                               Wide range of options to fit your needs without compromise
AIR-TO-WATER REVERSIBLE HEAT PUMPS CXAF 290 - 700 KW - Trane
CXAF HEAT

HEat: bringing HIGH EFFICIENCY in HEATING mode
                  Trane Engineering has built on years of experience with CXAM,
                  CXAX and CXAO heat pumps to bring forward the latest
                  innovation in refrigeration circuit design.
                                       The characteristic Sintesis™ ‘V’ shaped heat exchanger has been
                     Optimized         optimized to accelerate the defrost cycle, improving the unit
                      defrost          reliability by minimizing compressor cycling and maintaining
                    management         comfort for building user.

                                       An innovative suction line gas heat exchanger (SLGHE), designed
                        Boost          and built by Trane, combined with an electronic expansion valve
                   thermodynamic       and a meticulously tested software algorithm, allows the CXAF unit
                                       to achieve high performances in heating mode. The heat
                     performance
                                       exchanger, located at the compressor inlet, increases subcooling
                      with Trane       and minimizes superheating in the evaporator, boosting the coil
                    SLGHE system       capacity through a higher enthalpy gain, without an impact on
                                       power consumption. Thus, the COP and SCOP increase on average
                                       by 12% compared to units without the Trane SLGHE system.

                  Proven reliability   Additionally, the SLGHE system prevents any liquid from entering
                                       into the compressor, improving unit reliability.
AIR-TO-WATER REVERSIBLE HEAT PUMPS CXAF 290 - 700 KW - Trane
CXAF ACOUSTIC OPTIONS

 Option       Sound reduction      Description

    LN                              •   Compressor jackets
                                    •   Piping insulation
Low noise     ‐ 3 dB(A)

   XLN
                                    •   Compressor sound enclosure
Extra Low                           •   Piping insulation
               ‐ 4 dB(A)
  noise

  NNSB
                                    •   Automatic lower fan speed based
Night noise    ‐ 2 dB(A)                on external signal (e.g. occupancy
 setback                                sensor)
AIR-TO-WATER REVERSIBLE HEAT PUMPS CXAF 290 - 700 KW - Trane
CXAF PRODUCT DATA
                                                                                            SE AND HEAT VERSIONS
                                                                                             With AC fans (for other options, refer to literature)

CXAF Standard Efficiency (SE)                              190    180    165    150    140         130       110       100       090       080
          Net heating capacity (1)               (kW)      636    602    543    509    480         425       389        345       310       276
          Total power input in heating net (1)   (kW)      209    196    179    166    156         139       127        109       98        86
Heating

          COP net (1)                            (kW/kW)   3.04   3.07   3.02   3.06   3.09        3.05      3.08      3.17       3.17      3.20
          Eurovent class heating                            B      B      B      B      B           B         B          B         B         A
          Seasonal space efficiency, ηs,h        (%)       126%   126%   126%   125%   125%       126%       125%      131%      132%      132%
          Net cooling capacity (2)               (kW)      621    587    529    497    469         416       380        334       303       276
          Total power input net (2)              (kW)      227    209    195    180    164         152       134        117       102       87
Cooling

          EER net (2)                            (kW/kW)   2.74   2.81   2.71   2.77   2.85        2.74      2.84      2.86       2.99      3.16
          Eurovent class cooling                            C      C      C      C      C           C         C          C         B         A
          Seasonal space efficiency, ηs,c        (%)       163%   163%   161%   161%   161%       160%       162%      167%      173%      172%

CXAF High Heat Efficiency (HEat)                           190    180    165    150    140         130       110       100       090       080
          Net heating capacity (1)               (kW)      669    633    572    533    472         450       415        370       338       305
          Total power input in heating net (1)   (kW)      208    195    178    165    143         139       126        108       97        86
Heating

          COP net (1)                            (kW/kW)   3.22   3.25   3.21   3.23   3.29        3.25      3.30      3.43       3.48      3.56
          Eurovent class heating                            A      A      A      A      A           A         A          A         A         A
          Seasonal space efficiency, ηs,h        (%)       134%   132%   130%   129%   130%       136%       133%      144%      145%      146%
          Net cooling capacity (2)               (kW)      619    585    529    497    470         417       380        335       304       277
          Total power input net (2)              (kW)      227    209    195    179    164         152       133        116       101       87
Cooling

          EER net (2)                            (kW/kW)   2.73   2.80   2.71   2.77   2.86        2.75      2.85      2.88       3.00      3.18
          Eurovent class cooling                            C      C      C      C      C           C         C          C         B         A
          Seasonal space efficiency, ηs,c        (%)       170%   169%   167%   167%   169%       166%       169%      172%      179%      177%
OPERATING MAPS

Heating mode                                                                                                Cooling mode
                       50                                                                                         60

                       40                                                                                         50

                                                                                                                  40
                       30
Outdoor ambient (ºC)

                                                                                           Outdoor ambient (ºC)
                                                                                                                  30
                       20
                                                                                                                  20

                       10                                                                                         10

                                                                                                                   0
                        0
                                                                                                                  -10
                       -10
                                                                                                                  -20
                                  ‐12ºC
                       -20                                                                                        -30
                             10      15   20    25    30   35    40   45   50    55   60                                -15   -5             5          15      25
                                                        HLWT (ºC)
                                                                                                                                          LWT (ºC)
                                               Full Load              Min Load
                                                                                                                              Full Load              Min Load