XNX Universal Transmitter

Page created by Carmen Bishop
 
CONTINUE READING
XNX Universal Transmitter
XNX Universal Transmitter

                                                       A universal transmitter for toxic
                                                       and combustible gas detection
                                                       that merges Honeywell’s
                                                       industry-leading gas sensing
                                                          technology on a single platform

                    DASTEC S.R.L. Hipólito Yrigoyen 850. Piso 3 Of. 335 C1086AAN Buenos Aires - Argentina
    TE: (54-11) 4343-6200 // 4331-2288 Fax: (54-11) 4334-3120 Email: dastecsrl@dastecsrl.com.ar Web: www.dastecsrl.com.ar
XNX Universal Transmitter
XNX Universal Transmitter – I = IR
Description                        Transmitter for use with Searchpoint Optima Plus, Searchpoint Excel infrared gas detectors from Honeywell Analytics.

                                   Modular system enabling connectivity to a wide variety of system architectures including 4-20mA/HART and optional
                                   integral relays or serial communications (Foundation Fieldbus or Modbus). Optional local IS HART port for Hand Held
                                   Interface (HHI).

XNX Universal Transmitter – L = mV
Description                        Transmitter for use with conventional mV flammable gas detectors from Honeywell Analytics and new Multi-Purpose
                                   Detector (MPD) providing field serviceable CB flammable and IR Slug flammable and CO2 detectors.

                                   Modular system enabling connectivity to a wide variety of system architectures including 4-20mA/HART and optional
                                   integral relays or serial communications (Foundation Fieldbus or Modbus). Optional local IS HART port for Hand Held
                                   Interface (HHI).

XNX Universal Transmitter – T = ECC; - R -= Remote ECC
Description                        Transmitter for use with conventional toxic gas detectors from Honeywell Analytics. Remote connection to these sensors.

                                   Modular system enabling connectivity to a wide variety of system architectures including 4-20mA/HART and optional
                                   integral relays or serial communications (Foundation Fieldbus or Modbus). Optional local IS HART port for Hand Held
                                   Interface (HHI).

Environmental
Operating Temperature              -40°C to +65°C
Operating Humidity                 0% to 99% rH (non-condensing)
Environmental Protection           IP 66 and IP 67
Construction
Material                           Painted LM25 Aluminum or painted 316L Stainless Steel
Entries                            5 x M25 or ¾ NPT for sensor and cabling connections
Performance
Refer to individual product specifications for Searchpoint Optima Plus, Searchline Excel, Searchline Horizon and conventional catalytic bead/electrochemical
devices.

Electrical
Supply Voltage                     18V to 32V (24V nominal)
HA Approvals
Hazardous Area                     ATEX: Ex II 2 G D, EEx d IIC T5 (Tamb -40°C to +65°C) / UL: Class 1, Div 1, Groups B, C, and D / Class 1, Zone 1 AEx d IIC
                                   T5 (Tamb -40°C to +65°C) /
                                   CSA: Class 1, Div 1, Groups B, C, and D T5 (Tamb -40°C to +65°C)

Performance                        EU – ATEX, EN45544, EN50104, EN50270, EN50271, EN13980, EN60079
                                   NA – UL 913, UL 1203, CSA 22.2 No. 152
                                   Other – IEC61508 (SIL Assessment, SIL 2), IECEx OD 005

                                     DASTEC S.R.L. Hipólito Yrigoyen 850. Piso 3 Of. 335 C1086AAN Buenos Aires - Argentina
                     TE: (54-11) 4343-6200 // 4331-2288 Fax: (54-11) 4334-3120 Email: dastecsrl@dastecsrl.com.ar Web: www.dastecsrl.com.ar
XNX Universal Transmitter
Display Module & User Interface (Standard Supply)
Display Type                     Backlit LCD
Information Displayed            Base Information:              Gas Reading
                                                                Gas Name and Units of measurement
                                                                Fault and Alarm Status
                                 Other Information:             Set up & configuration of field devices e.g.
                                                                Alignment, calibration, alarm settings etc
                                                                Refer to Optima Plus/Excel/SHC1 product manuals for information

Interface                        Magnetic wand with terminal screwdriver (supplied each unit)
4-20mA & HART (Standard Supply)
Description                      Fully configurable isolated 4-20mA & HART output module providing current sink, current source and isolated
                                 modes of operation. Configurable with or without HART data superimposed on the 4-20mA signal output. Multi-
                                 drop enabled where 4-20mA analogue signal is not required.

Non-intrusive Interface          Optional local IS port to enable HOT connection of a HART handheld configurator
Operating Modes                  Current sink / Current source / Isolated current sink /Conventional or with HART data
Output Range                     0 to 22mA
4-20mA Signal Accuracy           +/- 1% FS
Max loop resistance              600 Ohms at 24Vdc loop supply
Functions Supported via          Gas Reading
HART                             Gas Name and Units of measurement
                                 Fault and Alarm Status
                                 4-20mA signal level
                                 General/Device Information
                                 Detailed Sensor Information Including:
                                            Optical Signal Level
                                            Dynamic Reserve (Excel Only)
                                            Raw reading
                                            24V supply voltage
                                            Temperature
                                            RTC (Excel Only)
                                            Calibration and Configuration status
                                            Detailed Fault and Warning Information
                                            Fault and Alarm History
                                 Installation
                                 Configuration
                                 Calibration
                                 Forcing of 4-20mA output

Local IS HART Port (Optional)
Description                      Provides externally accessible IS connections to the XNX Universal transmitter to enable HOT connection of
                                 HC275/375 HART or equivalent hand held configurator

Installation                     Fitted to one of the cable entries on the XNX Universal transmitter.
Environmental Protection         Terminals protected by cover to IP 66 and IP 67 when not in use

                            DASTEC S.R.L. Hipólito Yrigoyen 850. Piso 3 Of. 335 C1086AAN Buenos Aires - Argentina
            TE: (54-11) 4343-6200 // 4331-2288 Fax: (54-11) 4334-3120 Email: dastecsrl@dastecsrl.com.ar Web: www.dastecsrl.com.ar
XNX Universal Transmitter
Relay Module (Optional)
Description                          Provides three fully user configurable relay outputs that can be switched based on the current gas level
                                     and/or status of the transmitter. Provides 2 x SPCO alarm and 1 x SPCO fault relays
Installation                         Fitted into XNX by qualified service engineer.
Rating                               Maximum: 240VAC, 5A (non inductive load)
                                     Minimum: 5V, 10mA (non inductive load)
Electrical Connections               Fault: Common, Normally Open, Normally Closed
                                     Alarm 1: Common, Normally Open, Normally Closed
                                     Alarm 2: Common, Normally Open, Normally Closed
Configuration                        Default                                                  Configurable Options
                                     Fault Relay:                                             Fault Relay:
                                      Normally energized                                       Normally energized / normally de-energized
                                      Non latching                                             None
                                      Signal inhibit as fault                                  Enable/disable

                                     Alarm 1 / 2 Relays:                                       A1 / A2 Relays:
                                     Normally de-energized                                     Normally energized / de-energized
                                     Non latching                                              Latching / non latching
                                     Alarm rising on gas reading                               Alarm on rising / falling
                                     Alarm level 20% and 40% of scale                          Alarm level 10% to 90% of full scale
                                     Hysteresis of 2% of scale
Re-setting of Latched Relays      Easily accessible interface on display (if used) or via HART interface (local or remote)
Note                              Use of the Relay Module or ‘Other’ Communications Module (E.g. Foundation Fieldbus) is mutually
                                  exclusive. However, relay function may be used in conjunction with standard communication output i.e. 4-
                                  20mA with HART.
Relay Specific Functions via HART Relay status information / Reset of latched conditions / Configuration of relays
Interface                         Forcing of relay state
Foundation Fieldbus Module (Optional)
Description                       Foundation Fieldbus compliant digital communications interface enables connection of the XNX Universal
                                  transmitter to a multi-drop Foundation Fieldbus H1 network.
Installation                      Fitted into housing base either at the factory or in the field by qualified service engineer.
Connections                       Sig+, Sig- and Screen
Physical Layer                    Conforms to IEC 1158-2 and ISA 50.02, 31.25Kbits/s
Maximum No. of Nodes              32
Functions Supported               Gas Reading
                                  Gas Name and Units of measurement
                                  Instrument status (OK, warning, fault, over-range)
                                  General/Device Information
                                  Remote zero and span calibration (detector dependent)
                                  Detailed Sensor Information Including:
                                             Optical Signal Level
                                             Dynamic Reserve (Excel Only)
                                             Raw reading
                                             24V supply voltage
                                             Temperature
                                             RTC (Excel Only)
                                             Calibration and Configuration status
                                  Detailed Fault and Warning Information
                                             Fault and Alarm History
                                             Zero Calibration

Modbus RTU Module (Optional)
Description                          The Modbus output module provides an Isolated RS485 output to enable the connection of the XNX
                                     Universal transmitter to a multi-drop Modbus network
Installation                         Fitted into housing base either at the factory or in the field by qualified service engineer.
Connections                          RS485+, RS485-, Drain
Physical Layer                       Isolated RS485, 1200 to 19.2K Baud
Maximum No. of Nodes                 254 XNX Universal compatible transmitters only
Protocol                             Modbus RTU
Functions Supported via Modbus       Gas Reading
                                     Gas Name and Units of measurement
                                     Instrument status (OK, warning, fault, over-range)
                                     General/Device Information
                                     Remote zero and span calibration (detector dependent)
                                     Detailed Sensor Information Including:
                                                Optical Signal Level
                                                Dynamic Reserve (Excel Only)
                                                Raw reading
                                                24V supply voltage
                                                Temperature
                                                RTC (Excel Only)
                                                Calibration and Configuration status
                                     Detailed Fault and Warning Information
                                                Fault and Alarm History
                                                Zero Calibration

                           DASTEC S.R.L. Hipólito Yrigoyen 850. Piso 3 Of. 335 C1086AAN Buenos Aires - Argentina
           TE: (54-11) 4343-6200 // 4331-2288 Fax: (54-11) 4334-3120 Email: dastecsrl@dastecsrl.com.ar Web: www.dastecsrl.com.ar
Honeywell Analytics Lines of Business

  Commercial                                                                           Industrial                                      Portables
  Vulcain-brand gas detection from stand-                                              Renowned Sieger and Manning gas                 Single or multi-gas Lumidor and other
  alone units to fully engineered, multi-                                              detection systems with advanced                 premium detectors with compact,
  point systems, all offering cost-effective                                           electrochemical, infrared and open path         lightweight designs ranging from
  regulatory compliance                                                                sensing technologies                            simple alarm only units to advanced,
  » Applications: parking structures,                                                  » Applications: oil and gas, cold storage,      fully configurable and serviceable
     chillers, mechanical rooms, office                                                   water/wastewater treatment,                  instruments
     towers, commercial buildings,                                                        chemicals, engine rooms, plastics            » Applications: underground utility
     shopping centers, swimming pools,                                                    and fibers, agriculture, printing and            and electricity ducts, boiler rooms,
     golf courses, schools and universities,                                              light industrial                                 post-fire sites, sewers, industrial
     laboratories                                                                                                                          plants, industrial hygiene, first
                                                                                                                                           responder teams, remote fleets

                                                                                       High Tech/Government                            Technical Services
Find out more                                                                          A complete portfolio of gas and chemical        24/7 global network includes
www.honeywellanalytics.com                                                             detection instrumentation including in-         post-sales service and Systems
                                                                                       frared spectroscopy (MST) with no cross         Integration teams
                                                                                       interference to Chemcassette paper-             » Emergency call out, service
Contact Honeywell Analytics:                                                           based solutions (MDA Scientific) offering          contracts, on/off-site repair, training
                                                                                       detection down to parts per billion                and commissioning
Americas                                                                               » Applications: semiconductor                   » Complete range of spares,
Honeywell Analytics Distribution, Inc.                                                    manufacturing and nanotechnology,               consumables and accessories
405 Barclay Blvd.                                                                         aerospace propulsion and safety,
Lincolnshire, IL 60069                                                                    specialty chemicals industry
USA
Tel: +1 847 955 8200
Toll free: +1 800 538 0363
                                                                                    Europe, Middle East, Africa                       Asia Pacific
Fax: +1 847 955 8208
                                                                                    Life Safety Distribution AG                       Honeywell Analytics Asia Pacific
detectgas@honeywell.com
                                                                                    Wilstrasse 11-U31                                 #508, Kolon Science Valley (1)
                                                                                    CH-8610 Uster                                     187-10 Guro-Dong, Guro-Gu
                                                                                    Switzerland                                       Seoul, 152-050,
Technical Services                                                                  Tel: +41 (0)44 943 4300                           Korea
ha.global.service@honeywell.com                                                     Fax: +41 (0)44 943 4398                           Tel: +82 (0)2 2025 0307
                                                                                    gasdetection@honeywell.com                        Fax: +82 (0)2 2025 0329
www.honeywell.com                                                                                                                     analytics.ap@honeywell.com
                                                                                                                                                                                    12791007

Please Note:
While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for errors or omissions.
Data may change, as well as legislation, and you are strongly advised to obtain copies of the most recently issued regulations,
standards, and guidelines. This publication is not intended to form the basis of a contract.
H_X5_DS01060_V1 10/07
© 2007 Honeywell Analytics
                               DASTEC S.R.L. Hipólito Yrigoyen 850. Piso 3 Of. 335 C1086AAN Buenos Aires - Argentina
               TE: (54-11) 4343-6200 // 4331-2288 Fax: (54-11) 4334-3120 Email: dastecsrl@dastecsrl.com.ar Web: www.dastecsrl.com.ar