PRODUCT CATALOG BATTERY CHARGER - AT10.1 Battery Charger - Amper Online
←
→
Page content transcription
If your browser does not render page correctly, please read the page content below
PRODUCT CATALOG AT10.1 Battery Charger HIGH QUALITY ENERGY EFFICIENCY BATTERY CHARGER Atlantic Power Energy www.atlanticpowerenergy.com Copyright © 2021 Atlantic Power Energy - All rights reserved
ABOUT US ATLANTIC POWER Energy (ATP) was founded in 2008 with the focus of serving Latin American customers in their power quality demands covering: UPS’s (Uninterruptible Power Supply), Edge Micro Data Center (Indoor & Outdoor), Racks, PDU’s, Technical Floor, VRLA batteries. From our headquarters in Florida, USA we attend all of your LATAM distributors offering sales and technical support. Our policy is to supply products only through our distributors in order to provide a solid and personalized support. ATLANTIC POWER since 2012 has started to supply the single phase UPS systems covering the South Cone Area and now is expanding the products range to Low Voltage Products. OUR MISSION To guarantee our customers and end users to the continuity of their critical processes providing with high quality green energy, with operational excellence, generating confidence and assured availability. Making power 24/7 without Interruption! OUR MAIN PRODUCTS Provide on-stop solution High Voltage UPS Quality equipment to Protect Critical Applications Low Voltage UPS Edge Micro Data Centers Racks & PDU’s Technical Floors Batteries & Chargers Atlantic Power Energy www.atlanticpowerenergy.com Copyright © 2021 Atlantic Power Energy - All rights reserved
ATD Battery Charger Standard features • 5 Year Product Warranty • Membrane front panel • Universal main control board operates in any AT • Front panel controls can be disabled for security Series charger • A redundant analog circuit for LDCV alarm, • Alarm assembly with local LEDs and summary relay independent of the microprocessor contact for AC • Redundant control loops for higher reliability • Failure, DC Failure, High Vdc, Low • Local or remote voltage sense with redundancy to • Vdc, Positive(+) and Negative(-) ground fault protect against remote sense failure • High DC voltage shutdown • Self-diagnostics • Forced load share during parallel operation • Input & output MOV surge suppressors • Float/equalize selector switch with indicating lights • Reverse polarity protection via free wheeling diodes • Manual equalize timer (0-255 hr.) with indicating • CU-AL I/O compression lugs lights AC line failure automatic equalize timer • Switchboard wire, UL VW-1 (0-255 hr.) with indicating light • Enclosure pre-treated using a 5-stage iron phosphate • AC On indicating light process with baked epoxy powder coating in ANSI • 1% Digital LED meter for Vdc, Adc, timer hours and 61 gray alarm settings • AC input and DC output circuit breakers 5 YEAR WARRANTY www.atranticpowerenergy.com Atlantic Power Energy Copyright © 2021 Atlantic Power Energy - All rights reserved
Environmental Safety & Acceptance • Operating Ambient: Temperature 0°F to • Meets NEMA PE 5-1996, PE 5-1997 (R2003) 122°F (-18°C to 50°C) w/o derating specification • Operating Altitude: 10,000 feet 3,000 meters) • NEMA-1/IP20 type standard enclosure above sea level w/o derating • Third party agency approvals: • Relative Humidity 0% to 95% (without condensation) • Audible Noise Less than 65 dBA at any point 5ft (1.5m) from any vertical surface of enclosure CSA C22.2 · NRTL/C · UL 1012/UL 1564 compliant Seismic qualified ABS · CE certification available upon request Specifications MADE IN USA AC Input DC Output • Group 1 (6-25 Adc) Voltage: • Voltage Ratings: 120/208/240Vac (multi-tap) 60Hz 12, 24, 48, or 130Vdc nominal 480Vac 60Hz • Current Ratings: 220Vac, 380/416Vac 50/60Hz GROUP 1: 6, 12, 16, 20, 25Adc 550-600 Vac 60Hz GROUP 2: 30, 40, 50, 75, 100Adc • Group 2 (30-100 Adc) Voltage: • Continuous Rating: 120, 208, 240 or 480Vac 60Hz 110% rated current at maximum 220Vac, 380 or 416Vac 50/60Hz equalize voltage at 50ºC 550-600 Vac 60Hz • Current Limit Adjustment Range: • Input Voltage Tolerance: 50% to 110% rated output +10%, -12% • Voltage Regulation: • Input Frequency Tolerance: ±0.25% for line, load and temp. ±5% variations • Efficiency: *Regulation at max. equalize voltages may not meet ±0.25% 85-90% typical for 130Vdc at 50-100% • Electrical Noise: load 32dBrnc • Ripple: 12/24/48Vdc Unfiltered on battery 1% Vrms Filtered on battery 30mVrms Filtered off battery 1% Vrms Battery Eliminator 30mVrms 130Vdc Unfiltered on battery 2% Vrms Filtered on battery 100mVrms Filtered off battery 2% Vrms Battery Eliminator 100mVrms • Surge Withstand Capability: Meets IEEE-472, ANSI C37.90a www.atranticpowerenergy.com Atlantic Power Energy Copyright © 2021 Atlantic Power Energy - All rights reserved
GROUP 1 6-25Adc Cabinet Style 586 Cabinet Style 594 Atlantic Power Energy www.atlanticpowerenergy.com Copyright © 2021 Atlantic Power Energy - All rights reserved
GROUP 2 30-100Adc Cabinet Style 5017 Cabinet Style 5018 *NOTE: Dimensions shown are for reference only; for installation and mounting please refer to user manual. www.atranticpowerenergy.com Atlantic Power Energy Copyright © 2021 Atlantic Power Energy - All rights reserved
Specification Chart DC Output AC Input Ampere Rating Battery Charger AC Circuit Breaker DC Cabinet Approx. Heat Based on maximum rms value of the input current delivered to Rating the charger under all operating conditions within Ampere Rating Circuit Style Shipping Loss (standard AIC breakers) manufacturer's specifications Breaker Weights Watss Rating lbs. (kg) (BTU/hr) *Regulation at max. equalize voltages may not meet ±0.25% Atlantic Power Energy www.atranticpowerenergy.com www.atlanticpowerenergy.com Atlantic Power Energy Copyright Copyright © 2021 Atlantic Power Energy - All rights reserved © 2021 Atlantic Power Energy - All rights reserved
Configuration GROUP 1: 6-25Adc 6-25Adc Circuit Breaker AC & DC Ratings STANDARD MEDIUM HIGH • Input: • Input: • Input: 10kAIC - 240VAC 25kAIC - 240VAC 65kAIC - 240VAC 10kAIC - 480VAC 18kAIC - 480VAC 25kAIC - 480VAC • Output: 18kAIC - 600VAC 18kAIC - 600VAC 10kAIC -125VDC* • Output: • Output: 10kAIC - 250VDC 20kAIC - 250VDC * For chargers 16Adc and larger; consult factory for other ratings. GROUP 1 (6-25 Adc - SPECIFICATION TABLE) Input Filter Inductor Transformer Microprocessor Control Board I/O Assembly Rectifier Assembly Filter Assembly Input Circuit Breaker Output Circuit Breaker www.atranticpowerenergy.com Atlantic Power Energy Copyright © 2021 Atlantic Power Energy - All rights reserved
GROUP 2: 6-25Adc 30-100Adc Circuit Breaker AC & DC Ratings STANDARD MEDIUM HIGH • Input: • Input: • Input: 5kAIC - 120/208/240/480VAC 25kAIC - 120/208/240/480VAC 65kAIC - 120/208/240/480VAC • Output: 18kAIC - 600VAC 25kAIC - 600VAC 5kAIC - 125VDC • Output: • Output: 10kAIC - 250VDC 20kAIC - 250VDC GROUP 2 (30-100 Adc) - SPECIFICATION TABLE Rectifier Assembly Microprocessor Control Board Filter Inductor I/O Assembly Input Circuit Breaker Output Circuit Breaker Input Transformer www.atranticpowerenergy.com Atlantic Power Energy Copyright © 2021 Atlantic Power Energy - All rights reserved
Customize your AT10.1 Summary of options • DC output filtering: per NEMA • Battery temperature compensation • End of discharge alarm PE5 1996, standard and • Fan control contactor • Battery discharge alarm battery eliminator • Mechanical lock for front door • Zero-center ground detection meter • Medium & High AIC Breakers • Custom Paint • Analog AC voltmeter • Auxiliary alarm relay board • NEMA 4 (12) type enclosure w/fan • Analog AC ammeter • Copper ground bus • Rack mounting • Cabinet heater assembly • AC lightning arrestor • Wall mounting • CE marking upon request • Fungus proofing (tropicalization) • Floor mounting stand • ABS certification upon request • Static proofing • NEMA Type 2 Drip Shield • Custom drawing package w/ • Communications module: DNP3 • Barrier type alarm terminal optional DWG and PDF files Level 2 or MODBUS protocols block • Forced load share cable Filtering - Standard Filtering - Battery Eliminator Output filtering is essential whenever An additional "battery eliminator" there is need for low ac ripple and feature is also available, meeting low noise on the dc bus for critical the specifications of NEMA standard loads. The standard dc output filtering PE5-1996 withno battery connected, limits ripple to no more than 30mV measured at the dc output terminals. RMS on 12, 24 & 48Vdc units, and This feature is recommended for 100mV RMS on 130Vdc units, measured sites where the battery may occasionally at the battery terminals. This feature be disconnected from the dc bus for meets the specifications of NEMA maintenance. Additional filtering is standard PE5-1996, and is recommended essential to limit ac ripple and noise for installations using VRLA or gelled for critical dc loads. electrolyte batteries. Atlantic Power Energy www.atlanticpowerenergy.com Copyright © 2021 Atlantic Power Energy - All rights reserved
Medium & High AIC Breaker Copper Ground Bus This feature provides thermal-magnetic This option provides a convenient circuit breakers with higher Ampere means to tie the AT10.1 to the site Interrupting Capacity ratings than the building ground. A copper ground standard. See the tables for Group 1 and bus bar is provided at the I/O terminal, Group 2 medium and high AIC breaker with an extra CU-AL compression ratings. For AT10.1 Group 1, AC and DC box lug. breakers ratings must be ordered together, and are supplied in a separate penthouse enclosure. For Group 2, ac and dc breakers can be specified separately and are supplied in the standard cabinet. Auxiliary Alarm Relay Board Communications The AT10.1 features several industry - This option allows full remote standard alarms, with individual LED monitoring of the AT10.1 and control indicators on the front instrument of the front panel features, using panel, and are accessible to the user MODBUS or DNP3 Level 2 protocols. via one (1) Summary Alarm contact Standard serial connections are on the Main Control PC Board. This provided for use with local SCADA feature provides a separate user - systems. Additional Ethernet and accessed pc board, featuring discreet Fiber Optics Modem interfaces are two (2) form-C relay contacts for also available for use with the AT all six (6) alarms. In AT10.1 Group 1 Communications option. Contact ratings, the board is supplied in an factory for part number. additional penthouse enclosure. In AT10.1 Group 2 ratings, it is supplied within the standard enclosure. Atlantic Power Energy www.atlanticpowerenergy.com Copyright © 2021 Atlantic Power Energy - All rights reserved
AC Lightning Arrestor Temperature Compensation This options features an industrial - Supplied in a kit, this option adjusts the grade surge arrestor in polycarbonate AT10.1 dc output voltage up or down, housing, rated for 20,000 Amperes. in response to battery temperature It is recommended for installations fluctuations. Temperature is measured with risk of frequent ac surges, such by an epoxyenclosed thermistor. as high elevations or severe weather. This probe is mounted on or near the battery, and connected by a cable to the Main Control PC Board. It is compatible with both lead-acid and nickelcadmium batteries, and recommended for VRLA batteries. Cable lengths of 25, 50, 100, and 200 ft are available. NEMA Type 4 Cabinet NEMA Type 2 Drip Shield With this accessory, a fully assembled Standard AT10.1 battery chargers standard AT10.1 NEMA-1 vented are supplied in NEMA Type 1 vented enclosure is installed within another enclosures. The optional drip shield gasketed, sealed cabinet. prevents overhead water and small The combined assembly meets the falling particles from entering the NEMA Type 4 (and therefore Type 12 top vented panels, protecting internal and 13) enclosure specification. All equipment from damage. ratings feature forced cooling, with The combined standard enclosure user-supplied 120VAC for the fan. and drip shield meets the NEMA Type 2 specification. Rack Mounting Brackets Floor Stand These accessories are provided This accessory is provided with when the AT10.1 enclosure is to be smaller wallmounted AT10.1 chargers installed into a standard EIA relay when a vertical surface is not desired. rack. Smaller AT10.1 models may The assembly mounts the AT10.1 be installed into 19in racks, and all approximately 44in / 1.12m from AT10.1s may be installed into 23in or the floor. The kit features mounting 24in relay racks. All hardware is brackets, assembly hardware to included for assembling the brackets secure the AT10.1 to the brackets, to the AT10.1. Relay rack mounting and user instructions with a drilling hardware is user-supplied. pattern. Floor mounting anchor bolts are still user-supplied. www.atranticpowerenergy.com Atlantic Power Energy Copyright © 2021 Atlantic Power Energy - All rights reserved
AT-DC Distribution Panel Fan Control Contactor This product augments AT10.1 with a Lead-acid batteries produce hydrogen customized dc distribution panel for gas. This small wall-mounted external userspecified loads. accessory provides a relay contactor to The AT-DC is configurable to various activate a battery installation vent or combinations of main and branch exhaust fan. Available in 10A or 20A breakers. The AT-DC panel is models, the accessory is factoryset optimally supplied from the factory, to provide relay closure when the mounted to the AT10.1 and pre-wired AT10.1 enters into Equalize mode. to the charger's dc output terminals. For additional product details, including applicable 3rd party agency approvals, refer to the AT-DC literature (JF5032-00). Atlantic Power Energy www.atlanticpowerenergy.com Copyright © 2021 Atlantic Power Energy - All rights reserved