Introduction of Secondary Frequency Control in Indian Power System - 16th Mar 2018 - ERPC

Page created by Kim Wolfe
 
CONTINUE READING
Introduction of Secondary Frequency Control in Indian Power System - 16th Mar 2018 - ERPC
Introduction of Secondary Frequency Control
           in Indian Power System

              16th Mar 2018
Introduction of Secondary Frequency Control in Indian Power System - 16th Mar 2018 - ERPC
F e uen y P ofile o e the yea s…

                          Slow Tertiary
                          implemented
                          from April, 2016
Introduction of Secondary Frequency Control in Indian Power System - 16th Mar 2018 - ERPC
India…Cat hing up ith Best in the Wo ld

S.No Description                                       Values for
                                                    CE          India
 1   Standard Deviation (Hz)                      0.019         0.042
 2   Frequency Variation Index (FVI) in Hz       0.0036         0.020
 3   Instantaneous maximum frequency (Hz)        50.060        50.154
 4   Instantaneous minimum frequency (Hz)        49.916        49.885
 5   15-minute maximum average frequency (Hz)    50.033        50.065
 6   15-minute minimum average frequency (Hz)    49.965        49.952
 7   % of time frequency within 49.90-50.05 Hz    99.61         81.08
 8   % of time frequency below 49.90 Hz           0.00           0.06
 9   % of time frequency above 50.05 Hz           0.39          18.86
Introduction of Secondary Frequency Control in Indian Power System - 16th Mar 2018 - ERPC
Load Following and Regulation

                Regulation

           Load Following
Introduction of Secondary Frequency Control in Indian Power System - 16th Mar 2018 - ERPC
Frequency Control Continuum in India
Introduction of Secondary Frequency Control in Indian Power System - 16th Mar 2018 - ERPC
Frequency Control Response
    System
    Frequency               Restore Normal
    50 Hz

Deviation from 50 Hz             5-30s
                       Primary           Free
          Activate     Control           Reserves

                                                         30s – 5 min+
                                  Take          Secondary           Free
          Activate                Over          Control             Reserves

                                                                                   > 5 min +
• Primary (droop) control                                  Take            Tertiary
     Obligatory, Automatic response                       Over            Control
• Secondary (AGC) control
     Spinning reserve, NLDC/RLDC/SLDC controlled, Automatic Generation Control (AGC)
• Tertiary control
     Tertiary Reserve and response from State, Manual
Introduction of Secondary Frequency Control in Indian Power System - 16th Mar 2018 - ERPC
Immediate Frequency Response after an Event

                 Rate of change
                 of Frequency
                                        C. Quasi Steady State Frequency

                                  B. Nadir Frequency

 Importance
  of Inertia
 Load
 Frequency
  Nadir
 Quasi Steady
  State
  Frequency
Introduction of Secondary Frequency Control in Indian Power System - 16th Mar 2018 - ERPC
All in a day’s play…Repeated again and again
Timeline of Activities

Roadmap to
operationalise                                No ’1           Under
Reserves in                   Jan’1           Hon’ le CERC    continuous
the country      Ma ’1        LOA to          visit to NTPC   operation from
O t’1            FOLD meet    M/s Siemens     Dadri           4th Jan’1

          Jan’1           POSOCO       Mock Test        CERC Order
          Brainstorming   visit to     29th Jun’1       6th De ’1
          session         NTPC Dadri
                          May’1
Region considered as an Area for secondary control
                                               ACE = (Ia - Is) + 10 * Bf * (Fa - 50)
                      NORTHERN
                      REGION
                                                               NORTH-
                                                               EASTERN
                                                               REGION

         WESTERN
                                              Eastern      Ia = Actual net interchange, negative for NR
                                              REGION
         REGION                                             meaning import by NR
                                                          EASTERN
                                                            Is= Scheduled net interchange, negative for NR
                                                           REGION
                                                            meaning import by NR
                                                           Bf = Frequency Bias Coefficient in MW/0.1 Hz,
                                                            positive value
                      SOUTHERN                             Fa = Actual System Frequency
                      REGION
                                                           ACE positive means NR is surplus and NR
                                                            internal generation has to back down
                                                           ACE negative means NR is deficit and NR
                                                            internal generation has to increase
•   Tie line bias mode and Frequency bias only mode both possible
•   Interchange scaled using a factor of 15, changeable
                                                                                                   10
Data Flow in AGC Project
                                                               AGC console at
                                                                  NTPC
                                        AGC Local/Remote
          AGC On/OFF                    Unit Load Set Point              Factor
          AGC Set point                 Actual Generation
           Scaled ACE                  Circuit Breaker Status
Back-up
 NLDC                      AGC System at                         AGC RTU
              ICCP                          IEC 104 Protocol
SCADA                         NLDC                                at NTPC
          NR-IR Schedule                   AGC Set point
           NR-IR Actual
            Frequency                        AGC Local/Remote
                                             Unit Load Set Point         DeltaP
                                             Actual Generation
                                            Circuit Breaker Status

                                                               NTPC DCS
Architecture of the Project
                        Existing   New

 New
Display at NLDC
AGC Compensation Mechanism

        Up Regulation

                                               Down Regulation
 Payment from Pool +                         Payment to Pool +
Incentive to Generator                     Incentive to Generator
                         5-Minute Accounting
Future Ready AGC for 175 GW of RE by 2022

• Forecasting of Load & RE
• Use of Pumped Storage Plants
• Automatic controls
Detailed implementation plan to operationalize the
           spinning reserves in the country
• Detailed plan submitted to CERC on 14th July 2017
• Secondary Control as an Ancillary Service.
• https://posoco.in/download/detailed-modus-operandi-on-
  operationalization-of-spinning-reserves/?wpdmdl=13461
• Phase-I
   – All the ISGS generators whose tariff is regulated / adopted
     by CERC
• Phase-II
   – To improve the availability of Reserves
   – All Regional Entity generating stations scheduled by RLDCs
   – Over and above the Phase-I power stations
Essential requirements for Secondary Control

• Shall bear the cost of secondary control hardware at
  the plant end
   – Including the cost of the fibre optic cable
• Shall share DC and Schedule like ISGS generators on
  day ahead basis
   – Subsequent revisions with RLDCs
• The generating units shall have working control
  systems for turbine, boiler and governor
   – Governor response plots/graphs of past incidents have to
     be submitted to RLDC
• Existing wide band communication node
   – Within a radius below 30-40 km from the plant
   – Detailed survey is given in Annexe-VI of the report
Coordinated action items
• Ensuring accurate load forecasting and Renewable
  Energy (RE) forecasting.
• Proper scheduling by each state including indication of
  reserves
• Evaluate Area Control Error (ACE) of each control area
• The SLDCs must also monitor the primary response from
  the generating units within the state
• Periodic monitoring of the data quality needs to be done
  at the RPC forums
• Fibre optic communication from Regional Entity power
  plant to nearest CTU node and there on to RLDCs/NLDC
• Ensure adequate reserves for secondary control
• Renewable Energy (RE) resources under AGC
Pathway to Pan-India AGC Rollout

1                                     100+
Generation Plant                      Generation Plants

    1 GW                                        65 GW+
    Generation plant under pilot                By 2022

₹ 1 Crore                              ₹ 150 Crore+
Project Cost                           Pan-India roll out

       2000                                  25000+
       Highly Skilled Manhours               Highly Skilled Manhours

50 km                                  1000s km
Existing Communication path            Existing Communication path

           6 km                                     140 km+
           Optical Fibre (GI Piped)          Optical Fibre (GI Piped)
Image Credit: NASA

                     20
You can also read