INSTRUCTION MANUAL AQ S391 - Bay control IED - Arcteq

Page created by Dustin Hanson
 
CONTINUE READING
INSTRUCTION MANUAL AQ S391 - Bay control IED - Arcteq
INSTRUCTION MANUAL

AQ S391 – Bay control IED
INSTRUCTION MANUAL AQ S391 - Bay control IED - Arcteq
Instruction manual –AQ S391 bay control IED                                      2 (63)

 Revision         1.01
 Date             January 2012
 Changes                 -   HW construction and application drawings revised

 Revision         1.02
 Date             May 2012
 Changes                 -   Synchrocheck chapter revised
                         -   Voltage measurement module revised
                         -   CPU module description added
                         -   Binary input module description revised
                         -   IRIG-B information added
                         -   Updated ordering information and type designation
                         -   Technical data revised

 Revision         1.03
 Date             July 2012
 Changes                 -   Synch check parameter updates

 Revision         1.04
 Date             6.10.2015
 Changes                 -   Updated parameters

 Revision         1.05
 Date             18.10.2019
 Changes                 -   Updated construction and installation chapter

 Revision         1.06
 Date             23.6.2020
 Changes                 -   Added redundant power supply, possibility to remove
                             display.

 Revision         1.07
 Date                    22.01.2021
 Changes                 -   Removed statement that binary input modules are
                             capable of IRIG-B.
INSTRUCTION MANUAL AQ S391 - Bay control IED - Arcteq
Instruction manual –AQ S391 bay control IED                                                                                           3 (63)

TABLE OF CONTENTS

1      GENERAL ............................................................................................................................... 5
2      APPLICATION........................................................................................................................ 6
3      MAIN CHARACTERISTICS OF THE AQ S391 BAY CONTROL IED ................................ 7
3.1    System design ....................................................................................................................... 7
4      SOFTWARE SETUP OF THE IED ........................................................................................ 9
4.1    Circuit breaker control block ............................................................................................... 9
    4.1.1        Application.................................................................................................................. 9
    4.1.2        Mode of operation ..................................................................................................... 9
    4.1.3        Available internal status variable and command channel ................................. 10
    4.1.4        Configuration examples .......................................................................................... 13
4.2    Disconnector control function ........................................................................................... 14
    4.2.1        Application................................................................................................................ 14
    4.2.2        Mode of operation ................................................................................................... 14
    4.2.3        Available internal status variable and command channel ................................. 15
    4.2.4        Configuration example............................................................................................ 18
4.3    Dead line detection function ............................................................................................. 18
4.4    Voltage transformer supervision function (VTS) ............................................................ 20
4.5    Synchrocheck function du/df (25).................................................................................... 24
5      APPLICATION EXAMPLES ................................................................................................ 34
5.1    One and half circuit breaker configuration ..................................................................... 34
5.2    IED IO Positions in one and half circuit breaker configuration .................................... 35
6      CONSTRUCTIONS AND INSTALLATION ........................................................................ 36
6.1    CPU Module......................................................................................................................... 38
6.2    Power supply module ......................................................................................................... 40
6.3    Binary input modules ......................................................................................................... 42
6.4    Singaling binary output modules ...................................................................................... 45
6.5    9DI + BNC IRIG-B ............................................................................................................... 48
6.6    mA input module ................................................................................................................. 49
6.7    Tripping module .................................................................................................................. 50
6.8    RTD module ......................................................................................................................... 50
6.9    Voltage measurement module .......................................................................................... 53
6.10 Current measurement module .......................................................................................... 54
6.11 Installation and dimensions .............................................................................................. 55
7      TECHNICAL DATA .............................................................................................................. 57
7.1    Monitoring functions .......................................................................................................... 57
INSTRUCTION MANUAL AQ S391 - Bay control IED - Arcteq
Instruction manual –AQ S391 bay control IED                                                                                            4 (63)

7.2    Control functions ................................................................................................................ 57
7.3    Hardware.............................................................................................................................. 58
    Power supply module ............................................................................................................. 58
    Current measurement module .............................................................................................. 58
    Voltage measurement module .............................................................................................. 59
    High speed trip module .......................................................................................................... 59
    Binary output module ............................................................................................................. 59
    Binary input module ................................................................................................................ 59
    mA input module ..................................................................................................................... 60
7.4    Tests and environmental conditions ................................................................................ 60
    Disturbance tests .................................................................................................................... 60
    Voltage tests ............................................................................................................................ 60
    Mechanical tests ..................................................................................................................... 61
    Casing and package ................................................................................................................ 61
    Environmental conditions and Lifetime ............................................................................... 61
8      ORDERING INFORMATION ............................................................................................... 62
9      REFERENCE INFORMATION............................................................................................. 63
INSTRUCTION MANUAL AQ S391 - Bay control IED - Arcteq
Instruction manual –AQ S391 bay control IED                                      5 (63)

1 GENERAL
  The AQ S391 bay control IED is a member of the AQ-300 product line. The AQ-300
  protection product line in respect of hardware and software is a modular device. The
  hardware modules are assembled and configured according to the application IO
  requirements and the software determines the available functions. This manual
  describes the specific application of the AQ S391 bay control IED. All generic AQ 300
  series features such as color touch screen HMI but can be manufactured also without
  any displays. Wide range of communication protocols including IEC 61850, DNP3,
  IEC101, IEC103 and IEC104 are available in this device as well.
INSTRUCTION MANUAL AQ S391 - Bay control IED - Arcteq
Instruction manual –AQ S391 bay control IED                                      6 (63)

2 APPLICATION
   The AQ S391 bay control IED is suitable to various types of control and monitoring
   applications in extra-high voltage, high voltage and medium voltage applications. The
   modular hardware construction offers required options for different kind of bay
   configurations in terms of type and quantity of analogue and digital signals. The
   versatile programmable software logic allows for extensive customization of provided
   standard configurations.

   The IED may be applied to single or double breaker arrangements both in single or
   double busbar configurations. Control and monitoring of full diameter of one and half
   circuit breaker arrangement can be realized with a single IED as well.

   Motorized switching devices can be controlled from remote control system through
   communication or locally using the HMI. Synchrocheck function is provided for safe
   closing of circuit breakers.
INSTRUCTION MANUAL AQ S391 - Bay control IED - Arcteq
Instruction manual –AQ S391 bay control IED                                           7 (63)

3 MAIN CHARACTERISTICS OF THE AQ S391 BAY CONTROL
  IED
   -   Flexible and modular hardware construction allowing for multiple sets of current and
       voltage measurement modules, digital input and output modules and mA input
       modules
   -   Flexible software adaptation to different busbar and interlocking schemes using
       programmable logic functions
   -   Configurable MIMIC display
   -   Touch screen (TFT) colour display
   -   Local and remote control and/or status indication of up to 12 controllable objects
   -   Direct control mode or select before execute control mode
   -   CT supervision (CTS)
   -   Dead line detection features (DLD)
   -   Voltage transformer supervision (VTS)
   -   Synchrocheck and synchroswitch function over multiple circuit breakers
   -   Optional redundant power supply (80-300Vac/dc or 48Vdc)
   -   Programmable disturbance recorder for up to 100 records stored in non-volatile
       memory
   -   Event recorder for up to 10000 latest events stored in non-volatile memory
   -   IED time synchronization (e.g. SNTP or IRIG-B)
   -   Wide range of communication protocols, including IEC 61850
   -   IED self supervision functionality

3.1 SYSTEM DESIGN

   The AQ-300 protection device family is a scalable hardware platform to adapt to
   different applications. Data exchange is performed via a 32-bit high-speed digital non-
   multiplexed parallel bus with the help of a backplane module. Each module is
   identified by its location and there is no difference between module slots in terms of
   functionality. The only restriction is the position of the CPU module because it is
   limited to the “CPU” position. The built-in self-supervisory function minimizes the risk
   of device malfunctions.
INSTRUCTION MANUAL AQ S391 - Bay control IED - Arcteq
Instruction manual –AQ S391 bay control IED   8 (63)

Figure 1 CPU block diagram
Instruction manual –AQ S391 bay control IED                                          9 (63)

4 SOFTWARE SETUP OF THE IED
      In this chapter are presented the protection and control functions as well as the
      monitoring functions.

        Name           IEC       ANSI   Description
        CB Control      -          -    Circuit breaker control
        DS Control      -          -    Disconnector control
        DLD             -          -    Dead line detection
        VTS             -         60    Voltage transformer supervision
        CTS             -               Current transformer supervision
        SYN25         SYNC        25    Synchro-check function Δf, ΔU, Δφ
        DREC            -          -    Disturbance recorder
      Table 4-1 Available control and monitoring functions

 4.1 CIRCUIT BREAKER CONTROL BLOCK

4.1.1           APPLICATION

      The circuit breaker control block can be used to integrate the circuit breaker control of
      the AQ 300 device into the station control system and to apply active scheme screens
      of the local LCD of the device.

4.1.2           MODE OF OPERATION

      The circuit breaker control block receives remote commands from the SCADA system
      and local commands from the local LCD of the device, performs the prescribed
      checking and transmits the commands to the circuit breaker. It processes the status
      signals received from the circuit breaker and offers them to the status display of the
      local LCD and to the SCADA system.

      Main features:

  •     Local (LCD of the device) and Remote (SCADA) operation modes can be enabled or
        disabled individually.
  •     The signals and commands of the synchro check / synchro switch function block can be
        integrated into the operation of the function block.
  •     Interlocking functions can be programmed by the user applying the inputs “EnaOff” and
        “EnaOn”, using the graphic equation editor.
Instruction manual –AQ S391 bay control IED                                      10 (63)

  •     Programmed conditions can be used to temporarily disable the operation of the
        function block using the graphic equation editor.
  •     The function block supports the control models prescribed by the IEC 61850 standard.
  •     All necessary timing tasks are performed within the function block:
            o Time limitation to execute a command
            o Command pulse duration
            o Filtering the intermediate state of the circuit breaker
            o Checking the synchro check and synchro switch times
            o Controlling the individual steps of the manual commands
  •     Sending trip and close commands to the circuit breaker (to becombined with the trip
        commands of the protection functions and with the close command of the automatic
        reclosing function; the protection functions and the automatic reclosing function
        directly gives commands to the CB). The combination is made graphically using the
        graphic equation editor
  •     Operation counter
  •     Event reporting

4.1.3           AVAILABLE INTERNAL STATUS VARIABLE AND COMMAND CHANNEL

      To generate an active scheme on the local LCD, there is an internal status variable
      indicating the state of the circuit breaker. Different graphic symbols can be assigned
      to the values. (See AQtivate 300 software instructions for more details).

           Status variable                 Title                  Explanation
           CB1Pol_stVal_Ist_               Status                 Can be:
                                                                     0: Intermediate
                                                                     1: Off
                                                                     2: On
                                                                     3:Bad

      Table 4-2: Status variable of the circuit breaker control

      The available control channel to be selected is:

           Command channel                 Title                  Explanation
           CB1Pol_Oper_Con_                Operation              Can be:
                                                                     On
                                                                     Off

      Table 4-3: Command channel of the circuit breaker control

      Using this channel, the pushbuttons on the front panel of the device can be assigned
      to close or open the circuit breaker. These are the “Local commands”.
Instruction manual –AQ S391 bay control IED                                       11 (63)

                 Figure 4-1: Function block symbol of circuit breaker control

The binary input and output status signals of the circuit breaker control are listed in
tables below.
Instruction manual –AQ S391 bay control IED                                                         12 (63)

Binary status signal         Title         Explanation
CB1Pol_Local_GrO_            Local         If this input is active, the circuit breaker can be
                                           controlled using the local LCD of the device.
CB1Pol_Remote_GrO_           Remote        If this input is active, the circuit breaker can be
                                           controlled via remote communication channels of
                                           the SCADA system.
CB1Pol_SynOK_GrO_            SynOK         This input indicates if the synchron state of the
                                           voltage vectors at both sides of the circuit breaker
                                           enables the closing command. This signal is usually
                                           generated by the synchro check/ synchro switch
                                           function. If this function is not available, set the
                                           input to logic true.
CB1Pol_EnaOff_GrO_           EnaOff        The active state of this input enables the opening of
                                           the circuit breaker. The state is usually generated
                                           by the interlocking conditions defined by the user.
CB1Pol_EnaOn_GrO_            EnaOn         The active state of this input enables the closing of
                                           the circuit breaker. The state is usually generated
                                           by the interlocking conditions defined by the user.
CB1Pol_BlkProc_GrO_          BlkProc       The active state of this input blocks the operation of
                                           the circuit breaker. The conditions are defined by
                                           the user.
CB1Pol_stValOff_GrO_         stValOff      Off state of the circuit breaker.
CB1Pol_stValOn_GrO_          stValOn       On state of the circuit breaker.
CB1Pol_ExtTrip_GrO_          ExtTrip       External trip command for the circuit breaker (e.g.
                                           from protection). This signal is considered when
                                           evaluating unintended operation.

Table 4-4: The binary input status signals of the circuit breaker control

Binary status signal        Title                    Explanation
CB1Pol_CmdOff_GrI_          Off Command              Off command impulse, the duration of
                                                     which is defined by the parameter “Pulse
                                                     length”
CB1Pol_CmdOn_GrI_           On Command               On command impulse, the duration of
                                                     which is defined by the parameter “Pulse
                                                     length”
CB1Pol_StartSW_GrI_         Start Synchro-switch     If the synchro check/synchro switch
                                                     function is applied and the synchron state
                                                     conditions are not valid for the time
                                                     defined by the parameter “Max.SynChk
                                                     time”, then this output triggers the synchro
                                                     switch function (see synchro check/
                                                     synchro switch function block description).
CB1Pol_Oper_GrI_            CB Operated              An impulse with a duration of 150 ms at
                                                     any operation of the circuit breaker
CB1Pol_SelfOper_GrI_        Unintended Oper          This output is logic true if the status of the
                                                     circuit breaker has changed without
                                                     detected command from the SCADA
                                                     system or on the input “Ext trip”
CB1Pol_Opened_GrI_          Opened                   The filtered status signal for opened state
                                                     of the circuit breaker
CB1Pol_Closed_GrI_          Closed                   The filtered status signal for closed state of
                                                     the circuit breaker

Table 4-5: The binary output status signals of the decision logic
Instruction manual –AQ S391 bay control IED                                      13 (63)

4.1.4        CONFIGURATION EXAMPLES

        Example 1

    Figure 4-2: Simulation of the circuit breaker (and disconnectors; detail)

    In the Figure above the local/remote selection is made by another function block
    (Common).

    In VB1Pol, synchro check is not applied, the input “SynOK” is programmed for
    constant “True”.

    The circuit breaker can be switched any time, no interlocking is needed, the “EnaOff”
    and “EnaOn” are programmed for constant “True”. (However, note the similar
    DisConn_Bus function block in the Figure above.)

    The function block does not need to be blocked; the “BlkProc” input is not connected.

    The CB is simulated by an RS flip-flop, the status inputs are connected to the
    simulated signals.
Instruction manual –AQ S391 bay control IED                                      14 (63)

4.1.4.1 Example 2

    Figure 4-3: A simple application

    In Figure 4-3 above the local/remote selection is made by another function block
    (Common).

    In VB1Pol, synchro check is not applied, the input “SynOK” is programmed for
    constant “True”.

    Interlocking is applied; the “EnaOff” and “EnaOn” are programmed with external
    binary input signals.

    The function block does not need to be blocked; the “BlkProc” input is not connected.

    The CB status inputs are connected to the binary input signals.

    The commands are directed to another graphic page (to be “OR”-ed with the signals
    of the protection and automatic reclosing functions).

 4.2 DISCONNECTOR CONTROL FUNCTION

4.2.1        APPLICATION

    The disconnector control block can be used to integrate the disconnector control of
    the AQ 300 device into the station control system and to apply active scheme screens
    of the local LCD of the device.

4.2.2        MODE OF OPERATION

    The disconnector control block receives remote commands from the SCADA system
    and local commands from the local LCD of the device, performs the prescribed
    checking and transmits the commands to the disconnector. It processes the status
Instruction manual –AQ S391 bay control IED                                      15 (63)

      signals received from the disconnector and offers them to the status display of the
      local LCD and to the SCADA system.

      Main features:

  •     Local (LCD of the device) and Remote (SCADA) operation modes can be enabled or
        disabled individually.
  •     Interlocking functions can be programmed by the user applying the inputs “EnaOff” and
        “EnaOn”, using the graphic equation editor.
  •     Programmed conditions can be used to temporarily disable the operation of the
        function block using the graphic equation editor.
  •     The function block supports the control models prescribed by the IEC 61850 standard.
  •     All necessary timing tasks are performed within the function block:
           o Time limitation to execute a command
           o Command pulse duration
           o Filtering the intermediate state of the disconnector
           o Controlling the individual steps of the manual commands
  •     Trip and close commands to the disconnector
  •     Operation counter
  •     Event reporting

4.2.3          AVAILABLE INTERNAL STATUS VARIABLE AND COMMAND CHANNEL

      To generate an active scheme on the local LCD, there is an internal status variable
      indicating the state of the circuit breaker. Different graphic symbols can be assigned
      to the values. (See AQtivate 300 software instructions for more details).

           Status variable                Title                Explanation
           DisConn l_stVal_Ist_           Status               Can be:
                                                                  0: Intermediate
                                                                  1: Off
                                                                  2: On
                                                                  3:Bad

      Table 4-6: Status variable of the disconnector control

      The available control channel to be selected is:
Instruction manual –AQ S391 bay control IED                                    16 (63)

     Command channel                Title                Explanation
     DisConn _Oper_Con_             Operation            Can be:
                                                            On
                                                            Off

Table 4-7: Command channel of the disconnector control

Using this channel, the pushbuttons on the front panel of the device can be assigned
to close or open the disconnector. These are the “Local commands”.

Figure 4-4: The symbol of the function block

The binary input and output status signals of the disconnector control are listed in
tables below.
Instruction manual –AQ S391 bay control IED                                                        17 (63)

Binary status signal         Title        Explanation
DisConn_Local_GrO_           Local        If this input is active, the disconnector can be
                                          controlled using the local LCD of the device.
DisConn_Remote_GrO_          Remote       If this input is active, the disconnector can be
                                          controlled via remote communication channels of
                                          the SCADA system.
DisConn_EnaOff_GrO_          EnaOff       The active state of this input enables the opening of
                                          the disconnector. The state is usually generated by
                                          the interlocking conditions defined graphically by
                                          the user.
DisConn_EnaOn_GrO_           EnaOn        The active state of this input enables the closing of
                                          the disconnector. The state is usually generated by
                                          the interlocking conditions defined graphically by
                                          the user.
DisConn_BlkProc_GrO_         BlkProc      The active state of this input blocks the operation of
                                          the disconnector. The conditions are defined
                                          graphically by the user.
DisConn_stValOff_GrO_        stValOff     Off state of the disconnector.
DisConn_stValOn_GrO_         stValOn      On state of the disconnector.

Table 4-8: The binary input status signals of the disconnector control

Binary status signal       Title                    Explanation
DisConn_CmdOff_GrI_        Off Command              Off command impulse, the duration of
                                                    which is defined by the parameter “Pulse
                                                    length”
DisConn_CmdOn_GrI_         On Command               On command impulse, the duration of
                                                    which is defined by the parameter “Pulse
                                                    length”
DisConn_Oper_GrI_          CB Operated              An impulse with a duration of 150 ms at
                                                    any operation of the disconnector
DisConn_SelfOper_GrI       Unintended Oper          This output is logic true if the status of the
_                                                   disconnector      has    changed       without
                                                    detected command from the SCADA
                                                    system or on the input “Ext trip”
DisConn_Opened_GrI_        Opened                   The filtered status signal for opened state
                                                    of the disconnector
DisConn_Closed_GrI_        Closed                   The filtered status signal for closed state of
                                                    the disconnector

Table 4-9: The binary output status signals of the disconnector control
Instruction manual –AQ S391 bay control IED                                          18 (63)

4.2.4         CONFIGURATION EXAMPLE

    Figure 4-5: Simulation of the disconnector (and circuit breaker; detail)

    In the Figure above the local/remote selection is made by another function block
    (Common).

    The disconnector cannot be switched any time: interlocking is needed; the “EnaOff”
    and “EnaOn” are programmed for the “Opened” state of the circuit breaker.

    The function block does not need to be blocked; the “BlkProc” input is not connected.

    The disconnector is simulated by an RS flip-flop, the status inputs are connected to
    the simulated signals.

 4.3 DEAD LINE DETECTION FUNCTION

    The “Dead Line Detection” (DLD) function generates a signal indicating the dead or
    live state of the line. Additional signals are generated to indicate if the phase voltages
    and phase currents are above the pre-defined limits.

    The task of the “Dead Line Detection” (DLD) function is to decide the Dead line/Live
    line state.

    Criteria of “Dead line” state: all three phase voltages are below the voltage setting
    value AND all three currents are below the current setting value.
Instruction manual –AQ S391 bay control IED                                         19 (63)

Criteria of “Live line” state: all three phase voltages are above the voltage setting
value.

Dead line detection function is used in the voltage transformer supervision function
also as an additional condition.

In the figure below is presented the operating logic of the dead line detection function.

Figure 4-6: Principal scheme of the dead line detection function

The function block of the dead line detection function is shown in figure bellow. This
block shows all binary input and output status signals that are applicable in the
AQtivate 300 software.

Figure 4-7: The function of the dead line detection function

The binary input and output status signals of the dead line detection function are
listed in tables below.
Instruction manual –AQ S391 bay control IED                                                          20 (63)

   Table 4-10: The binary input signal of the dead line detection function

   Table 4-11: The binary output status signals of the dead line detection function

   Table 4-12Setting parameters of the dead line detection function

    Parameter       Setting value, range   Description
                    and step
    Operation       On                     Operating mode selection for the function. Operation can
                    Off                    be either disabled “Off” or enabled “On”. Default setting is
                                           enabled.
    Min. operate    10…100 % by step of    Minimum voltage threshold for detecting the live line
    voltage         1%                     status. All measured phase to ground voltages have to be
                                           under this setting level. Default setting is 60 %.
    Min. operate    8…100 % by step of     Minimum current threshold for detecting the dead line
    current         1%                     status. If all the phase to ground voltages are under the
                                           setting “Min. operate voltage” and also all the phase
                                           currents are under the “Min. operate current” setting the
                                           line status is considered “Dead”. Default setting is 10 %.

4.4 VOLTAGE TRANSFORMER SUPERVISION FUNCTION (VTS)

   The voltage transformer supervision function generates a signal to indicate an error in
   the voltage transformer secondary circuit. This signal can serve, for example, a
   warning, indicating disturbances in the measurement, or it can disable the operation
Instruction manual –AQ S391 bay control IED                                        21 (63)

of the distance protection function if appropriate measured voltage signals are not
available for a distance decision.

The voltage transformer supervision function is designed to detect faulty asymmetrical
states of the voltage transformer circuit caused, for example, by a broken conductor in
the secondary circuit. The voltage transformer supervision function can be used for
either tripping or alarming purposes.

The voltage transformer supervision function can be used in three different modes of
application:

Zero sequence detection (for typical applications in systems with grounded neutral):
“VT failure” signal is generated if the residual voltage (3Uo) is above the preset
voltage value AND the residual current (3Io) is below the preset current value

Negative sequence detection (for typical applications in systems with isolated or
resonant grounded (Petersen) neutral): “VT failure” signal is generated if the negative
sequence voltage component (U2) is above the preset voltage value AND the negative
sequence current component (I2) is below the preset current value.

Special application: “VT failure” signal is generated if the residual voltage (3Uo) is
above the preset voltage value AND the residual current (3Io) AND the negative
sequence current component (I2) are below the preset current values.

The voltage transformer supervision function can be triggered if “Live line” status is
detected for at least 200 ms. The purpose of this delay is to avoid mal-operation at
line energizing if the poles of the circuit breaker make contact with a time delay. The
function is set to be inactive if “Dead line” status is detected. If the conditions
specified by the selected mode of operation are fulfilled then the voltage transformer
supervision function is triggered and the operation signal is generated. When the
conditions for operation are no longer fulfilled, the resetting of the function depends
on the mode of operation of the primary circuit:

  • If the “Live line” state is valid, then the function resets after approx. 200 ms of
     time delay.

  • If the “Dead line” state is started and the “VTS Failure” signal has been
     continuous for at least 100 ms, then the “VTS failure” signal does not reset; it is
     generated continuously even when the line is in a disconnected state. Thus, the
     “VTS Failure” signal remains active at reclosing.
Instruction manual –AQ S391 bay control IED                                                         22 (63)

   • If the “Dead line” state is started and the “VTS Failure” signal has not been
        continuous for at least 100 ms, then the “VTS failure” signal resets.

                Preparation
                                                             VTS
   UL1                                 Negative
                                       Sequence
   UL2
                       Fourier
   UL3                                 Zero
                                       Sequence
 Parameters
                                                        VTS
                                                                                   Status signals
                                                        Algorithm    Decision
                                       Dead Line
                                       Detection                     Logic

                                          DLD

  IL1                                  Negative
                                       Sequence
  IL2
                      Fourier
  IL3                                  Zero
                                       Sequence

  Status
  signals

Figure 4-8: Operation logic of the voltage transformer supervision and dead line detection.

The voltage transformer supervision logic operates through decision logic presented in
the following figure.
Instruction manual –AQ S391 bay control IED                                                      23 (63)

  DLD_StIL1_GrI
  _                                                                                  DLD_
  DLD_StIL2_GrI                                                                      DeadLine_
  _                                                                                  GrI_
  DLD_StIL3_GrI
  _                  OR NOT
  DLD_StUL1_GrI
  _
  DLD_StUL2_GrI
  _
  DLD_StUL3_GrI
  _                                                                                  DLD_
                                                                                     LineOK_GrI_
                     AND

                            t       S
                            200

                                    R    AND
  VTS_Fail_int_
                                                       t      S                      VTS_
                         NOT                           100        OR       t         Fail_GrI_
  VTS_Blk_GrO_                                   OR                     100    AND
                                                       NOT    R

Figure 4-9: Decision logic of the voltage transformer supervision function.

NOTE: For the operation of the voltage transformer supervision function the “ Dead
line detection function” must be operable as well: it must be enabled by binary
parameter

   The symbol of the function block in the AQtivate 300 software

The function block of voltage transformer supervision function is shown in figure
below. This block shows all binary input and output status signals that are applicable
in the graphic equation editor.

Figure 4-10: The function block of the voltage transformer supervision function

The binary input and output status signals of voltage transformer supervision function
are listed in tables below.
Instruction manual –AQ S391 bay control IED                                                        24 (63)

   Binary status signal            Explanation
   VTS_Blk_GrO_                    Output status defined by the user to disable the voltage
                                   transformer supervision function.

   Table 4-13: The binary input signal of the voltage transformer supervision function

   Binary output signals         Signal title             Explanation
   VTS_Fail_GrI                  VT Failure               Failure status signal of the VTS function

   Table 4-14: The binary output signal of the voltage transformer supervision function

4.5 SYNCHROCHECK FUNCTION DU/DF (25)

   Several problems can occur in the power system if the circuit breaker closes and
   connects two systems operating asynchronously. The high current surge can cause
   damage in the interconnecting elements, the accelerating forces can overstress the
   shafts of rotating machines or the actions taken by the protective system can result in
   the eventual isolation of parts of the power system.

   To prevent such problems, this function checks if the systems to be interconnected
   are operating synchronously. If yes, then the close command is transmitted to the
   circuit breaker. In case of asynchronous operation, the close command is delayed to
   wait for the appropriate vector position of the voltage vectors on both sides of the
   circuit breaker. If the conditions for safe closing cannot be fulfilled within an expected
   time, then closing is declined.

   NOTE: For capacitive reference voltage measurement, the voltage measurement
   card can be ordered with
Instruction manual –AQ S391 bay control IED                                        25 (63)

The limits for automatic reclosing and manual close commands can be set
independently of each other.

The function compares the voltage of the line and the voltage of one of the busbar
sections (Bus1 or Bus2). The bus selection is made automatically based on a binary
input signal defined by the user.

For the reference of the synchrocheck any phase-to-ground or phase-to-phase
voltage can be selected.

The function processes the signals of the voltage transformer supervision function
and enables the close command only in case of plausible voltages.

The synchrocheck function monitors three modes of conditions:

  • Energizing check:

        • Dead bus, live line,

        • Live bus, dead line,

        • Any Energizing case (including Dead bus, dead line).

  • Synchro check (Live line, live bus)

  • Synchro switch (Live line, live bus)

If the conditions for “Energizing check” and “Synchro check” are fulfilled, then the
function generates the release command, and in case of a manual or automatic close
request, the close command is generated.

If the conditions for energizing and synchronous operation are not met when the close
request is received, then synchronous switching is attempted within the set time-out.
In this case, the rotating vectors must fulfill the conditions for safe switching within
the set waiting time: at the moment the contacts of the circuit breaker are closed, the
voltage vectors must match each other with appropriate accuracy. For this mode of
operation, the expected operating time of the circuit breaker must be set as a
parameter value, to generate the close command in advance taking the relative vector
rotation into consideration.

Started closing procedure can be interrupted by a cancel command defined by the
user.
Instruction manual –AQ S391 bay control IED                                         26 (63)

In “bypass” operation mode, the function generates the release signals and simply
transmits the close command.

In the following figure is presented the operating logic of the synchrocheck function.

                                                                 RelA

                   SwStA
                  CancelA                         SYN25_Eva
                                                     (aut)       SynSWA
                                                                 InProgA
             UlineFour(3ph)                                      UOKA
                Ubus1Four                                        FrOKA
                Ubus2Four                                        AngOKA
                               SYN25_Com
                   Bus Sel

                   VTS Blk
                                                                 RelM
              Bus1 VTS Blk
              Bus2 VTS Blk
                        Blk                       SYN25_Eva
                                                     (man)
                                                                 SynSWM
                    SwStM                                        InProgM
                  CancelM                                        UOKM
                                                                 FrOKM

                Parameters                                       AngOKM

               Figure 4-11: Operation logic of the synchrocheck function.

The synchro check/synchro switch function contains two kinds of software blocks:

     • SYN25_Com is a common block for manual switching and automatic switching
     • SYN25_EVA is an evaluation block, duplicated for manual switching and for
        automatic switching
The SYN25_Com block selects the appropriate voltages for processing and calculates
the voltage difference, the frequency difference and the phase angle difference
between the selected voltages. The magnitude of the selected voltages is passed for
further evaluation.

These values are further processed by the evaluation software blocks. The function is
disabled if the binary input (Block) signal is TRUE. The activation of voltage
transformer supervision function of the line voltage blocks the operation (VTS Block).
The activation of voltage transformer supervision function of the selected bus section
blocks the operation (VTS Bus1 Block or VTS Bus2 Block).
Instruction manual –AQ S391 bay control IED                                           27 (63)

                      SYN25_Com

                                                                          -U_diff
   UlineFour (3ph)
                                                              Calc        -f_diff
     Ubus1Four
                      U_bus
                                                                          -fi_ diff
     Ubus2Four
                                                                          -U_bus

                                                                          -U_line
          BusSel
                                       1000ms
                                       100m
                                       s                Blk
          VTS Blk                                  OR

     Bus1 VTS Blk
                        VTS
                       U_bus
     Bus2 VTS Blk

       Parameters

    Figure 4-12: Synchrocheck common difference calculation function structure.

If the active bus section changes the function is dynamically blocked for 1000ms and
no release signal or switching command is generated. The processed line voltage is
selected based on the preset parameter (Voltage select). The choice is: L1-N, L2-N,
L3-N, L1-L2, L2-L3 or L3-L1. The parameter value must match the input voltages
received from the bus sections. The active bus section is selected by the input signal
(Bus select). If this signal is logic TRUE, then the voltage of Bus2 is selected for
evaluation.

The software block SYN25_Eva is applied separately for automatic and manual
commands. This separation allows the application to use different parameter values
for the two modes of operation.

The structure of the evaluation software block is shown in the following figure.
Instruction manual –AQ S391 bay control IED                                         28 (63)

Figure 4-13: Synchrocheck evaluation function structure.

This evaluation software block is used for two purposes: for the automatic reclosing
command (the signal names have the suffix “A”) and for the manual close request (the
signal names have the suffix “M”). As the first step, based on the selected line voltage
and bus voltage, the state of the required switching is decided (Dead bus-Dead line,
Dead bus-Live line, Live bus-Dead line or Live bus- Live line). The parameters for
decision are (U Live) and (U Dead). The parameters (Energizing Auto/Manual) enable
the operation individually. The choice is: (Off, DeadBus LiveLine, LiveBus DeadLine,
Any energ case). In simple energizing modes, no further checking is needed. This
mode selection is bypassed if the parameter (Operation Auto/Manual) is set to
“ByPass”. In this case the command is transmitted without any further checking.

First, the function tries switching with synchro check. This is possible if: the voltage
difference is within the defined limits (Udiff SynChk Auto/Manual)) the frequency
difference is within the defined limits (FrDiff SynChk Auto) and the phase angle
difference is within the defined limits (MaxPhaseDiff Auto/Manual)).

If the conditions are fulfilled for at least 45 ms, then the function generates a release
output signal (Release Auto/Manual).

If the conditions for synchro check operation are not fulfilled and a close request is
received as the input signal (SySwitch Auto/Manual), then synchro switching is
Instruction manual –AQ S391 bay control IED                                          29 (63)

attempted. This is possible if: the voltage difference is within the defined limits (Udiff
SynSW Auto /Manual)) the frequency difference is within the defined limits (FrDiff
SynSW Auto).

These parameters are independent of those for the synchro check function. If the
conditions for synchro check are not fulfilled and the conditions for synchro switch are
OK, then the relative rotation of the voltage vectors is monitored. The command is
generated before the synchronous position, taking the breaker closing time into
consideration (Breaker Time). The pulse duration is defined by the parameter (Close
Pulse). In case of slow rotation and if the vectors are for long time near-opposite
vector positions, no switching is possible, therefore the waiting time is limited by the
preset parameter (Max.Switch Time).

The progress is indicated by the output status signal (SynInProgr Auto/Manual). The
started command can be canceled using the input signal (Cancel Auto/Manual).

   Figure 4-14 The function block of the synchro check / synchro switch function
The binary input and output status signals of the dead line detection function are
listed in tables below.
Instruction manual –AQ S391 bay control IED                                               30 (63)

Table 4-15 The binary input signal of the synchro check / synchro switch function

 Binary status signal        Title              Explanation
                                                If this signal is logic TRUE, then the voltage
 SYN25_BusSel_GrO_           Bus Select         of Bus2 is selected for evaluation
                                                Blocking signal of the voltage transformer
                                                supervision function evaluating the line
 SYN25_VTSBlk_GrO_           VTS Block          voltage
                                                Blocking signal of the voltage transformer
                                                supervision function evaluating the Bus1
 SYN25_Bus1VTSBlk_GrO_       VTS Bus1 Block     voltage
                                                Blocking signal of the voltage transformer
                                                supervision function evaluating the Bus2
 SYN25_Bus2VTSBlk_GrO_       VTS Bus2 Block     voltage
                                                Switching request signal initiated by the
 SYN25_SwStA_GrO_            SySwitch Auto      automatic reclosing function
                                                Signal to interrupt (cancel) the automatic
 SYN25_CancelA_GrO_          Cancel Auto        switching procedure
 SYN25_Blk_GrO_              Block              Blocking signal of the function
                                                Switching request signal initiated by
 SYN25_SwStM_GrO_            SySwitch Manual    manual closing
                                                Signal to interrupt (cancel) the manual
 SYN25_CancelIM_GrO_         Cancel Manual      switching procedure
Instruction manual –AQ S391 bay control IED                                         31 (63)

Table 4-16 The binary output status signals of the synchro check / synchro switch
function

 Binary status signal       Title              Explanation
                                               Releasing the close command initiated by
 SYN25_RelA_GrI_            Release Auto       the automatic reclosing function
                                               Switching procedure is in progress,
                                               initiated by the automatic reclosing
 SYN25_InProgA_GrI_         SynInProgr Auto    function
                                               The Voltage difference is appropriate for
 SYN25_UOKA_GrI_            Udiff OK Auto      automatic closing command
                                               The frequency difference is appropriate
                                               for automatic closing command, evaluated
 SYN25_FrOKA_GrI_           FreqDiff OK Auto   for synchro-check
                                               The angle difference is appropriatefor
 SYN25_AngOKA_GrI_          Angle OK Auto      automatic closing command
                                               Releasing the close command initiated by
 SYN25_RelM_GrI_            Release Man        manual closing request
                                               Switching procedure is in progress,
 SYN25_InProgM_GrI_         SynInProgr Man     initiated by the manual closing command
                                               The Voltage difference is appropriate for
 SYN25_UOKM_GrI_            Udiff OK Man       automatic closing command
                                               The frequency difference is appropriate
                                               for manual closing command, evaluated
 SYN25_FrOKM_GrI_           FreqDiff OK Man    for synchro-check
                                               The angle difference is appropriatefor
 SYN25_AngOKM_Grl_          Angle OK Man       manual closing command
Instruction manual –AQ S391 bay control IED                                                          32 (63)

Table 4-17 Setting parameters of the synchro check / synchro switch function

 Parameter         Setting value, range   Description
                   and step
 Voltage select    L1-N                   Reference voltage selection. The function will monitor the
                   L2-N                   selected voltage for magnitude, frequency and angle
                   L3-N                   differences. Default setting is L1-N
                   L1-L2
                   L2-L3
                   L3-L1
 U Live            60…110 % by step of    Voltage setting limit for “Live Line” detection. When
                   1%                     measured voltage is above the setting value the line is
                                          considered “Live”. Default setting is 70 %.
 U Dead            10…60 % by step of     Voltage setting limit for “Dead Line” detection. When
                   1%                     measured voltage is below the setting value the line is
                                          considered “dead”. Default setting is 30 %.
 Breaker Time      0…500 ms by step of    Breaker operating time at closing. This parameter is used
                   1 ms                   for the synchro switch closing command compensation and
                                          it describes the breaker travel time from open position to
                                          closed position from the close command. Default setting is
                                          80 ms.
 Close Pulse       10…60000 ms by         Close command pulse length. This setting defines the
                   step of 1 ms           duration of close command from the IED to the circuit
                                          breaker. Default setting is 1000 ms.
 Max      Switch   100…60000 ms by        Maximum allowed switching time. In case synchro check
 Time              step of 1 ms           conditions are not fulfilled and the rotation of the networks
                                          is slow this parameter defines the maximum waiting time
                                          after which the close command is failed. Default setting is
                                          2000ms.
 Operation         On                     Operation mode for automatic switching. Selection can be
 Auto              Off                    automatic switching off, on or bypassed. If the Operation
                   ByPass                 Auto is set to “Off” automatic switch checking is disabled. If
                                          selection is “ByPass” Automatic switching is enabled with
                                          bypassing the bus and line energization status checking.
                                          When the selection is “On” also the energization status of
                                          bus and line are checked before processing the command.
                                          Default setting is “On”
 SynSW Auto        On                     Automatic synchroswitching selection. Selection may be
                   Off                    enabled “On” or disabled “Off”. Default setting is Enabled
                                          “On”.
 Energizing        Off                    Energizing mode of automatic synchroswitching. Selections
 Auto              DeadBus LiveLine       consist of the monitoring of the energization status of the
                   LiveBus DeadLine       bus and line. If the operation is wanted to be LiveBus
                   Any energ case         LiveLine or DeadBus DeadLine the selection is “Any energ
                                          case”. Default setting is DeadBus LiveLine.
 Udiff SynChk      5…30 % by step of 1    Voltage difference checking of the automatic synchrocheck
 Auto              %                      mode. If the measured voltage difference is below this
                                          setting the condition applies. Default setting is 10 %.
 Udiff    SynSW    5…30 % by step of 1    Voltage difference checking of the automatic synchroswitch
 Auto              %                      mode. If the measured voltage difference is below this
                                          setting the condition applies. Default setting is 10 %.
 MaxPhasediff      5…80 deg by step of    Phase difference checking of the automatic synchroswitch
 Auto              1 deg                  mode. If the measured phase difference is below this
                                          setting the condition applies. Default setting is 20 deg.
Instruction manual –AQ S391 bay control IED                                                      33 (63)

 FrDiff SynChk   0.02…0.50 Hz by       Frequency difference checking of the automatic
 Auto            step of 0.01 Hz       synchrocheck mode. If the measured phase difference is
                                       below this setting the condition applies. Default setting is
                                       0.02 Hz.
 FrDiff SynSW    0.10…1.00 Hz by       Frequency difference checking of the automatic
 Auto            step of 0.01 Hz       synchroswitch mode. If the measured phase difference is
                                       below this setting the condition applies. Default setting is
                                       0.2 Hz.
 Operation       On                    Operation mode for manual switching. Selection can be
 Man             Off                   manual switching off, on or bypassed. If the Operation Man
                 ByPass                is set to “Off” manual switch checking is disabled. If
                                       selection is “ByPass” manual switching is enabled with
                                       bypassing the bus and line energization status checking.
                                       When the selection is “On” also the energization status of
                                       bus and line are checked before processing the command.
                                       Default setting is “On”
 SynSW Man       On                    Manual synchroswitching selection. Selection may be
                 Off                   enabled “On” or disabled “Off”. Default setting is Enabled
                                       “On”.
 Energizing      Off                   Energizing mode of manual synchroswitching. Selections
 Man             DeadBus LiveLine      consist of the monitoring of the energization status of the
                 LiveBus DeadLine      bus and line. If the operation is wanted to be LiveBus
                 Any energ case        LiveLine or DeadBus DeadLine the selection is “Any energ
                                       case”. Default setting is DeadBus LiveLine.
 Udiff SynChk    5…30 % by step of 1   Voltage difference checking of the manual synchrocheck
 Man             %                     mode. If the measured voltage difference is below this
                                       setting the condition applies. Default setting is 10 %.
 Udiff   SynSW   5…30 % by step of 1   Voltage difference checking of the manual synchroswitch
 Man             %                     mode. If the measured voltage difference is below this
                                       setting the condition applies. Default setting is 10 %.
 MaxPhaseDiff    5…80 deg by step of   Phase difference checking of the manual synchroswitch
 Man             1 deg                 mode. If the measured phase difference is below this
                                       setting the condition applies. Default setting is 20 deg.
 FrDiff SynChk   0.02…0.50 Hz by       Frequency difference checking of the manual synchrocheck
 Man             step of 0.01 Hz       mode. If the measured phase difference is below this
                                       setting the condition applies. Default setting is 0.02 Hz.
 FrDiff SynSW    0.10…1.00 Hz by       Frequency difference checking of the manual synchroswitch
 Man             step of 0.01 Hz       mode. If the measured phase difference is below this
                                       setting the condition applies. Default setting is 0.2 Hz.
Instruction manual –AQ S391 bay control IED   34 (63)

5 APPLICATION EXAMPLES

5.1 ONE AND HALF CIRCUIT BREAKER CONFIGURATION
Instruction manual –AQ S391 bay control IED                       35 (63)

5.2 IED IO POSITIONS IN ONE AND HALF CIRCUIT BREAKER CONFIGURATION
Instruction manual –AQ S391 bay control IED                                         36 (63)

6 CONSTRUCTIONS AND INSTALLATION
   The Arcteq AQ-S391 bay control IED consists of hardware modules. Due to modular
   structure optional positions for the slots can be user defined in the ordering of the IED
   to include I/O modules and other types of additional modules. An example module
   arrangement configuration of the AQS391 is shown in the figure below. Visit
   https://configurator.arcteq.fi/ to see all of the available options.

   Figure 6-1: An example module arrangement configuration of the AQ-S391 IED.

   Example above presents a simple hardware configuration with redundant power
   supplies (PS+2103), signaling binary outputs (R16+0000), binary input cards
   (O16+1101 and O8+1101) and 100Base-FX Ethernet MM/LC communication card
   (CPU+6601).

   Figure 6-2: An example module arrangement configuration of the AQ-S391 IED.

   Example above presents a simple hardware configuration with redundant power
   supplies (PS+2103), trip contacts (TRIP+2101), signaling binary outputs (R12+0000),
Instruction manual –AQ S391 bay control IED                        37 (63)

binary input cards (O16+1101 and O8+1101) and 100Base-FX Ethernet MM/LC
communication card (CPU+6601).

Following chapters describe the cards in more detail.
Instruction manual –AQ S391 bay control IED                                    38 (63)

6.1 CPU MODULE

  Figure 3 Communication card with 100Base-FX Ethernet MM/LC 1300 nm, 50/62.5/125 μm
  connector, (up to 2 km) fiber.

  The CPU module contains all the protection, control and communication functions of
  the AQ-300 device. Dual 500 MHz high-performance Analog Devices Blackfin
  processors separate relay functions (RDSP) from communication and HMI functions
  (CDSP). Reliable communication between processors is performed via high-speed
  synchronous serial internal bus (SPORT). Each processor has its own operative
  memory such as SDRAM and non-volatile flash memories for configuration, parameter
  and firmware storage. The firmwares are stored in a dedicated flash memory
  independent from the disturbance recorder and event storage. CDSP’s operating
  system (uClinux) utilizes a robust JFFS flash file system, which enables fail-safe
  operation and the storage of disturbance record files, configuration and parameters.

  The RDSP core runs at 500 MHz and its external bus speed is 125 MHz. The
  backplane data speed is limited to approx. 20 MHz, which is more than enough for
  module data throughput. An additional logic element (CPLD and SRAM) is used as a
  bridge between the RDSP and the backplane. The CPLD collects analogue samples
  from CT/VT modules and also controls signaling outputs and inputs.
Instruction manual –AQ S391 bay control IED                                      39 (63)

After power-up the RDSP processor starts up with the previously saved configuration
and parameters. Generally, the power-up procedure for the RDSP and relay functions
takes only a few seconds. That is to say, it is ready to trip within this time. CDSP’s
start-up procedure is longer because its operating system needs time to build its file
system, initializing user applications such as HMI functions and the IEC61850
software stack.

HMI and communication tasks

   •   Embedded WEB-server:
         o Firmware upgrade possibility
          o   Modification of user parameters
          o   Events list and disturbance records
          o   Password management
          o   Online data measurement
          o   Commands
           o Administrative tasks
   •   Front panel TFT display handling: the interactive menu set is available through
       the TFT and the touchscreen interface
   •   User keys: capacitive touch keys on front panel
   •   The built-in 5-port Ethernet switch allows AQ-300 to connect to IP/Ethernet-
       based networks. The following Ethernet ports are available:
          o Station bus (100Base-FX Ethernet) SBW
          o Redundant station bus (100Base-FX Ethernet) SBR
          o Process bus (100Base-FX Ethernet)
          o EOB or EOB2 (Ethernet Over Board) or RJ-45 Ethernet user interface on
              front panel
          o Optional 10/100Base-T port via RJ-45 connector
   •   PRP/HSR     seamless redundancy for          Ethernet networking (100Base-FX
       Ethernet)
   •   Other communication:
          o RS422/RS485 interfaces (galvanic interface to support legacy or other
              serial protocols, ASIF)
          o   Plastic or glass fiber interfaces to support legacy protocols, ASIF
          o   Proprietary process bus communication controller on COM+ module
          o   Telecommunication interfaces: G.703, IEEE C37.94
Instruction manual –AQ S391 bay control IED                                    40 (63)

6.2 POWER SUPPLY MODULE

  The power supply module converts primary AC and/or DC voltage to required system
  voltages. In most applications, one power supply module is sufficient to provide the
  required power to the system. Redundant power supply modules extend system
  availability in case of the outage of any power source.

  IMPORTANT: Depending on the hardware configuration, the power consumption of
  the devices can be different. We reserve the right to make the decision about which
  PS+ module must be used. For most applications where the power consumption does
  not reach 30 W we use one of our 4 HP wide PS+ modules.

  Figure 4 Power supply module connections

  Module type                                   PS+2101
  Nominal voltage                               110 V DC / 220 V DC
  Input voltage range                           88 - 264 V DC
                                                80 – 250 V AC
  Nominal power                                 20 W
  Input voltage interruption time (at           Min. 100ms in the specified input
  nominal load)                                 voltage range
  Internal fuse                                 3.15A/250V
  Connector type                                Power                     connector:
Instruction manual –AQ S391 bay control IED                                           41 (63)

                                                         Receptacle: Weidmüller SLA 2/90
                                                         Plug: Weidmüller BLA 2/180

                                                         Fault          relay         connector:
                                                         Receptacle: Weidmüller SLA 3/90
                                                         Plug: Weidmüller BLA 3/180

         Main features:

             •   Fault relay contacts (NC and NO): device fault contact and also assignable to
                 user functions. All the three relay contact points are accessible to users.
             •   Redundant applications (nominal power and reliability can be increased by
                 using parallel power supplies)
             •   On-board self-supervisory circuits: temperature and voltage monitors
             •   Short-circuit-protected outputs
             •   Efficiency: > 70 %, power consumption = nominal power / efficiency
             •   Passive heatsink
             •   Early power failure indication signals to the CPU the possibility of power
                 outage, thus the CPU has enough time to save the necessary data to non-
                 volatile memory
             •   Inrush current (until 0.1 s): < 10 A for all types excluding PS+4401 which has <
                 21 A inrush current.
             •   Common features for internal fuses:
                    o   5 mm x 20 mm (0.20" x 0.79")
                    o   TT characteristics (very inverse time-lag)
                    o   35 A @ 250 V AC rated breaking capacity
•   Recommended external protection: miniature circuit breaker, 6 A (C char.)
Instruction manual –AQ S391 bay control IED                                        42 (63)

6.3 BINARY INPUT MODULES

   The inputs are galvanic isolated and the module converts high-voltage signals to the
   voltage level and format of the internal circuits.

   Module type             O8+2401            O8+4801       O8+1101          O8+2201
   Number of                   8                  8             8                 8
   channels
   Time                   Configured         Configured    Configured        Configured
   synchronization        by AQtivate       by AQtivate    by AQtivate      by AQtivate
   Rated voltage              24 V              48 V          110 V            220 V
   Thermal                    72 V              100 V         250 V            320 V
   withstand
   voltage
   Clamp voltage          Falling 0.64      Falling 0.64   Falling 0.64     Falling 0.64
                               Un                Un             Un               Un
                           Rising 0.8        Rising 0.8     Rising 0.8       Rising 0.8
                               Un                Un             Un               Un
   Grounding             independent        independent    independent      independent
   groups
   Connector type        Receptacle:          Weidmüller              SLA          16/90
                         Plug: Weidmüller BLA 16/180

   Module type            O12+2401           O12+4801      O12+1101         O12+2201
   Number of                   12                12            12               12
   channels
   Time                   Configured        Configured     Configured       Configured
   synchronization        by AQtivate       by AQtivate    by AQtivate      by AQtivate
   Rated voltage              24 V              48 V          110 V            220 V
   Thermal                    72 V              72 V          250 V            320 V
   withstand
   voltage
   Clamp voltage          Falling 0.64      Falling 0.64   Falling 0.64     Falling 0.64
                              Un                 Un            Un               Un
                           Rising 0.8        Rising 0.8    Rising 0.8       Rising 0.8
                              Un                 Un            Un               Un
   Grounding                 4x3                4x3           4x3              4x3
   groups                  common             common        common           common
                            ground             ground        ground           ground
You can also read