Installation, operating and maintenance instructions EKO-SRB1 Table of Contents Product handling.........................................3 General assembly........................................4 Mounting accessories.................................5 Installation instructions............................ 5-6 Operation and maintenance........................7 Declaration Of Performance........................8 2 Owner of place of manufacture: EKOVENT AB, Vellinge Certification: 0402 SP Certification Product type description: EKO-SRB1 Aproval number: SC0848-13 Fire classification: E 60 (ve i< >o, ho i< >o) SC20 000 EKOVENT AB We reserve the right to make changes 2021-03
Product handling on the construction site Transport Storage The fire dampers are transported to the The storage of materials on the site should construction site with a forklift or crane be planned so that you get the least pos- with a lifting fork. To avoid damage, they sible internal transport. The fire dampers must be lifted, not dragged and never lo- must be protected against water and wered hard against the ground. always stored in a dry place. Furthermore, they must be handled so that no mechani- Reception and inspection cal damage occurs to them. of the delivery The fire dampers are inspected imme- Commissioning diately when the delivery arrives at the The fire dampers must not be put into use workplace. The inspection is to check that until the entire installation is in operational the delivery corresponds to the order and condition. the consignment note. The approved deli- very is acknowledged on the consignment note. Products with defects or defects must not be installed. Contact the supplier immediately. 3 EKOVENT AB hereby disclaims all responsibility for: – Damage due to incorrect transport, EKOVENT:s liability shall be limited to repair handling or storage. or replacement of faulty equipment part. – That the user has failed to inspect, maintain and to a reasonable extent take care of the equipment. – Personal injury or property damage as a result of using the product in violation of the instructions and specifications in this manual. EKOVENT AB We reserve the right to make changes 2021-03
Installation, operating and maintenance instructions EKO-SRB1 General assembly Why Fire dampers? Fire dampers are one of several factors in a building that together must provide good fire protection in the event of a fire. The fire protection requirements are mainly affected by building class, fire load, heat output, air supply, the rescue service’s response time and the presence of fire protection technical installations. An al- ternative to calculations or to prove that selected solutions meet the set functional requirements is to use P- and CE-marked products. Mounting Electrical connection In order for the P- and CE marking to To be performed by a qualified electrician apply, assembly must always take place according to drawings and current wiring 4 in accordance with the supplied assembly diagram. instructions. Other details such as flexible wall sleeve and wall to damper caulking are ordered separately. The hole size is always the damper diameter + 55 mm. Wiring diagram actuator EKOVENT AB We reserve the right to make changes 2021-03
Mounting accessories EKO-SRB1 Flexible wall sleeve EKO-GIS Installation 90 5 Mounting instructions EKO-SRB1 Installation in flexible wall sleeve EKO-GIS Gipsväggstos EKO-GIS_mellanvägg 2013 Plåtskruv eller popnit av stål 1. Squeeze the wall sleeve EKO-GIS and insert it into the hole. 2. Lock the wall sleeve with a sheet metal screw or pop rivets in the overlap. EKO SRBG Gipsväggsstos Mont 2013 EKOVENT AB We reserve the right to make changes 2021-03
Installation, operating and maintenance instructions EKO-SRB1 Assembly instruction EKO-SRB1 Supporting construction - wall or floor in fire resistance class EI 60. P-approval SC0848-13 Suspension Duct EKO- Ø A+55 SRB1 Duct Duct EKO- SRB1 Fire sealant * Duct 6 Fire sealant * Important! The smoke damper should always be installed with the blade EKO-SRB1 Mont schakt 2014 shaft horizontal.. 1. The duct system should be suspen- – The damper blade shaft must always ded and insulated in accordance with be installed horizontally. the fire resistance of the supporting 3. Mount the thermal sensor with the sen- construction in which the hole is made sor probe in the air flow, ensuring that it (EI 60). Insulation of the ventilation does not obstruct the movement of the duct must be done in accordance with damper blade. “Installationsbrandskydd Ventilation – Rör” section 21.3.4 (ISBN: 978-91- 4. The following minimum dimensions 633-1723-1) corresponding to the fire must be observed when mounting resistance of the supporting construc- – Minimum distance between dampers: tion in which the hole is made (EI 60). 200 mm. – Minimum distance to supporting con- 2. Mount the damper in the duct. struction: 75 mm. – No gaps between the damper and the supporting construction. * Fire sealing must be done using an approved method that complies with the relevant fire classification, e.g. EKO-KER, EKO-GIS and fire protection sealant. EKOVENT AB We reserve the right to make changes 2021-03
Operation and maintenance Operation check which is located on the front of Fire damper EKO-SRB1 is a P- and CE the monitoring unit (applies to EKO-KE). marked damper for fire separation of hea- Powerless damper closes. Check that ting, ventilation and air conditioning instal- the damper is fully open during opera- lations in buildings. EKO-SRB1 is always tion, closes and opens completely during supplied with an electric safety actuator testing and closes completely in the event complete with thermal sensor that discon- of a power failure. Otherwise follow the nects the power to the actuator if the tem- instructions for monitoring systems EKO – perature exceeds 72 °C. The facility must MKE/SKE, EKO-KE, EKO-TME/TSE, MME/ have a smoke detector which indicates an SME. alarm and which closes the fire damper and which must be connected to moni- Cleaning toring systems EKO-MKE/SKE, EKO-KE, We advocate preventive maintenance of EKO-TME/TSE, MME/SME or equivalent. the damper according to the facilities Automatic function check takes place eve- needs. Clean the damper blade and dam- ry 48 hours (or at more frequent intervals), per (inside) with a brush, vacuuming or malfunction is shown in the display. wiping. NOTE! Water or other liquids must not be used. Regular testing according to Maintenance 7 the P-approval. External and internal control At least every three years, check the elec- Note! trical wiring for actuators, end position After inspection, the fire damper must contacts and smoke detectors as well as be left in normal working position. the damper cover so that no foreign de- tails can prevent the damper blade from Warning! moving. Also check the attachment of Never keep your hands inside the dam- the actuator, damper blade and sealing per when it closes. Risk of crushing strip so that no damage has occurred. injuries. Also check that the corrosion protection is intact. Spare parts list Function control Actuator, see type designation of the ac- Automatic: see above. tuator. Manuell: Manual: Manual function check can be performed from the central unit menu. During installation, manual function check can also be performed on the re- spective slave unit (applies to EKO-MKE/ SKE, EKO-TME/TSE, MME/SME). Manual function check can be done by pressing the test button for automatic function EKOVENT AB We reserve the right to make changes 2021-03
Installation, operating and maintenance instructions EKO-SRB1 Declaration Of Performance DECLARATION OF PERFORMAN CE Fire Damper SRB1 Type and batch number accord ing to product label. Fire damper to be used in conjun ction with fire separating eleme compartmentation of at least 60 nts to maintain fire min according to EN 15650.2010 EKOVENT AB, Mejselgatan 7, 23532 Vellinge, www.ekovent.se Certificate: SP Technical Research Institute of Sweden, nr 0402, has perfor the manufacturing plant and factor med type testing, initial inspection y production control (FPC) under of system 1 EC Certificate of Conformity 0402- CPR-SC0844-13 Size Type Ø 100 mm till Ø 630 mm Classification 8 Horizontal duct E 60 (ho i o) S Vertical duct E 60 (Ve i o) S Classification according to EN 13501 -3 Nominal activation conditions/s ensitivity: Pass - Sensing element load bearing ISO 10294-4 capacity - Sensing element response tempe rature Response delay (reponse time): Pass EN 1366-2 -Closure time Operational reliability: Pass EN 1366-2 -Cycling Durability of response delay: Pass EN 1366-2 - Sensing element responset o temperature and load bearing capac ity Durability of operational reliability: 20 000 cycles -Pass EN 15650:2010 -Open and closing cycle tests The performance of SRB1 is in confo rmity with the declared performance above. This declaration of performance is issued under the sole responsibili ty of EKOVENT AB. Signed for and on behalf of the manufacturer by: ______________________________ _________ Vellinge 2017-09-20, Michael Bränd ström R&D Manager EKOVENT AB, Mejselgatan 7 SE-235 32 Vellinge Sweden, +46 40 42 16 00 EKOVENT AB We reserve the right to make changes 2021-03
Notes: 9 EKOVENT AB We reserve the right to make changes 2021-03