Fire damper EKO-SRB1

     Installation, operating and maintenance instructions 2021-03
Installation, operating and maintenance instructions EKO-SRB1

                                                    Table of Contents

                                                                Product handling.........................................3
                                                                General assembly........................................4
                                                                Mounting accessories.................................5
                                                                Installation instructions............................ 5-6
                                                                Operation and maintenance........................7
                                                                Declaration Of Performance........................8

2

        Owner of place of manufacture: EKOVENT AB, Vellinge

             Certification:                       0402 SP Certification

             Product type description:            EKO-SRB1

             Aproval number:                      SC0848-13

             Fire classification:                 E 60 (ve i< >o, ho i< >o) SC20 000

    EKOVENT AB                           We reserve the right to make changes                                     2021-03
Product handling on the construction site

Transport                                                         Storage
The fire dampers are transported to the                           The storage of materials on the site should
construction site with a forklift or crane                        be planned so that you get the least pos-
with a lifting fork. To avoid damage, they                        sible internal transport. The fire dampers
must be lifted, not dragged and never lo-                         must be protected against water and
wered hard against the ground.                                    always stored in a dry place. Furthermore,
                                                                  they must be handled so that no mechani-
Reception and inspection                                          cal damage occurs to them.
of the delivery
The fire dampers are inspected imme-                              Commissioning
diately when the delivery arrives at the                          The fire dampers must not be put into use
workplace. The inspection is to check that                        until the entire installation is in operational
the delivery corresponds to the order and                         condition.
the consignment note. The approved deli-
very is acknowledged on the consignment
note. Products with defects or defects
must not be installed. Contact the supplier
immediately.                                                                                                             3

    EKOVENT AB hereby disclaims all responsibility for:
    –    Damage due to incorrect transport,                       EKOVENT:s liability shall be limited to repair
         handling or storage.                                     or replacement of faulty equipment part.
    –    That the user has failed to inspect,
         maintain and to a reasonable extent
         take care of the equipment.

    –    Personal injury or property damage as
         a result of using the product in violation
         of the instructions and specifications in
         this manual.

EKOVENT AB                                We reserve the right to make changes                                 2021-03
Installation, operating and maintenance instructions EKO-SRB1

    General assembly

    Why Fire dampers?
    Fire dampers are one of several factors
    in a building that together must provide
    good fire protection in the event of a fire.
    The fire protection requirements are mainly
    affected by building class, fire load, heat
    output, air supply, the rescue service’s
    response time and the presence of fire
    protection technical installations. An al-
    ternative to calculations or to prove that
    selected solutions meet the set functional
    requirements is to use P- and CE-marked
    products.

    Mounting                                                    Electrical connection
    In order for the P- and CE marking to                       To be performed by a qualified electrician
    apply, assembly must always take place                      according to drawings and current wiring
4   in accordance with the supplied assembly                    diagram.
    instructions. Other details such as flexible
    wall sleeve and wall to damper caulking are
    ordered separately. The hole size is always
    the damper diameter + 55 mm.

    Wiring diagram actuator

    EKOVENT AB                          We reserve the right to make changes                          2021-03
Mounting accessories EKO-SRB1

Flexible wall sleeve EKO-GIS

Installation

   90

                                                                                                          5

Mounting instructions EKO-SRB1

Installation in flexible wall
sleeve EKO-GIS

                  Gipsväggstos EKO-GIS_mellanvägg 2013

                                                 Plåtskruv eller
                                                 popnit av stål

1. Squeeze the wall sleeve EKO-GIS and
   insert it into the hole.
2. Lock the wall sleeve with a sheet metal
   screw or pop rivets in the overlap.
             EKO SRBG Gipsväggsstos Mont 2013

EKOVENT AB                                               We reserve the right to make changes   2021-03
Installation, operating and maintenance instructions EKO-SRB1

    Assembly instruction EKO-SRB1
    Supporting construction - wall or floor in fire resistance class EI 60.
    P-approval SC0848-13

                                       Suspension

                                                                                           Duct
                                           EKO-
     Ø A+55

                                           SRB1
                     Duct                                Duct

                                                                                         EKO- SRB1

                      Fire sealant *

                                                                                           Duct

6

                                                                    Fire sealant *

    Important! The smoke damper should always be installed with the blade
                           EKO-SRB1 Mont schakt 2014
    shaft horizontal..

    1. The duct system should be suspen-                                       – The damper blade shaft must always
       ded and insulated in accordance with                                    be installed horizontally.
       the fire resistance of the supporting
                                                                         3. Mount the thermal sensor with the sen-
       construction in which the hole is made
                                                                            sor probe in the air flow, ensuring that it
       (EI 60). Insulation of the ventilation
                                                                            does not obstruct the movement of the
       duct must be done in accordance with
                                                                            damper blade.
       “Installationsbrandskydd Ventilation
       – Rör” section 21.3.4 (ISBN: 978-91-                              4. The following minimum dimensions
       633-1723-1) corresponding to the fire                                must be observed when mounting
       resistance of the supporting construc-                               – Minimum distance between dampers:
       tion in which the hole is made (EI 60).                              200 mm.
                                                                            – Minimum distance to supporting con-
    2. Mount the damper in the duct.
                                                                            struction: 75 mm.
       – No gaps between the damper and
       the supporting construction.
                                                                         *     Fire sealing must be done using an
                                                                               approved method that complies with
                                                                               the relevant fire classification, e.g.
                                                                               EKO-KER, EKO-GIS and fire protection
                                                                               sealant.
    EKOVENT AB                                    We reserve the right to make changes                           2021-03
Operation and maintenance

Operation                                                     check which is located on the front of
Fire damper EKO-SRB1 is a P- and CE                           the monitoring unit (applies to EKO-KE).
marked damper for fire separation of hea-                     Powerless damper closes. Check that
ting, ventilation and air conditioning instal-                the damper is fully open during opera-
lations in buildings. EKO-SRB1 is always                      tion, closes and opens completely during
supplied with an electric safety actuator                     testing and closes completely in the event
complete with thermal sensor that discon-                     of a power failure. Otherwise follow the
nects the power to the actuator if the tem-                   instructions for monitoring systems EKO –
perature exceeds 72 °C. The facility must                     MKE/SKE, EKO-KE, EKO-TME/TSE, MME/
have a smoke detector which indicates an                      SME.
alarm and which closes the fire damper
and which must be connected to moni-                          Cleaning
toring systems EKO-MKE/SKE, EKO-KE,                           We advocate preventive maintenance of
EKO-TME/TSE, MME/SME or equivalent.                           the damper according to the facilities
Automatic function check takes place eve-                     needs. Clean the damper blade and dam-
ry 48 hours (or at more frequent intervals),                  per (inside) with a brush, vacuuming or
malfunction is shown in the display.                          wiping. NOTE! Water or other liquids must
                                                              not be used. Regular testing according to
Maintenance                                                                                                  7
                                                              the P-approval.
External and internal control
At least every three years, check the elec-
                                                              Note!
trical wiring for actuators, end position
                                                              After inspection, the fire damper must
contacts and smoke detectors as well as
                                                              be left in normal working position.
the damper cover so that no foreign de-
tails can prevent the damper blade from
                                                              Warning!
moving. Also check the attachment of
                                                              Never keep your hands inside the dam-
the actuator, damper blade and sealing
                                                              per when it closes. Risk of crushing
strip so that no damage has occurred.
                                                              injuries.
Also check that the corrosion protection
is intact.
                                                              Spare parts list
Function control                                              Actuator, see type designation of the ac-
Automatic: see above.                                         tuator.
Manuell: Manual: Manual function check
can be performed from the central unit
menu. During installation, manual function
check can also be performed on the re-
spective slave unit (applies to EKO-MKE/
SKE, EKO-TME/TSE, MME/SME). Manual
function check can be done by pressing
the test button for automatic function

EKOVENT AB                            We reserve the right to make changes                         2021-03
Installation, operating and maintenance instructions EKO-SRB1

    Declaration Of Performance

                     DECLARATION OF PERFORMAN
                                                                      CE
                     Fire Damper SRB1
                     Type and batch number accord
                                                      ing to product label.
                    Fire damper to be used in conjun
                                                     ction with fire separating eleme
                    compartmentation of at least 60                                   nts to maintain fire
                                                     min according to EN 15650.2010
                    EKOVENT AB, Mejselgatan 7, 23532
                                                         Vellinge, www.ekovent.se
                   Certificate:
                   SP Technical Research Institute
                                                   of Sweden, nr 0402, has perfor
                   the manufacturing plant and factor                              med type testing, initial inspection
                                                       y production control (FPC) under                                 of
                                                                                         system 1
                   EC Certificate of Conformity 0402-
                                                      CPR-SC0844-13
                   Size
                                                        Type
                   Ø 100 mm till Ø 630 mm                                                  Classification
8                                                       Horizontal duct
                                                                                          E 60 (ho i  o) S
                                                        Vertical duct
                                                                                          E 60 (Ve i  o) S
                                                                                       Classification according to EN 13501
                                                                                                                              -3
                   Nominal activation conditions/s
                                                     ensitivity: Pass
                   - Sensing element load bearing                                             ISO 10294-4
                                                    capacity
                   - Sensing element response tempe
                                                        rature
                  Response delay (reponse time):
                                                                  Pass                        EN 1366-2
                  -Closure time
                  Operational reliability:
                                                                 Pass                        EN 1366-2
                  -Cycling
                  Durability of response delay:
                                                                 Pass                        EN 1366-2
                 - Sensing element responset o
                 temperature and load bearing capac
                                                         ity
                 Durability of operational reliability:
                                                                 20 000 cycles -Pass         EN 15650:2010
                 -Open and closing cycle tests

                 The performance of SRB1 is in confo
                                                       rmity with the declared performance
                                                                                                 above.
                 This declaration of performance
                                                    is issued under the sole responsibili
                                                                                            ty of EKOVENT AB.
                 Signed for and on behalf of the
                                                   manufacturer by:

                 ______________________________
                                                       _________
             Vellinge 2017-09-20, Michael Bränd
                                                      ström R&D Manager

                                                    EKOVENT AB, Mejselgatan 7
                                             SE-235 32 Vellinge Sweden, +46
                                                                            40 42 16 00

    EKOVENT AB                                               We reserve the right to make changes                                  2021-03
Notes:

                                                              9

EKOVENT AB   We reserve the right to make changes   2021-03
REGIONAL OFFICE GÖTEBORG
                                 Boråsvägen 5, 435 31 Mölnlycke
HEAD OFFICE                      Tel 031-23 07 40
Mejselgatan 7, 235 32 Vellinge
Tel 040-42 16 00                 REGIONAL OFFICE STOCKHOLM
                                 Vallgatan 9, 170 67 Solna
www.ekovent.se info@ekovent.se   Tel 08-508 613 00
You can also read