Technical Guidelines As of: 1 January 2021 - Christmasworld
←
→
Page content transcription
If your browser does not render page correctly, please read the page content below
Technical Guidelines Contents → The items that have been marked contain new changes. Page Page Page 1. Preliminary remarks 4 Emergency escape route 4.9.1 Requests for approval 29 → 1.1 House Rules 5 signage 18 4.9.2 Restrictions applying to stand 1.2 Opening hours 6 Wall hydrants 18 superstructures, safety clearances 1.2.1 Set-up and dismantling periods 6 Fire extinguishers 18 and the heights of stand interiors 29 1.2.2 Opening hours during trade Fire alarm system 18 4.9.3 Live loads/design loads 29 fairs/exhibitions 6 Acoustic/visual alarm 18 4.9.4 Escape routes / stairways 30 Smoke removal 19 → 4.9.5 Building materials 30 2. Traffic on the exhibition grounds, Sprinkler systems 19 4.9.6 Top floors 30 rescue routes, → 4.4.1.1 Construction and decorative safety equipment 7 materials 19 5. Operational safety, technical 2.1. Traffic regulations, 4.4.1.2 Exhibiting motor vehicles safety provisions, technical parking permits 7 at stands 19 regulations and utilities 31 2.2 Rescue routes 7 4.4.1.3 Explosive materials 20 5.1 General regulations 31 2.2.1 Fire department manoeuvring 4.4.1.4 Pyrotechnics 20 5.1.1 Damage 31 areas, fire hydrants 7 4.4.1.5 Balloons 20 5.1.2 Coordinating work on the 2.2.2 Emergency exits, emergency 4.4.1.6 Flying objects exhibition grounds escape hatches, → 4.4.1.7 Fog machines, hazers, 5.2 Employment of tools and other exhibition hall aisles 7 Sparkulars and laser systems 20 equipment 31 2.3 Safety equipment 8 4.4.1.8 Ash containers, ashtrays 21 5.3 Electrical installations 31 → 2.4 Stand numbering 8 4.4.1.9 Containers for trash, recyclable 5.3.1 Electrical outlets 31 2.5 Guard services 8 materials and residual waste 21 5.3.2 Electrical installations on stands 31 2.6 Evacuation in an emergency 9 4.4.1.10 Spray guns, nitrocellulose 5.3.3 Installation and operating lacquers, cleaning agents, regulations 32 3. Technical data on, and solvents 21 5.3.4 Safety precautions 32 equipment of, 4.4.1.11 Work that poses a fire hazard 5.3.5 Emergency lighting 32 the exhibition halls and 4.4.1.12 Empty packaging / storage of 5.3.6 Equipotential bonding (stand outdoor exhibition areas 10 materials 21 earthing) for metal constructions 32 3.1 Hall data 10 4.4.1.13 Fire extinguishers 22 5.4 Water and drain installations 32 3.1.1 General lighting, types of electrical 4.4.1.14 Water features/pools 22 5.5 Compressed air/gas installation 33 supplies, supply voltages 10 4.4.2 Stand ceilings 22 5.5.1 Compressed air installations 33 3.1.2 Compressed air, electrical and 4.4.3 Glass and acrylic glass 22 5.5.2 Gas installations 33 water supplies 10 4.4.4 “Trapped rooms” / occupied rooms 22 5.6 Machinery, pressure vessels, 3.1.3 Communications facilities 10 4.5 Exits, escape routes, doors 22 exhaust systems 33 3.1.4 Sprinkler systems 10 4.5.1 Exits, escape routes 23 5.6.1 Noise generated by machinery 33 3.1.5 Heating, ventilation and → 4.5.2 Doors 23 5.6.2 Product safety 33 air-conditioning 10 → 4.6 Platforms, ladders, stairs, 5.6.2.1 Safety equipment 34 3.1.6 Outages 10 landings 23 5.6.2.2 Inspection procedures 34 3.1.7 Stand air-conditioning 11 4.7 Stand design 24 5.6.2.3 Prohibition of operation 34 3.2 Outdoor exhibition areas 11 4.7.1 Stand appearance 24 → 5.6.2.4 Additional protective measures 34 3.3 Designation of clear gate heights 11 4.7.2 Verification of rented areas 24 5.6.3 Pressure vessels 34 4.7.3 Interventions in the structures 5.6.3.1 Certificates of approval 34 4. Stand construction regulations 12 and equipment of buildings 24 5.6.3.2 Testing 35 4.1 Stand safety 12 → 4.7.4 Exhibition hall floors 24 5.6.3.3 Rental equipment 35 4.2 Stand construction permits, 4.7.5 Suspension points/installation of 5.6.3.4 Inspections by regulatory 35 project approval 12 trusses/fasteners 25 agencies 4.2.1 Inspection and approval of 4.7.5.1 Electric chain hoists 25 5.6.4 Exhaust gases and vapours 35 structures requiring a permits 12 → 4.7.5.2 Manual chain hoists 25 5.6.5 Exhaust systems 35 4.2.2 Vehicles and containers 13 4.7.5.3 Fasteners 26 5.7 Employment of compressed 4.2.3 Alterations to stand structures not 4.7.6 Stand bounding walls 26 gases, liquefied gases and in compliance with regulations 13 4.7.7 Advertising media/presentations 26 → combustible liquids 36 4.2.4. Limits of liability 13 4.7.8 Barrier-free construction 27 5.7.1 Compressed gas and liquefied 4.3 Construction heights 13 4.7.9 Foundations, pits 27 → gas systems 36 → 4.4 Fire protection and safety 4.8 Outdoor areas 27 5.7.1.1 Application for Approval of com- regulations 14 4.8.1 Stand construction permits/stand- pressed gas bottles 36 4.4.1 Fire protection regulations 14 structures requiring approval 28 5.7.1.2 Employment of liquefied gases 36 General remarks / Area data 17 4.8.2 Ground anchors/excavations 28 5.7.1.3 Installation and maintenance Closed ceilings 17 4.8.3 Weather-related loads 28 of liquefied gas systems 36 Stand construction materials, 4.8.3.1 Wind loads 28 5.7.2 Combustible liquids 36 stairs 18 4.8.4 Severe weather warnings 28 5.7.2.1 Operation requirements 36 Emergency escape routes 18 4.9 Two-storey structures 29 5.7.2.2 Filling systems with 2
Technical Guidelines Contents → The items that have been marked contain new changes. Page Page Page combustible liquids 36 systems, electromagnetic 6.2 Water, waste water, soil 5.7.2.3 Empty containers 36 compatibility and harmonics 39 protection 43 5.7.3 Combustible pastes and other 5.12 Cranes, forklifts, and empty 6.2.1 Oil/grease traps 43 fuels 36 packings 39 6.2.2 Stand cleaning/cleaning agents 43 5.8 Asbestos and other hazardous 5.13 Musical reproduction 40 6.3 Environmental pollution 43 materials 37 5.14 Beverage dispensing systems 40 6.3.1 Packaging materials 43 5.9 Movie and TV screenings, slide 5.15 Food inspections 40 6.3.2 Kitchen waste 43 shows and other presentations, 5.16 Vehicle and driving demonstra- 6.3.3 Manufacturing wastes 43 stages 37 tions 41 6.3.4 Stand components 43 5.10 Radiation protection 37 5.10.1 Radioactive materials 37 6. Environmental protection 42 7. General information 45 5.10.2 X-ray systems and sources of 6.1 Waste 42 7.1 Limitation of liability 45 broadcast interference 38 6.1.1 Waste disposal 42 5.10.3 Laser systems 38 6.1.2 Hazardous waste 43 5.10.4 LED 38 6.1.3 Waste brought onto the 5.11 High-frequency equipment, radio exhibition grounds 43 3
Technical Guidelines 1. Preliminary remarks Messe Frankfurt has issued guide- lines, it does not refer to a physical The trade fair companies lines for trade fairs and other structure in the sense of the Ger- - Deutsche Messe AG Hannover events in order that all exhibitors/ man Federal Building Code - Leipziger Messe GmbH event organisers will have optimum (BauGB). In legal terms, trade fair - Messe Berlin GmbH opportunities to present their stand constructions are considered - Messe Düsseldorf GmbH exhibits and attract attendees and to be “facilities” in the venue. - Messe Frankfurt Venue GmbH interested parties to visit their In the interest of all participants, - Messe München GmbH stands. Messe Frankfurt can prohibit the - Kölnmesse GmbH These guidelines are binding upon holding of an event and/or the - NürnbergMesse GmbH all exhibitors and event organisers. opening of an exhibition stand if - Landesmesse Stuttgart GmbH They also incorporate safety regu- defects previously found have not have compiled these Technical lations that are intended to provide been remedied by the start of the Guidelines with a uniform classifi- high degrees of safety in relation to fair. cation system. technical and stand equipment in Messe Frankfurt retains the right to the interest of protecting our ex- issue further safety regulations and Building codes are issued by the hibitors and visitors. The building stand construction standards at governments of the respective provisions, fire protection regulations any time. Messe Frankfurt also German states. and other safety regulations in- reserves the right to permit The respective event regulations volved have been coordinated with exceptions to these regulations in may therefore differ from exhibition the responsible agencies of the individual cases. site to exhibition site due to City of Frankfurt am Main. The documents required to order differing local building codes and Messe Frankfurt reserves the right services will be sent in due time differing construction conditions at to verify compliance with these before the event. the various exhibition sites. regulations. Furthermore, the These Technical Guidelines must Messe Frankfurt also reserves the applicable legal regulations, as be forwarded to all of the exhibi- right to modify these Technical amended from time to time, shall tor’s contracting partners. Guidelines and other regulations at be observed at all times. Further information on details of any time. Insofar as the term “stand con- preparation and staging of the The German version alone shall be struction” is used in its convention- event will be sent to exhibitors if binding. al sense in the Technical Guide- applicable. 4
Technical Guidelines 1.1 Site Regulations These Site Rules and Regulations observed. Vehicles are subject orders or the conducting of apply throughout the premises of to a 30 km/h speed limit. surveys, if such activities take Messe Frankfurt Venue GmbH E-scooters, e-boards and other place outside exhibition (hereinafter referred to as “Messe similar vehicles may not be stands. Frankfurt”), including all buildings, used in buildings or in outdoor 7. No commercial activities are the Rebstock multi-storey car event areas during events. permitted on the exhibition park, Kap Europa convention cen- 3. Messe Frankfurt shall be enti- grounds unless they are being tre and all outdoor areas in the tled to search the boots and conducted on behalf of Messe Rebstock area that are used by cargo areas of vehicles and Frankfurt or an organiser, ex- Messe Frankfurt (hereinafter re- bags or personal items of indi- hibitor, lessee, service provider ferred to as the “exhibition viduals at any time regardless or other contracting party that grounds”). of whether or not there is any has entered into an agreement Messe Frankfurt and the event or- suspicion of wrongdoing. with Messe Frankfurt.Messe ganiser each have the right to en- Should anyone refuse permis- Frankfurt reserves the right to force the Site Rules and Regula- sion, Messe Frankfurt reserves permit or prohibit the activities tions. Any additional agreements the right to expel them from of third parties acting on be- reached with exhibitors, service the exhibition grounds. half of contracting parties and partners etc. remain unaffected. 4. Messe Frankfurt has the right to specify the type, scope and 1. Entrance to the exhibition to issue restrictions on the ad- conditions of their activities. grounds on foot or in vehicles mission of visitors and to pro- 8. Over-the-counter sales, cash is only permitted with proper hibit the transport of animals sales, or the acceptance and and valid authorisation (em- or items onto the exhibition removal of exhibited goods ployee IDs, service partner IDs, grounds; it may either issue during trade fairs and exhibi- event-specific admission tick- general provisions or make tions is prohibited. If goods are ets, set-up and dismantling such restrictions dependent on given away free as samples, passes) at predefined times the satisfaction of specific re- the exhibitor must provide the and in the predefined areas of quirements in individual cases. third party with a correspond- the exhibition buildings and Children and young people un- ing declaration of transfer (re- grounds. Messe Frankfurt re- der the age of 14 may only en- ceipt). Third parties must de- serves the right to conduct ter the exhibition grounds in mand a receipt from the spot checks of individuals to the company of an official exhibitor and must produce ensure that they are authorised guardian or suitable chaperone this on request.Should any to be on the exhibition 5. Messe Frankfurt accepts no li- such third party be found with- grounds, regardless of wheth- ability whatsoever for any per- out a receipt, Messe Frankfurt er they are suspected of sonal injury, property damage reserves the right to impound wrongdoing. or financial loss that might oc- the goods without compensa- 2. The provisions of the German cur at the exhibition grounds tion and expel the third party Road Traffic Regulations 6. Unless Messe Frankfurt has from the exhibition grounds. (StVO) are applicable for every- given express permission, it 9. Devices that can be used to one on the exhibition grounds. does not allow advertising of produce photos or film are pro- All signs regulating vehicular any kind, neither does it permit hibited throughout the exhibi- and pedestrian traffic on the the offer of goods or services tion grounds. Filming, taking exhibition grounds must be of any kind, the acceptance of pictures and making sketches 5
Technical Guidelines 1.1 House Rules of exhibited goods on the exhi- reasons. rary or permanent ban on their bition grounds and in the exhi- 11. There is a general smoking ban return, as well as to confiscate bition halls is only permissible in all buildings and enclosed their access documents with- in exceptional cases with the rooms within the exhibition out compensation, and to have written consent of Messe grounds. any vehicles removed from the Frankfurt. If there is reasonable 12. Instructions given by Messe premises at the expense an- suspicion, Messe Frankfurt is Frankfurt security staff and drisk of the owner or operator. entitled to confiscate any stewards must be followed at 14 A limited road and walkway sketches, photographs or other all times. clearance service is provided film materials that have been 13. In the event that the House during the winter months. This made and have these de- Rules or other requirements applies for both the restricted stroyed without providing and regulations are violated, and the publicly accessible ar- compensation. This also ap- access documentation is mis- eas of the Messe Frankfurt ex- plies if other film or photo- used or forged, or there is oth- hibition grounds graphic material will be de- er disruptive behaviour, Messe stroyed as a result. Frankfurt reserves the right to As at: November 2020 10. It should be noted that the ex- expel those responsible from hibition grounds are under vid- the exhibition buildings and eo surveillance for security grounds and to issue a tempo- 1.2 Opening hours 1.2.1 Set-up and dismantling tures and structures built into of dismantling periods. periods stands, shall have been concluded In the interest of general safety, all In general, stand building and de- and the exhibition hall vacated no exhibition halls and the exhibition liveries of exhibited goods may later than the second calendar day grounds shall commence five (5) calendar days following the close of the event in- remain closed outside official prior to the opening of the event volved. The exhibitor and any stand set-up and dismantling periods and involved. construction companies they work event opening hours. During the general set-up and with should report to the service dismantling periods, work in the office responsible for the hall both 1.2.2 Opening hours during exhibition halls and on the outdoor at the start of stand set-up and at trade fairs/exhibitions exhibition areas may proceed the end of dismantling. Stand are- Exhibition halls shall be opened around the clock, that is, 24 hours as shall be swept and returned in a one hour prior to the official opening per day (normally no work may be clean condition. In special cases, of the trade fair and shall be closed performed after 3 p.m. on the final Messe Frankfurt Venue GmbH’s one hour after it closes, on every days of set-up periods, however), Technical Project Management day the event involved is officially unless other hours and a schedule may grant extensions of set-up open. of working hours have been and/or dismantling periods. Exhibi- Exhibitors who, in special cases, announced for a particular event. tion halls are neither heated nor have valid grounds for working on In general, dismantling of stand air-conditioned prior to the official their stands outside said opening equipment and furnishings, includ- commencement of set-up periods hours shall require special written ing exhibitors’ own stand struc- or following the official termination permits issued by Messe Frankfurt. 6
Technical Guidelines 2. Traffic on the exhibition grounds, rescue routes, safety equipment 2.1 Traffic regulations, parking permits All rules directing and regulating speed. Engines must be turned off Driving any type of vehicle on the traffic, such as those described in during loading/unloading. Before exhibition grounds requires a per- the Traffic regulations, and all in- entering/exiting exhibition halls, mit from Messe Frankfurt, is at structions given by the personnel drivers must come to a full stop drivers’ own risk, and is prohibited deployed by Messe Frankfurt for and ensure that gates offer suffi- at all times during events. this purpose, shall be observed at cient overhead clearance. Parking There is a limited number of car all times. vehicles in the exhibition halls is parking spaces available for exhibi- The exhibition grounds are the pri- prohibited. Caravans/campers may tors on the exhibition grounds. In vate property of Messe Frankfurt. not be used on the exhibition accordance with the number of The provisions of the StVO (German grounds. spaces available, parking permits road traffic regulations) apply Illegally parked vehicles, trailers, can only be ordered for the entire throughout the exhibition grounds containers, and goods of any kind duration of the event using the cor- and on/in Messe Frankfurt’s parking may be removed by authorised responding form (please also see facilities. The speed limit on the towing companies working under the Transport Guidelines). exhibition grounds is 30 km/h. contract to Messe Frankfurt at their If called for by traffic conditions, owners’ or operators’ expense and vehicles must not exceed walking risk. 2.2 Rescue routes 2.2.1 Fire department possible to easily open the doors structing stands or exhibits deliv- manoeuvring areas, fire hydrants along escape and rescue routes ered for immediate installation at The necessary fire-department entry from the inside to their fully open the stand area may be deposited in routes and manoeuvring areas des- position. Escape and rescue the escape and rescue routes for a ignated by “no-parking” signs routes, exit doors, emergency exits short period of time during the set- must be kept clear at all times. and their identifying signs or mark- up and dismantling phases as long Vehicles or objects parked/deposited ings must not be obstructed, ob- as the aisle widths required for in rescue routes or on safety areas scured, have anything built over safety reasons are maintained and shall be removed at their owners’ them, be blocked, have anything logistical concerns are sufficiently expense and risk. hung on them or otherwise be ren- taken into consideration. This will Fire hydrants in the exhibition halls dered unrecognisable. Escape and be considered to be fulfilled if a and on outdoor exhibition areas rescue routes in exhibition halls strip of no more than 0.9 m in shall not be obstructed or rendered shall not be constricted by objects width between the stand border unrecognisable or inaccessible. deposited therein or extending into and the hall aisle is used to deposit them at any time. In the event that items. Regardless of the width of 2.2.2 Emergency exits, these rules are not complied with, the hall aisle and the items depos- emergency escape hatches, Messe Frankfurt shall be entitled to ited there, it is mandatory to main- exhibition hall aisles remedy the situation at the ex- tain an unblocked passageway of Escape and rescue routes shall be pense and risk of the responsible no less than 1.2 m in width. Areas kept clear at all times. It must be party. Materials required for con- in front of emergency exits and ar- 7
Technical Guidelines 2.2 Rescue routes eas where hall aisles intersect are bly or to set up machines (e.g. clearing of all hall aisles for logisti- the exception: their entire width woodworking equipment, work- cal reasons. must be kept clear at all times. Hall benches etc.). Messe Frankfurt aisles may not be used for assem- may (also) request the immediate 2.3. Safety equipment Sprinkler systems, fire alarms, fire hall doors and other items of safety shall remain visible and accessible extinguishers, smoke detectors, equipment, their signs or markings, at all times, and shall not be obst- mechanisms for closing exhibition and green emergency exit signs ructed or enclosed. 2.4. Stand numbering and aisle designations Stand numbering and corresponding construction. We recommend that ignations, for safety reasons they aisle designations are obligatory. All organisers adopt the existing aisle must first present an alternative aisle stands will be marked with stand designations with letters that are signage concept to Technical Project numbers by the organiser if techni- normally used in Frankfurt. If the or- Management for approval. cally possible with the given stand ganiser wishes to use different des- 2.5. Guard services Messe Frankfurt and Messe Frank- Exhibitors are expressly informed be arranged by the exhibitor where furt’s external service partners that exhibited materials and other necessary. monitor the exhibition halls and objects brought by the exhibitors outside areas during the set-up are subject to greater risk during As a general rule, stand guards and dismantling phases, as well as set-up and dismantling periods. may only be posted between 6:00 while events are underway. How- Valuable and easily moveable ob- p.m. and 8:00 a.m. by Messe ever, Messe Frankfurt accepts no jects should always be locked Frankfurt or its contractual service responsibility for property and ob- away at night. partner(s). Exhibitors may order jects brought or delivered by exhib- stand guards no later than six itors and third parties acting under Security for the stand and the ob- weeks before the start of the event Messe Frankfurt’s instructions. jects brought by the exhibitor must with the corresponding order form 8
Technical Guidelines 2.5. Guard services (please refer to the service folder or prior to, during and after events the shortest route passing by the go to Shop for Exhibitor Services shall also observe the following hall inspector’s office. In the event online). Ordering stand guards in- regulations: Guards shall sign in at that they fail to observe these reg- volves submitting a fully complet- the hall inspector’s office prior to ulations, Messe Frankfurt shall as- ed, preprinted order form for the going on duty. Their presence on sume that the presence of that per- event involved. Oral or telephone site shall be confirmed by entering son on the stand or in the orders for stand guarding must be their name, the name of the exhibi- exhibition hall is unauthorised and confirmed in writing by applicants. tor, the stand number, the number reserves the right to institute spe- All orders for stand guarding must of their personal identification card cial measures, to expel that person be signed by applicants. Messe or passport number, and the date from the exhibition grounds, and/ Frankfurt service personnel is not and time of their arrival on a list or to file other claims or claim authorised to assume responsibility provided for that purpose and damages. Bringing guard dogs for monitoring for third-party prop- maintained by the hall inspector’s onto the exhibition grounds re- erty. Exhibitors’ own stand security office. Upon concluding their peri- quires a permit issued by Messe staff who are to remain on duty in od of duty, and before leaving the Frankfurt that may be revoked by exhibition halls between 6 p.m. exhibition hall, stand security staff same at any time. Dogs shall be and 8 a.m. require special permits shall sign out at the hall inspector’s kept on a leash at all times. Weap- for which a fee is charged. Exhibi- office and note the termination of ons may not be brought onto the tors have no legal rights to demand their period of duty on the afore- exhibition grounds, even for guard- issuance of such permits. mentioned list. Stand security staff ing purposes. shall remain on that stand for Exhibitors’ own stand security staff which they have a guarding order, who are present in exhibition halls and shall enter and leave stands by 2.6. Evacuation in an emergency For safety or security reasons, Messe Frankfurt may order the clo- sure and evacuation of rooms, buildings or outdoor areas. 9
Technical Guidelines 3. Technical data on, and equipment of, the exhibition halls and outdoor exhibition areas 3.1 Hall data Since the technical data on the var- installation channels and connection mentioned rules and regulations ious exhibition halls differ from hall points in hall floors. are also applicable for WiFi trans- to hall, they have been listed in a On exhibition hall floors having mitters in exhibits. The operation of separate document (cf. the docu- supporting columns, connection WiFi networks that cause interfer- ment entitled “Technical Data on points are also available at terminal ence or disruption is prohibited. the Exhibition Halls of Messe boxes mounted on these supporting Messe Frankfurt reserves the right Frankfurt”). columns. to shut down these networks. Guidelines for the operation of ex- Forms for registering your own ac- 3.1.1 General lighting, types hibitors’ own WiFi networks at cess point are available at www. of electrical supplies, supply Messe Frankfurt: Exhibitors’ own messefrankfurt.com. Exhibitors’ voltages WiFi transmitters may only trans- own WiFi transmitters must be The general lighting in the exhibition mit in the 2.4 GHz band in accord- registered in good time before a halls differs from hall to hall, and ance with currently applicable trade fair in order to ensure that ranges from around 300 lux to standards (802.11 b/g/n); transmis- these rules are complied with by all around 400 lux, measured one me- sion in the 5 GHz band is prohibit- exhibitors. ter above floor level. The electrical ed! The 5 GHz band is reserved ex- supplies and supply voltages avail- clusively for Messe Frankfurt in 3.1.4 Sprinkler systems able on the exhibition grounds are order to allow for the provision of Exhibition halls are equipped with as follows: exhibitor-specific solutions. As a sprinkler systems. Network type: TN-C-S result, WiFi transmitters may only Exhibits and decorations must be Supply voltage: 230 V / 400 V transmit on channels 1, 6 or 11, and situated at least 1.0 m from sprinkler Tolerances as per DIN EN 50160 cannot be configured for automatic heads. Distances between lamps/ channel search. Channel bonding spotlights and sprinkler heads 3.1.2 Compressed air, electrical is not permitted, and the maximum should be chosen so as to preclude and water supplies channel bandwidth is 20 MHz. The false triggerings of fire extinguishing The compressed air, electrical and maximum transmission power of devices through the heat generated water supplies on stands located in the exhibitor’s transmitter may not by the lighting. exhibition halls are routed through exceed -80 dBm at the edge of the existing installation channels to stand. The SSID, i.e. your access 3.1.5 Heating, ventilation and connection points in hall floors. point ID, must begin with your air-conditioning On exhibition hall floors having stand number (e.g. H4.0 B42). All All halls are equipped with heating, supporting columns, electrical sup- of the aforementioned settings can ventilation and air-conditioning plies are also available at terminal be made using the access point systems. These systems will be boxes mounted on these supporting configuration menu. Any transmit- operational as required throughout columns. ters other than WiFi transmitters events. are prohibited, as they can cause 3.1.3 Communications facilities massive disruption to signals. In 3.1.6 Outages Stands located in exhibition halls the event that exhibits require dif- Messe Frankfurt should be notified are supplied with telephone, fax, ferent transmitters, please contact immediately in the event of any data and antenna lines via existing us in advance. Naturally the afore- outages of utilities, such as elec- 10
Technical Guidelines 3.1 Hall data tricity, water, compressed air, heating, 3.1.7 Stand air-conditioning vidual offer. It is not permitted to ventilation or telecommunications It is possible to individually air-con- use drinking water to flow-cool systems, etc. Messe Frankfurt as- dition stand areas. Messe Frank- stands. sumes no liability for any losses or furt’s Exhibitor Service would be damage due to such outages. happy to provide you with an indi- 3.2. Outdoor areas Outdoor areas are paved with as- the onset of darkness during event Please also be sure to note Item phalt or stones. The grounds have opening hours. Necessary utilities 4.8 “Outdoor areas” when con- general road and walkway lighting connections are spaced at irregular ducting your planning. systems that will be activated at intervals. 3.3. Designation of clear gate heights Gates having clear heights less than 4.00 m are designated by signs. 11
Technical Guidelines 4. Stand construction regulations 4.1 Stand safety Exhibition stands – including fur- decorative elements) which might ance is to be compiled in advance nishings, exhibits and advertising tip over must be designed to with- and presented to Messe Frankfurt media – must be structurally stable stand the following equivalent dis- on request (see Item 4.2.1). Devia- to ensure that there is no threat to tributed lateral loads qh: tions are possible in justified ex- public safety and order, and in qh1 = 0.125 kN/m² up to 4 m in ceptional cases and require de- particular that there is no danger height measured from the top of tailed documentation. to life or health. The exhibitor is the floor Bracing stands against neighbour- responsible for the structural safety qh2 = 0.063 kN/m² for all areas ing stands or existing building of their stands, and may be re- more than 4 m high measured structures is prohibited. quired to submit proof of same. from the top of the floor In justified cases, Messe Frankfurt Standing constructional elements The reference area is the respec- reserves the right to engage a or special constructions (e.g. free- tive surface area. structural engineer to conduct a standing walls, high exhibits, high Verifiable/verified proof of compli- chargeable verification of stand stability on site. 4.2 Stand construction permits, project permission Permits are not required for the be invoiced to the exhibitor / tal form (PDF) for approval by no lat- following: stand constructor. er than six weeks before the start of For single-storey stands set-up to veranstaltungstechnik@ - that are not considered to be Special constructions include: messefrankfurt.com. special constructions –S tand structures and exhibits After the stand plans have been in- - whose stand area is less than that are more than 4 metres in spected, one copy will be stamped 100 m² height as having received permission and - whose height does not exceed – Closed ceilings returned to the exhibitor / stand con- 4.00 m –P latforms and stages higher structor if accepted. Stand construc- it is not necessary to submit plan- than 0.20 m tion may not commence until the ning documents. – Glass constructions plans have been stamped as having – Moving components received permission. In order to re- Permits are required for the – Floor/ceiling connections ceive permission for the following: following: – Special constructions Exhibition stands larger than 100 4.2.1 Inspection and permission – Two-storey structures m² in area, stands located in out- for structures requiring a permit – Stands in outdoor areas door areas, temporary structures, Dimensioned stand plans drawn to a – Temporary structures mobile stands, two-storey stands, suitable scale (e.g. 1:100), labelled in – Cinemas and auditoriums special structures and special con- English or German, accompanied by – Stages and platforms structions require consent and in- floor plans (as well as sectioned the following documentation must spection, and are subject to addi- views and perspective views if ap- be submitted in digital form (PDF) tional cost. Any costs incurred will propriate), shall be submitted in digi- in German or English by no later 12
Technical Guidelines 4.2 Stand construction permits, project permission than six weeks before the start of their services. The firm of engi- concluded by the appointed time, set-up: neering consultants will contact Messe Frankfurt shall be entitled a) Structural calculations comply- the stand construction manager at to make the required alterations at ing with German building stand- a specified time / after consulta- exhibitors’ expense. ards that are checkable or have tion to provide assistance and ex- been checked by a second inde- amine structural characteristics, 4.2.4. Limits of liability pendent structural engineer and to inspect the structure for a Messe Frankfurt shall not be held b) A building description specify- fee. liable for theft or deterioration of, ing the materials used (including Due to the additional work en- or damage to, drawings, models, certificates in German or English tailed, the absence of structural or other items of documentation where applicable) calculations results in additional submitted, regardless of any legal c) Stand construction drawings to costs for the exhibitor / stand con- grounds that might apply. a suitable scale, e.g. 1:100 (floor structor. In the event that the exhibitor or plans, perspective views, sec- their subcontractors fails to com- tioned views) as well as a ceiling 4.2.2 Vehicles and containers ply with these stand construction plan with dimensions of the Vehicles and containers that are to regulations, the exhibitor shall be closed ceiling(s) be employed as exhibition stands liable for any damage arising as a d) Escape route plan including in exhibition halls or outdoor areas consequence of the violation of lengths and widths of emergency require permission. these stand construction regula- escape route(s) tions. Furthermore, the exhibitor e) Submission of a type certifica- 4.2.3 Alterations to stand shall indemnify Messe Frankfurt tion / certification book renders structures not in compliance from any third-party claims assert- item a) superfluous with regulations ed with respect to the violation of In the event that structural calcu- Stand structures that have not the aforementioned stand con- lations examined by a second, in- been granted permission or that struction regulations. dependent structural engineer are fail to comply with these Technical not submitted, Messe Frankfurt Guidelines or the state of the art will commission a firm of engi- must be altered or removed from neering consultants to check the the premises. plans and separately invoice the In the event that said alterations exhibitor / stand constructor for or removal shall not have been 4.3 Construction heights The maximum construction heights neighbouring stand. There may be eas must be at least 2.30 m. The rear for stands, rigging and advertising special restrictions in particular halls. sides of stands adjacent to neigh- can be found at www.messefrank- All measurements must be checked bouring stands must be kept smooth furt.com. Advertising media, logos, on site and Messe Frankfurt as- and be white in colour from a height etc., must be positioned at least 1 sumes no liability for figures being of 2.50 m. Deviations are only possi- metre from the border with the correct. The clear height of inside ar- ble with the agreement of neigh- bouring stands. 13
Technical Guidelines 4.4 Fire protection and safety regulations 4.4.1 Fire protection regulations systems be impaired by stand con- consult the following Tables 1 and The use of open fires and flames is structions (e.g. closed ceilings), ex- 2 for the necessary measures. prohibited. Exhibition halls are hibitors must undertake additional Closed ceilings are not permitted in equipped with fire alarms and fire measures in agreement with Mes- foyers. extinguishing systems. Should the se Frankfurt Venue GmbH’s Techni- operation of these fire protection cal Project Management. Please 14
Technical Guidelines 4.4 Fire protection and safety regulations Table 1: Fire protection programme for one-storey exhibition stands with closed GF ceilings and two-storey exhibition stands with open TF ceilings (GF = ground floor, TF = top floor) Ceiling area 0 - 30 m² 31 - 100 m² 101 - 200 m² 201 - 400 m² 401 - 1000 m² above the ground floor Fire protection measures Stand construction- Minimum B1, Minimum B1, Minimum B1, Minimum B1, Minimum B1, materials incl. ceilings flame retardant flame retardant flame retardant flame retardant flame retardant Stairs Minimum B1, Minimum B1, Minimum B1, Minimum B1, Minimum B1, flame retardant flame retardant flame retardant flame retardant flame retardant Emergency escape GF: GF: GF: GF: GF: route length max 20 m to aisle max 20 m to aisle max 20 m to aisle max 20 m to aisle max 20 m to aisle TF: TF: TF: TF: TF: max 20 m to aisle max 20 m to aisle max 20 m to aisle max 20 m to aisle max 20 m to aisle Exits from exhibition GF: one; 0.9 m GF: one; 0.9 m GF: Two, opposite one an- GF: Two, opposite one an- GF: Two, opposite one an- stands or from rooms TF: one flight of TF: one flight of other, other, other, located on stands stairs; 0.9 m stairs; 0.9 m < 200 m2: 0.9 m < 200 m2: 0.9 m < 200 m2: 0.9 m (minimum width) > 200 pers: min. 1.2 m + 0.6 m > 200 pers: min. 1.2 m + 0.6 m > 200 pers: min. 1.2 m + 0.6 m for each additional 100 pers. for each additional 100 pers. for each additional 100 pers. TF: Two flights of stairs oppo- TF: Two flights of stairs oppo- TF: Two flights of stairs oppo- site one another, each < 200 site one another, each < 200 site one another, each < 200 m2: 0.9 m m2: 0.9 m m2: 0.9 m > 200 pers: min 1.2 m + 0.6 m > 200 pers: min 1.2 m + 0.6 m > 200 pers: min 1.2 m + 0.6 m for each additional 100 pers. for each additional 100 pers. for each additional 100 pers. Emergency escape Yes Yes Yes Yes Yes route signage Escape sign lights Emergency lighting Emergency lighting Emergency lighting Fire extinguishers GF: Yes GF: Yes GF: Yes GF: Yes GF: Yes TF: Yes 1+1 p. stairs TF: Yes 1+1 p. stairs TF: Yes 1 + 1 per stairs TF: Yes 1 + 1 per stairs TF: Yes 1 + 1 per stairs Fire alarm system GF: No GF: Yes GF: Yes GF: Yes GF: Yes TF: No TF: No TF: No TF: No TF: No Acoustic/visual alarm GF: No GF: No GF: No GF: No GF: Yes TF: No TF: Yes TF: Yes TF: Yes TF: Yes Wall hydrant ”S“ GF: No GF: No GF: Yes, one GF: Yes, two GF: Yes, three at stand TF: No TF: No TF: No TF: No OG: Yes, three Smoke removal GF: No GF: No GF: No GF: Yes GF: Yes TF: No TF: No TF: No TF: No TF: No Sprinkling GF: No GF: No GF: No GF: No GF: Yes TF: No TF: No TF: No TF: No TF: No Please note: If there is no top storey used by people, the corresponding requirements for the top storey do not apply. 15
Technical Guidelines 4.4 Fire protection and safety regulations Table 2: Fire protection programme for two-storey exhibition stands with closed GF ceilings and closed TF ceilings (GF = ground floor, TF = top floor) Ceiling area 0 - 30 m² 31 - 100 m² 101 - 200 m² 201 - 400 m² 401 - 1000 m² above the top floor Fire protection measures Stand construction- Minimum B1, Minimum B1, Minimum B1, Minimum B1, Minimum B1, materials incl. ceilings flame retardant flame retardant flame retardant flame retardant flame retardant Stairs Minimum B1, Minimum B1, Minimum B1, Minimum B1, Minimum B1, flame retardant flame retardant flame retardant flame retardant flame retardant Emergency escape GF: GF: GF: GF: GF: route length max 20 m to aisle max 20 m to aisle max 20 m to aisle max 20 m to aisle max 20 m to aisle TF: TF: TF: TF: TF: max 20 m to aisle max 20 m to aisle max 20 m to aisle max 20 m to aisle max 20 m to aisle Exits from exhibition GF: one; 0.9 m GF: one; 0.9 m GF: Two, opposite one an- GF: Two, opposite one an- GF: Two, opposite one an- stands or from rooms TF: one flight of TF: one flight of other, other, other, located on stands stairs; 0.9 m stairs; 0.9 m < 200 m2: 0.9 m < 200 m2: 0.9 m < 200 m2: 0.9 m (minimum width) > 200 pers: min. 1.2 m + 0.6 m > 200 pers: min. 1.2 m + 0.6 m > 200 pers: min. 1.2 m + 0.6 m for each additional 100 pers. for each additional 100 pers. for each additional 100 pers. TF: Two flights of stairs oppo- TF: Two flights of stairs oppo- TF: Two flights of stairs oppo- site one another, each < 200 site one another, each < 200 site one another, each < 200 m2: 0.9 m m2: 0.9 m m2: 0.9 m > 200 pers: min 1.2 m + 0.6 m > 200 pers: min 1.2 m + 0.6 m > 200 pers: min 1.2 m + 0.6 m for each additional 100 pers. for each additional 100 pers. for each additional 100 pers. Emergency escape Yes Yes Yes Yes Yes route signage Escape sign lights Emergency lighting Emergency lighting Emergency lighting Fire extinguishers GF: Yes GF: Yes GF: Yes GF: Yes GF: Yes TF: Yes 1+1 p. stairs TF: Yes 1+1 p. stairs TF: Yes 1 + 1 per stairs TF: Yes 1 + 1 per stairs TF: Yes 1 + 1 per stairs Fire alarm system GF: No GF: Yes GF: Yes GF: Yes GF: Yes TF: No TF: Yes TF: Yes TF: Yes TF: Yes Acoustic/visual alarm GF: No GF: No GF: No GF: No GF: Yes TF: No TF: Yes TF: Yes TF: Yes TF: Yes Wall hydrant ”S“ GF: No GF: No GF: Yes, one GF: Yes, two GF: Yes, three at stand TF: No TF: No TF: Yes, one TF: Yes, two TF: Yes, three Smoke removal GF: No GF: No GF: No GF: Yes GF: Yes TF: No TF: No TF: No TF: Yes TF: Yes Sprinkling GF: No TF: No GF: No GF: No GF: No GF: Yes TF: No TF: No TF: No TF: Yes 16
Technical Guidelines 4.4 Fire protection and safety regulations Explanations for Table 1 and 2 - Up to 30 m² of ceiling area of next to one another without a each stand may be covered sprinkler system. A minimum General remarks / Area data without any additional meas- distance of 5 m (straight line) Two-storey structures and the in- ures being necessary as long as must be maintained between stallation of closed ceilings are only this does not exceed 50% of the ceiling areas. possible with the consent of Messe the stand area, because this Should a larger ceiling area result Frankfurt Venue GmbH’s Technical does not reduce the effective- from not observing the minimum Project Management. ness of the sprinkler system in distance, including across multiple Area data in m² refers in each case the exhibition hall. It is also stands, the expenses incurred for to the closed ceiling area per sto- possible to have multiple ceil- compensatory measures according rey; a rating in sections may be ing areas of up to 30 m² within to Table 1 or 2 will be billed to necessary. For stands with closed a single exhibition stand, as those who caused them, including ceilings measuring 1,000 m² or long as a minimum distance of expenses for the affected neigh- over, an individual fire protection 3.00 m is maintained between bouring stand. concept based on the Messe each ceiling area. In order to Frankfurt Technical Guidelines ensure that multiple ceiling ar- The top storey must always be left must be prepared and submitted to eas taken together do not ex- open to ensure that the effective- Messe Frankfurt for its consent. ceed the maximum size of 30 ness of sprinkler systems is not im- m², a distance of at least 1.50 m paired. If the ceilings of top storeys Closed ceilings from the edge of the stand is to are closed, additional requirements The effectiveness of the sprinkler be maintained at all times. set out in Table 2 shall apply. system (in the exhibition hall) must - Closed ceiling areas up to 100 m² Please also see Item 4.4.2. Closed not be reduced by covered or multi- in size require an automatic fire ceilings are not permitted in foyers. storey exhibition stands. alarm system. Ceilings are considered to be open: - Closed ceiling areas that are - if no more than 50% per each larger than 100 m² in size also m² of the roofed area is covered require the installation of wall - if sprinkler-compatible fabrics hydrants for immediate fire- with a minimum mesh width of fighting measures 2 mm x 4 mm or 3 mm x 3 mm - Closed ceiling areas that are are used (no Smoke Out). Tar- 401 m² or larger require a sprin- paulins are to be hung horizon- kler system for the area be- tally and only in one layer. neath the closed ceiling. It is Fire protection measures: not permissible to place multiple ceiling areas of up to 400 m² 17
Technical Guidelines 4.4 Fire protection and safety regulations Further general explanations: emergency lighting and safety sig- within a stand. For stands without nage must be provided for exits closed ceilings measuring up to 30 Stand construction materials, and emergency escape routes (cf. m², a can of fire extinguishing stairs Section 15 H-VStättR). For stands spray with an extinguishing capaci- All stand construction and decora- with an enclosed area of 30-100 m², ty of at least 8 A (2 extinguishing tive materials must at least be clas- illuminated emergency exit signs units pursuant to the extinguishing sified as flame-retardant class B1 in are sufficient. agent table ASR A2.2) can serve as accordance with DIN 4102 and/or an alternative to a fire extinguisher. class C s2 d2 in accordance with Wall hydrants The fire extinguishers must have EN 13501-1. Stricter requirements Additional wall hydrants at exhi- an extinguishing capacity of at apply in particular for materials bition stands are to be provided least 27 A for fire classification A that are used for ceiling structures primarily for self-help, but also or 144 B for fire classification B and or overhead: they must not only be for use by instructed persons. should not weigh more than 12 kg. flame-retardant, but also must not Wall hydrants for self-help com- Suitable fire extinguishers must be drip while burning. This corre- ply with DIN 14461 Part 1 Type provided if stands have kitchens. sponds to class C s2 d0 in accord- “S” and are to be marked with an Exhibitors must label fire extin- ance with EN 13501-1. For floor “S” accordingly, in addition to guishers with their stand number coverings, class C fl s1 is required. safety marking. The capacity of and exhibitor name to ensure that For safety reasons, special require- the wall hydrants for self-help is they can be properly assigned to ments may be imposed for load- 24 l/min with simultaneous oper- the correct stand areas. bearing structural components in ation of two wall hydrants with individual cases. All stairways must non-distorting hoses of 19 mm in Fire alarm system comply with DIN 18065. diameter and a jet pipe with The automatic fire alarm systems mouthpiece of 4 mm in diameter. on exhibition stands with closed Emergency escape routes Wall hydrants at exhibition stands ceilings are designed to detect a The routing and dimensioning of are to be installed in the direct fire at an early stage and to warn emergency escape routes are gov- vicinity of stand entrances or, re- both stand visitors, especially erned by the requirements of spectively, at the top or bottom of those on the top floor of a stand, H-VStättR (Hessian guidelines on stairs. Wall hydrants are to be lo- and the fire service. In this way, the public meeting places).Distances cated such that every covered conditions for escape are signifi- within exhibition stands shall be part of an exhibition stand can be cantly improved and fire service measured according to walking reached with at least one wall hy- intervention times minimised. As distance. drant. Stand personnel will be in- well as warning facilities, systems structed in use of the wall hy- for smoke removal can be activated Emergency escape route signage drants by Messe Frankfurt. by an automatic fire alarm system. Escape routes, emergency exits, emergency escape hatches and Fire extinguishers Acoustic/visual alarm doors along emergency escape Every level of an exhibition stand An acoustic/visual warning system routes must be identified in ac- must be equipped with at least one must be installed on the top floor cordance with the provisions of fire extinguisher appropriate to the of two-storey exhibition stands if ASR A1.3 “Health and Safety existing fire risk. One additional fire there is no visual contact with the Signage”. In the event that stands extinguisher must be provided for exhibition hall. In this way, people are enclosed or darkened and the each further 200 m². An additional on the top storey can be warned at general emergency lighting for the fire extinguisher must be provided an early stage if there is a fire exhibition hall is not sufficient, at the top of each flight of stairs alarm on the ground floor. The 18
Technical Guidelines 4.4 Fire protection and safety regulations warning system is activated/trig- elements either. A mechanical cordance with DIN 4102 and/or gered by the automatic fire alarm smoke removal system is triggered/ class C s2 d2 in accordance with system on the ground floor of a activated via the automatic fire EN 13501-1. Stricter requirements two-storey stand. For exhibition alarm system. apply in particular for materials that stands with closed ceilings larger are used for ceiling structures or than 400 m2, a warning system of Sprinkler systems overhead: they must not only be this type must be provided on the Closed ceiling areas that are larger flame-retardant, but also must not ground floor too. than 400 m² require a sprinkler sys- drip while burning. This corre- Soundproof booths must addition- tem for the area beneath the closed sponds to class C s2 d0 in accord- ally – irrespective of their size – ceiling. ance with EN 13501-1. For floor cov- either allow visual contact to the It is not permissible to place multiple erings, class C fl s1 is required. Test outside or feature an acoustic/visual ceiling areas of up to 400 m² next to certificates stating the classifica- signal system combined with an one another without a sprinkler sys- tions of the building materials em- alarm button or an emergency tem. A minimum distance of 5 m ployed shall be kept available at the switch outside the booth. (straight line) must be maintained stand at all times. between the ceiling areas. All materials brought on site must Smoke removal Should a larger ceiling area result be kept at a sufficient distance from Smoke removal from exhibition from not observing the minimum ignition sources, spotlights and heat stands is by natural means or distance, including across multiple sources to ensure that they cannot mechanically into the exhibition stands, the expenses incurred for be ignited. Decorations must be hall and from there by natural compensatory measures according mounted directly on walls, ceilings means or mechanically to the out- to Table 1 or 2 will be billed to those or furnishings. Decorations sus- side. No smoke extraction system is who caused them, including expens- pended (freely) within the room are required for exhibition stands with a es for the affected neighbouring only permissible if they are at least ceiling area of less than 200 m2. stand. 2.5 metres above the floor and do For stands with a ceiling area of up not impede the effectiveness of au- to 1,000 m2, smoke removal open- 4.4.1.1 Stand construction and tomatic fire extinguishing systems. ings with clear opening space decorative materials The rear of backlit areas/walls and totalling 1 percent of the stand Materials that are flammable, drip LED walls must remain accessible area, windows or doors with clear while burning or generate toxic to the fire brigade without the use opening space totalling 2 percent gases or large amounts of smoke, of tools. of the stand area or a mechanical such as most thermoplastics (in- Bamboo, reed, hay, straw, bark smoke extraction system with an cluding polystyrene (styrofoam)), mulch, peat or similar materials do air volume flow rate of 36 m3/h per cannot be used for stand construc- not generally satisfy the aforemen- square metre of stand area are tion. For safety reasons, special tioned requirements, and should considered adequate. No require- requirements may be imposed for generally be afforded special pro- ments relating to maintenance of load-bearing structural components tection or treated to render them thermal and electrical functions in individual cases (e.g. non-flam- non-flammable. Deciduous and co- apply to systems for mechanical mable). Attachments that are struc- niferous trees may only be used if smoke removal from exhibition turally necessary or load-bearing their roots are kept moist at all stands, since such smoke removal can only be made using non-flam- times. Attachments that are struc- is only relevant in the self-help mable fasteners and materials. All turally necessary can only be made phase and possibly for giving help stand construction and decorative using fasteners approved for this to third parties and no requirements materials must at least be classified purpose (e.g. plastic cable ties are are prescribed for exhibition stand as flame-retardant class B1 in ac- prohibited!). 19
Technical Guidelines 4.4 Fire protection and safety regulations The use of candles and similar nected from the battery, e.g. by Pyrotechnic articles lacking a cer- sources of light as table decora- means of a battery disconnect tificate of conformity and fireworks tions is permissible with the con- switch. of categories II, III and IV are pro- sent of Messe Frankfurt Venue - It must be ensured that there is no hibited. GmbH’s Technical Project Manage- voltage at the high-voltage battery ment department. / the high-voltage battery must be 4.4.1.5 Balloons in a typical, non-critical state for a The use of balloons filled with a 4.4.1.2 Exhibiting motor vehicles battery. combustible gas in the exhibition at stands - Batteries may only be charged in halls or outdoor areas is prohibited. Messe Frankfurt Venue GmbH’s the exhibition halls with the prior It is possible to apply to Messe Technical Project Management agreement of Messe Frankfurt Frankfurt Venue GmbH’s Technical must be notified if motor vehicles Venue GmbH’s Technical Project Project Management for its per- are to be exhibited. This notification Management mission for balloons filled with must include the number of vehi- - The positions of the vehicles with- safety gas that are firmly anchored cles, as well as the specification of in the stand area must be shown to a stationary structure, are locat- the type(s) of vehicle(s) to be on a plan. ed within the stand and do not ex- shown. - The relevant rescue sheets must ceed the maximum height. The dis- be kept at the stand, and are also tribution of gas-filled balloons is Vehicles with combustion engines to be submitted to Messe Frank- prohibited. - The fuel tank must be locked and furt in advance. nearly empty. -Vehicles with fuel cells or other 4.4.1.6 Flying objects - Vehicles being exhibited may be drive units are considered sepa- The use of flying objects such as powered by the starter battery as rately. UAS, drones etc. in the exhibition long as is it ensured that no haz- A sufficient quantity of suitable ex- halls or outdoor areas is only per- ardous gases are produced (e.g. tinguishing units/agents for all vehi- mitted with the prior agreement of by using gel batteries), the battery cles is to be kept available at the Messe Frankfurt Venue GmbH’s contacts are configured such that stand at all times. Technical Project Management. Ex- they are safe to touch, and the Messe Frankfurt Venue GmbH re- ceptions to this rule require the pri- starter remains disconnected from serves the right to require additional or written consent of Messe Frank- the battery. measures. furt Venue GmbH. - The battery is to be disconnected or removed in all other cases. 4.4.1.3 Explosive materials 4.4.1.7 Fog machines, hazers, Explosive materials are subject to Sparkulars and laser systems Vehicles with natural gas propul- the German Explosives Act Due to the fact that the use of fog, sion systems (Sprengstoffgesetz), and may not Sparkulars and haze may trigger - The gas tanks must have been be exhibited at trade fairs or exhibi- the automatic fire alarms installed emptied and depressurised (see tions. The same applies to ammuni- in the exhibition halls, Messe also Item 5.7). tion in the sense of the German Frankfurt Venue GmbH’s Technical Firearms Act (Waffengesetz). Project Management must be noti- Vehicles with alternative drive fied in writing of the use of such technologies, e.g. electrically-pow- 4.4.1.4 Pyrotechnics devices at least six weeks before ered vehicles or hybrid vehicles Pyrotechnic shows must be regis- the start of the set-up period. This - The fuel tank must be locked and tered with Messe Frankfurt. Fur- notification must include the num- nearly empty. thermore, approval must also be ber of such devices, their model(s), - The drive motor must be discon- obtained from local authorities. and information on the type of fog 20