Synchronous Generator Design Assignment Engineering 1931F Spring 2019
←
→
Page content transcription
If your browser does not render page correctly, please read the page content below
Synchronous Generator Design Assignment Engineering 1931F Spring 2019 Select an arbitrary amount of power between 30 and 250 MW and design a two-pole, smooth-rotor generator for 60 Hz power generation. As a fundamental constraint on your design, use a nameplate power factor of 0.9 for the output under proper operating condi- tions. (I chose that specification to match that of a large Hitachi generator, the design of which is discussed in a paper 1 posted on the class website 2. This also makes sense as giv- ing stable, high-efficiency, startup conditions.) In class, we made a very simple argument that the output power of a generator is directly proportional to the volume of the rotor. The easiest approach to the design process is to exploit this relationship. Instead of starting with the power, start with the size and calcu- late the power. Adjust size and turns counts to get the desired generator. It also turns out that any given mechanical arrangement, that is, rotor and winding design, will have an optimum output current and voltage that you can only tweak rather than specify in advance. The optimization comes from the constraint of the power factor through a phasor calculation of the output power at fixed angle and full excitation E. The design style shall be what we have discussed in class, namely both stator and rotor windings are crude discrete stepwise approximations to a sinusoidal distribution. The rotor induces a stepwise approximate sinusoid in each turn of a stator winding and spreading the stator turns sinusoidally smooths the output further. The number of turns in each phase of the stator is usually quite small. The design process for this exercise does not ask you to work out the real spacing for with set of windings. Instead it uses equa- tions based on continuous sinusoidal distributions of current. For the general idea behind this approach, see the Appendix to the “Generators Description and Analysis” from the class website under Class Notes and PowerPoints. At the end, you draw a couple of ap- proximate graphs of how the stepwise approximation changes the output. By “designing” I mean choosing quantitative values for the size of rotor and armature (stator), optimizing the number of stator turns, determining the rotor ampere-turns prod- uct, choosing a number of rotor turns, calculating required “wire” sizes for both stator and rotor, etc. While you will calculate the losses in each part of the generator, you do not have to work out all the details of coolant flow. The three places where heat is gener- ated are the rotor and stator windings, and the armature iron where there are hysteresis and eddy current losses. Each is a different cooling problem. You will calculate the amount of gas or water needed to carry off each component of the heat but do not have to figure out the pipe and port sizes or required pressures. (Should I teach this course again, I will fix that lost design opportunity!) 1 Seijiro Muramatsu, Kado Miyakawa, Mitsuru Onoda, Kazuhiko Takahashi, and Kengo Iwashige, Completion of a 1,120-MVA Turbine Generator for Huadian International Zouxian Power Plant in China, Hitachi Review Vol. 56 (2007), No. 4 2 http://www.brown.edu/Departments/Engineering/Courses/ENGN1931F/index.html
ENGN1931F – Spring 2019 Generator Design To make this exercise feasible, I have written an Excel spreadsheet that lays out the re- quired inputs and outputs of the calculation and has some of the data that you need in it already. I will post it on the class website shortly and will also post a pdf file of my own design of a 100 MVA generator 3. Table I gives a list of the inputs of the calculation. There is a sheet called “Parameters” in the Excel workbook from which Table I was tak- en that lists output and working parameters as well. The Excel file will be missing some strategic cell formulae so that there will be some- thing for you to enter by way of formulae. Table II below lists the missing formulae along with some indication of their functions and units. I have put the datasheets of two product data bulletins on the properties and usage of AK electrical steels and of Carpenter core irons on the class website. You will use the AK data for the stator laminations and will choose a Carpenter alloy for the rotor. There is section below on “Selecting Steel for the Stator” which is a short guide to where data may be found in the AK Steel user guides. There is a place in the Excel spreadsheet for you to enter the relevant material properties for the steel that that you select for the stator laminations. You will decide on the best choice of stator material by first estimating the stator weight and then looking at the total losses in the stator. There are two macros in the spreadsheet, one of which optimizes the number of stator turns and the other calculates and graphs the output voltage. The first is invoked when you have the system dimensions in place and want to know what output voltage and cur- rent the generator will give for nameplate ratings. The other macro is used after most of the generator is designed to show what the output is like. In the latter calculation, you select a number of rotor winding slots and draw what the generator waveform will be. A Few Rules of Thumbs and Pedagogy: 1. Do not choose an MVA rating between 85 and 115 MVA because that is my terri- tory. 2. The power of a generator is largely proportional to the volume of the rotor. The textbooks say the rotor is usually between 1.0 and 1.5 m in diameter but I think the range for our MVA ratings is a little wider, possibly as small as 0.8 m and as large as 1.6 m. 3. One cell (H16) requires choosing the cooling gas and the rough rule of thumb is hydrogen above 100 MVA and air below. The only place in calculations this af- fects is the cooling gas flow calculations. I have not automated calculating opera- tion with hydrogen. The unfortunate truth is that the cooling calculations are very crude and inaccurate. 4. Limit the peak field on the rotor in rated operating conditions to 1.0 T to limit the required rotor magnetomotive force. Very likely, this will not be a real limit as I have found lower than that was natural in several calculations. 3 I DO NOT guarantee the correctness of any results in my design. 2
ENGN1931F – Spring 2019 Generator Design 5. Results for many of the calculations depends sensitively on the gap between the rotor and stator. That gap is proportionately larger than it would be for a motor as stator inductance has to be minimized. The gap in this spreadsheet is maximized based on the limit of rotor heating. 6. In calculating the mean magnetic path length, the peak return path magnetization, and the mass and kinetic energy of the system, assume that the armature iron is an annulus with width outside the stator slots about equal to the radius of the rotor. This assures that the peak flux in the rotor and in the return path are approximate- ly equal. That width is a parameter of the machine and you are free to change it by a reasonable amount because the working B_r is much lower than the unloaded value. 7. In calculating the stator core loss, it is necessary to estimate the peak armature B field since the field induced by the output current in the stator coils tends to re- duce the armature field below what would be induced by the rotor alone, that is, in open-circuit operation. The B field on the surface of the armature is a single ro- tating field with an angular distribution that is nearly sinusoidal. This net field on the armature surface is what supplies the flux in the armature coils. Notice that the output voltage of the generator is simply whatever is induced by this flux in the stator coil. Estimate the peak armature surface field from the output voltage magnitude. 8. A correction to the gap length from the finite permeability of the iron is optional but I encourage it. Doing so gives a better feel for the effect of high permeability material. Since the net rotor field is near 1.0 T, the mean permeability at that field strength is a reasonable value for this correction. 9. There is no correction for fringing in either the gap or the stator and rotor end plates. Hence the coupling coefficient K = 1.0. 10. The lamination thickness is a matter of your choice but I think the range is lim- ited. Read the AK product brochure on selecting materials for a sophisticated and informed discussion of the factors that go into the choice. 11. The loss in the stator from hysteresis and eddy currents is based on the aggregate loss per pound for the material at peak magnetization of 15 kG (1.5 T) as given in the AK product brochures. Revise this for your actual peak under operating con- ditions as the square of the ratio of B to 1.5 T. 12. In Excel the dollar sign is used in cell references to prevent automatic changes to a formula as it is copied or moved. I have tried to use that notation in all refer- ences to cells in column H, e.g., $H$6 for the angular velocity of the rotor. 13. If you are confused by something, ask me! I pretty much guarantee some confu- sion as this is only the third time I have ever tried an exercise like this and I have completely rewritten the spreadsheet completely. Very likely there is an outright mistake somewhere. Structure of the Spreadsheet: The Excel spreadsheet is called “SynchronousGeneratorDesign2019.xlsm” on the class website from which you can download it. As Table I shows, I have tried to organize the 3
ENGN1931F – Spring 2019 Generator Design ‘Design Sheet’ tab so that inputs to the problem, e.g., stator turns, rotor size, etc., are near the top of column B in cells that are green. There are a three more inputs similarly la- beled with green further down column B. Similarly materials properties and other con- stants are in column H and the calculated outputs are in column B starting at line 14. I have duplicated the most important output values in a compact table starting at column G line 27. To give you something to do, I have removed some of the formulae. Table II lists the cells and functions that are missing. These are simple formulas and there are a couple of derivations and listings in the Strategic Derivations section of this write-up that should help you figure out the missing pieces. All the missing pieces are covered in the class notes on the class website on generator design. The spreadsheet does two distinctly different types of design calculations. The first done on the ‘Design Sheet’ tab is the calculation of rotor current, machine dimensions, output voltage, output currents, open-circuit voltage, etc. These are the discrete numbers that characterize the machine operation. Most of these calculations are done with simple ap- proximate formulae embedded in the output cells of column B. The optimum nameplate output current is the most complicated calculation and requires maximizing output power by adjusting the output current. There is a macro called OptimizeLoadCurrent that in- vokes the “Solver” in Excel to find the maximum power. It depends on the output per phase voltage being calculated correctly and the formula for that calculation is missing. The second type of calculation is the approximation of the output waveform to a sinusoid by finding the best rotor slot placement and the optimal spread for the stator windings. This calculation done on the ‘Rotor Winding Design’ tab and is a relative voltage calcula- tion scaled to a nominal 1 volt peak output. You fill in the slot angle formula, the number of slots and the spread of the stator winding and run a second macro called ‘SineApprox- imation’. The result is graphed on the ‘Open-circuit Waveform’ tab. Selecting Steel for the Stator: You need to choose a grade of non-oriented electrical steel and the lamination thickness from the materials supplied by AK Steel. I have copied two Product Data Bulletins from AK Steel’s website: “Selection of Electrical Steels for Magnetic Cores” and “AK Nonor- iented Electrical Steels.” I urge you to read these through but to help you along here are some of the most important points in these guides. In “Selection of Electrical Steels…” • Page 7: Composition by grade, particularly silicon weight percent. (Cost is affect- ed heavily by silicon and generally permeability decreases with increasing silicon but loss decreases.) • Page 8: Gauge (lamination) thickness • Page 12: Aggregate core loss, hysteresis and eddy current, per pound of steel by grade and lamination thickness. This simplifies and improves the accuracy of sta- 4
ENGN1931F – Spring 2019 Generator Design tor loss calculations. (Cost is affected by thickness for reasons discussed in this section of the PDB.) • Page 19: Industry practice in grade selection. Your most important consideration is loss at fairly high peak magnetization. In “AD Nonoriented Electrical Steels…” • Page 4: Interesting information on insulating the laminations • Page 12: Magnetic properties by grade, including saturation magnetization, hyste- resis loss, and maximum permeability at 10 kilogauss. What to Hand In: I would like both an electronic copy of the spreadsheet as you finish it up for your choice of power, size, etc. and a printed copies of the output table from the Design Sheet tab and the graph of the sine approximation. Finally try changing the number of your stator turns leaving other inputs untouched. What effect does this have on the major output? Does it affect loses? Nameplate ratings? Strategic Derivations: There is really no upper limit to the rotor excitation or mmf you would like to get but there is a practical limit. Whatever power you put into the rotor to raise the number of ampere turns ( N ROT I ROT ) has to be removed by some cooling system. A generator is a confined space and this limits the amount of power per square meter that can be removed within the limits set by the materials of the system. Similarly, there is an upper limit on the current density, the number of amperes per square centimeters of the rotor winding wire. The power dissipated under the side of the rotor is just the resistance of the wires along that side times the square of the rotor current. The wire resistance can be calculated from the resistivity of the wire in the usual way. Let ρ be the resistivity and AC be the 2 ρ lROT N ROT I ROT 2 cross sectional area of the rotor wire, then PROT _ SIDE = . Let pMAX be the AC maximum power per square meter that can be removed from the surfaces of the rotor by gas cooling. Divide the power PROT _ SIDE from the side of the rotor by the area of the rotor PROT _ SIDE to find pMAX ≥ . Substitute for PROT _ SIDE and rearrange terms to get 2π RROT lROT N ROT I ROT pMAX π ≤ RROT ρJ I ROT where J = is the current density in the rotor wire. There is a practical minimum for AC current density set by the need to fit enough turns onto the rotor. This implies that the number of ampere turns around the rotor circumference is limited to a certain constant 5
ENGN1931F – Spring 2019 Generator Design pMAX π . I have made my best guess as to this practical number and have put it into cell ρ J MIN H11. You will need this result because the mmf cell is missing the formula. Once you have found the mmf, you can trade off the selection of the peak open-circuit voltage (emf) against rotor-stator air gap. In my design flow, you choose E first and see what the resulting stator inductance and output current/voltage/and power will be. To some extent you can adjust the optimum output voltage with this choice. In class I derived simple formulas for the inductances and mutual inductances of wind- ings that are spread about the rotor or stator in approximately sinusoidal distributions. That information is collected in the “Generator Analysis Notes2019.doc” WORD file on the class website. These led to the equivalent circuit shown below. The factor of 3/2 the stator inductance as the principal part of the generator output impedance is the result of the mutual inductances of the stator coils at 120 degree spatial rotation relative to each other. By inspection generator of the equivalent circuit below, the open-circuit voltage relates to the terminal voltage and current as: eO −C = vG + iOUT ( RS + jX LEQU ) . You know the phase angle of the output current relative to vG from the nameplate power factor. The effect of RS on the calculated generator voltage under load is negligible and you can neglect it. The real output power is the product of the real component of iOUT with vG . If you use the peak values in this product you need to divide by 2 to get RMS and multiply by 3 be- cause all calculations are done on a per phase basis. You select E first and then must do a phasor calculation to find the relation between output voltage and current. Optimize to find the best nameplate rating by varying the current to maximize power with power fac- tor and E constant. LEQU = 1.5 LST RS I OUT cos(ωt − θ ) LGRID vG = VG cos(ωt ) vGRID Open-circuit voltage =e E cos(ωt + δ ) Generator - Grid There is a “Phasor Spreadsheet” on the website along with the other generator materials under Class Notes. (I like spreadsheets for poking-at-things calculations.) It has phasor calculations for joining a generator to the grid on one tab and the current-voltage relation of the generator itself on another tab. The phasor diagram below shows the critical con- struction at optimum. See spreadsheet for more details including phasors for over and un- der optimum current load. 6
ENGN1931F – Spring 2019 Generator Design In this phasor diagram, the vector marked “|I| is Optimum” is the voltage vector across the source inductance of the equivalent circuit. The dotted vertical line is the magnitude of the component of the voltage across the “source” inductance that is exactly out of phase with the output voltage. Dividing that magnitude by the inductive reactance gives the magnitude of the in-phase current. In turn, multiplying that by the generator output voltage gives the real output power. In the design flow, the rotor mmf is set by heat re- moval. You set E somewhat arbitrarily and use this trigonometric construction to deter- mine the current and voltage output ratings that optimize the output power. The algebraic result of this construction is what goes in cell B27. You are free to adjust the stator turns to trade off voltage for current (insulation for heat removal) somewhat. The ultimate per- formance is not very sensitive to the initial choice of E. In the analysis of generator operation that we did in class (see write-up under class notes), we showed that the peak voltage induced in the stator by this rotor flux is always πω RROT lROT BPEAK N STAT VSTAT _ PEAK = . You substitute a hypothetical, open-circuit 2 BPK _ OPEN to calculate E and the rotor-stator gap. Then work backwards to find the peak rotor field in full power operation from the generator voltage. The two values of BPEAK , open-circuit and in operation, come from the way the B field in the rotor from the output current subtracts from the excitation mmf field caused by the rotor current. [Note: the 7
ENGN1931F – Spring 2019 Generator Design generator never runs with the hypothetical BPK _ OPEN value because one never runs it with full rotor mmf when there is no load. One of the results of our phasor calculations of the generator is a specification of how the generator excitation and load must be adjusted to- gether during operation.] You can calculate the maximum B field throughout the armature iron by using conserva- tion of flux. The design uses an annular shape for the return path. Let T be the thickness of that annulus from the bottom of a wire slot to the outer edge and equate the total flux in the two sides of the return path to the flux on the armature surface to get: 2TlROT BARM = 2rlROT BPK (1.1) The peak field in the right hand side of this expression is the net peak field under rated operating conditions. When the thickness of the armature return path is the same as the radius of the rotor, i.e., T = r , the peak field in the armature iron is the same as the peak field on the surface of the armature. There is some possibility to trade off higher arma- ture field for a smaller armature here. The armature field is what causes eddy and hyste- resis losses so this calculation determines those losses when combined with the stator magnetic properties. AK Steel specifies the total loss per pound of their products at 15 kG peak magnetization for different lamination thicknesses. You may estimate losses at lower fields as varying with the square of the peak field. You calculate the armature B field from equation 1.1. In doing so you, you have to compensate for the net effect of both the rotor excitation and the opposing field induced by the output current on BPK . The easy way to do that is to realize that the generator output voltage is in fact the product of the number of stator turns with the actual flux over half the rotor at whatever orientation angle the net field peaks Finally, in approximating sinusoid fields with steps, the simplest thing to do is to select the rotor bar positions such that the sinusoid passes through the center of each step transi- tion. You set a peak field strength for the total stepwise approximation slightly smaller than the peak value of the sine wave (cell F11 on Rotor Winding Design tab). You calcu- late the values of the voltages halfway up or down each step and use the acos() function in Excel to find the angles for the rotor slots. The spreadsheet is set up so you only have to calculate for half the number of turns and it calculates the remaining positions based on the symmetry of the rotor. The spreadsheet use the total number of slots as input (cell F14) and looks for one fourth of that number for the starting slot positions. Table 1: Input Variables Units Cell Number Rotor radius meters B5 Rotor length meters B6 Nameplate power factor -- B9 N - stator turns -- B8 8
ENGN1931F – Spring 2019 Generator Design Peak open circuit rotor B with full rated excitation - used to calculate rotor mmf and the theoretical equivalent open-circuit voltage, E. Tesla B7 Number of rotor slots: (also used on Rotor Winding De- sign worksheet cell B14) -- B34 Number of Rotor turns -- B35 Width of stator from end of slot to outer radius; possible tradeoff of size of machine versus stator core loss. This is narrowest width of the flux return path meters B69 AK Steel material properties for your choice of material various H14 et seq. Loss in the stator windings as a percentage of the output power; stator bar size calculated from this % B54 Table II: Missing Formulae and Data From Design Sheet Item: Cell Units Open circuit V_gen as peak Y- equivalent voltage. This is related to the power fac- tor argument in this write-up. Another reference point is the spreadsheet on phasor relations posted on the class web site under Class Notes. That has under and over excited cases as well as the op- timum excitation. It shows what is being optimized by the solver. B27 V peak Selection of AK steel and all its properties from AK product selection bulletins Column H rows 14 to 21 Various Number of rotor ampere turns as limited by heat and current density. Very simple if you follow the argument in this write- up. B36 Tesla Rotor current B37 ohm Rotor self-inductance (The rotor self- inductance is related to the mutual in- ductance by a constant.) B38 H. Ohms per kilometer of the stator winding bar/wire. (Stator might be wound with either type of copper material.) B59 Ohm/km 9
ENGN1931F – Spring 2019 Generator Design Stator core losses from mass of stator, AK’s loss factor, and peak B in the return flux path. Correct for peak B relative to 15 kG of the AK specification using the assumption that those losses will scale as the square of B over this range. B75 W Cooling gas flow in cubic feet per minute, the unit most American vendors of cool- B96 ing equipment use. CFM From 'Rotor Winding Design: Angle from base plane of the rotor to turn number B11 to B20 (Same formula all slots) deg. 10
You can also read