SURNA CASSETTE FAN COIL - ISOSTREAM

Page created by Jeffery Austin
 
CONTINUE READING
SURNA CASSETTE FAN COIL - ISOSTREAM
ISOSTREAM®
SURNA CASSETTE
FAN COIL
COOLING/OPTIONAL HEAT
MODELS SCFC-08-X-X-AECM-X-X X

This Surna fan coil is another addition to our full    The unit uses an electronically commutated
line of purpose-built fan coil products providing      (EC) fan motor and modulating valves can be
a wide range of choices for both ducted and            integrated to allow for maximum output at
ductless applications for small to large commercial    minimum energy consumption. The EC fan motor
indoor cannabis cultivation facilities.                also provides extremely quiet operation.

This ceiling cassette ductless fan coil can be         For simple maintenance, the air filter is easily
mounted in any comfort or process room where           removable and washable and is made from self-
wall mounting or remote ducting are not desired        extinguishing acrylic with an efficiency class Merv
taking up no extra floor or wall space.                2-4.

This unit is available in many different sizes.
These fan coils provide maximum flexibility and
application specific options, ensuring a precise
solution for your unique application.

FEATURES AND BENEFITS

 Ductless                              Versatile                         Heating Options
 Ductless application for chilled      Available in multiple sizes and   Surna’s cassette fan coils offer
 water makes installation and          can be mounted in any drop        an electric heat kit or 4-pipe
 cleaning simple.                      ceiling or ceiling recess.        hot water re-heat options for
                                                                         providing cooling and heating
                                                                         options for any space.
SURNA CASSETTE FAN COIL - ISOSTREAM
SPECIFICATIONS
Custom configurations and sizes may be available upon request

                                          SCFC-08-V-X-AECM-X                     SCFC-08-V-X-AECM-X-EH                   SCFC-08-P-X-AECM-X
     PHYSICAL                              2-Pipe, Cooling Only                   2-Pipe with Electric Heat            4-Pipe with Hot Water Reheat

    Length                                                                            22-5/8 in (575 mm)

    Width                                                                             22-5/8 in (575 mm)

    Height                                                                            11-7/16 in (291 mm)

    Weight                                   66.1 lbs (30 kg)                           67.5 lbs (30.6 kg)                    66.1 lbs (30 kg)

    Water Inlet                                                                       3/4 in (19 mm) NPT

    Water Outlet                                                                      3/4 in (19 mm) NPT

    Condensate Drainage
                                                            Outside Diameter: 1 in (25 mm) / Inside Diameter: 13/16 in (21 mm)
    Connection

    Number of Fan Blowers                                                                    Single

     ELECTRICAL

    Power Supply (V/Ph/Hz)                                                                 220/1/60

    Power Input in Cooling Mode                                                               47 W

    Power Input in Heating Mode                   N/A                                                           42W

    Fan Motor Running Current
                                                                                             0.43 A
    @220V

    Min.Circuit Ampacity (MCA)                   0.27 A                                      11.6 A                                0.27 A

    Max. Overcurrent Protection
                                                                                              15 A
    (MOP)

    Full Load Amps (FLA)                         0.21 A                                       9.3 A                               0.43 A

     CHILLED WATER COIL PERFORMANCE

    Total Airflow                                                                   476 CFM (808.7 m3/h)

    Cooling Capacity                                            15342 BTU/Hr (4.5 kW)                                     12852 BTU/Hr (3.91 kW)

    Sensible Cooling Capacity                                   10239 BTU/Hr (3 kW)                                       8794 BTU/Hr (2.81 kW)

    Cooling Water Flow Rate                                       3 GPM (681.4 L/h)                                         2.5 GPM (567.8 L/h)

    Cooling Water Pressure Drop                                 10.6 Ft/Head (31.8 kPa)                                    5.6 Ft/Head (16.8 kPa)

    Heating Water Flow Rate                                              N/A                                                 0.7 GPM (159 L/h)

    Heating Water Pressure Drop                                          N/A                                               0.3 Ft/Head (0.9 kPa)

     ELECTRIC HEAT PERFORMANCE
    Max. Heating Capacity                         N/A                                         2 kW                                  N/A
     REHEAT COIL PERFORMANCE
    Hydronic Heating Capacity
                                                                         N/A                                               8794 BTU/hr (2.81 kW)
    (EWT 1400F/60°C)

     CERTIFICATIONS

                                                                                              ETL

             Note:
             a. Assumes entering water     b. Data is based on fan running c. Data assumes specified GPM         d. All dimensions are
             temperature (EWT) of 450 F    at maximum speed @ 220V                                               approximate within 1/16 of an
             (7.220 C)                                                                                           inch of those indicated

                                                   P    303.993.5271
                                                                                                                                     August 2021
 surna.com                                         E    info@surna.com                                   All data subject to change without notice
ISOSTREAM®
SURNA CASSETTE
FAN COIL
COOLING/OPTIONAL HEAT
MODELS SCFC-16-X-X-AECM-X-X X

This Surna fan coil is another addition to our full    The unit uses an electronically commutated
line of purpose-built fan coil products providing      (EC) fan motor and modulating valves can be
a wide range of choices for both ducted and            integrated to allow for maximum output at
ductless applications for small to large commercial    minimum energy consumption. The EC fan motor
indoor cannabis cultivation facilities.                also provides extremely quiet operation.

This ceiling cassette ductless fan coil can be         For simple maintenance, the air filter is easily
mounted in any comfort or process room where           removable and washable and is made from self-
wall mounting or remote ducting are not desired        extinguishing acrylic with an efficiency class Merv
taking up no extra floor or wall space.                2-4.

This unit is available in many different sizes.
These fan coils provide maximum flexibility and
application specific options, ensuring a precise
solution for your unique application.

FEATURES AND BENEFITS

 Ductless                              Versatile                         Heating Options
 Ductless application for chilled      Available in multiple sizes and   Surna’s cassette fan coils offer
 water makes installation and          can be mounted in any drop        an electric heat kit or 4-pipe
 cleaning simple.                      ceiling or ceiling recess.        hot water re-heat options for
                                                                         providing cooling and heating
                                                                         options for any space.
SPECIFICATIONS
Custom configurations and sizes may be available upon request

                                          SCFC-16-V-X-AECM-X                       SCFC-16-V-X-AECM-X-EH                    SCFC-16-P-X-AECM-X
     PHYSICAL                              2-Pipe, Cooling Only                     2-Pipe with Electric Heat            4-Pipe with Hot Water Reheat

    Length                                                                           44-7/8 in (1140 mm)

    Width                                                                            22-13/16 in (579 mm)

    Height                                                                               11-7/16 in (291 mm)

    Weight                                   115 lbs (52.2 kg)                            120 lbs (54.4 kg)                    115 lbs (52.2 kg)

    Water Inlet                                                                          3/4 in (19 mm) NPT

    Water Outlet                                                                         3/4 in (19 mm) NPT

    Condensate Drainage
                                                             Outside Diameter: 1 in (25 mm) / Inside Diameter: 13/16 in (21 mm)
    Connection

    Number of Fan Blowers                                                                       Twin

     ELECTRICAL

    Power Supply (V/Ph/Hz)                                                                   220/1/60

    Power Input in Cooling Mode                                                                89 W

    Power Input in Heating Mode                    N/A                                                            84 W

    Fan Motor Running Current
                                                                                               0.81 A
    @220V

    Min.Circuit Ampacity (MCA)                    0.51 A                                       17.6 A                               0.51 A

    Max. Overcurrent Protection
                                                   15 A                                         20 A                                 15 A
    (MOP)

    Full Load Amps (FLA)                          0.4 A                                        14.04                                0.4 A

     CHILLED WATER COIL PERFORMANCE

    Total Airflow                                                                   853 CFM (1449.3 m3/h)

    Cooling Capacity                                             28497 BTU/Hr (8.4 kW)                                     16078 BTU/Hr (4.71 kW)

    Sensible Cooling Capacity                                    19128 BTU/Hr (5.6 kW)                                     11280 BTU/Hr (3.31 kW)

    Cooling Water Flow Rate                                       5.6 GPM (1271.9 L/h)                                       3.2 GPM (726.8 L/h)

    Cooling Water Pressure Drop                                  12.8 Ft/Head (38.3 kPa)                                    4.5 Ft/Head (13.4 kPa)

    Heating Water Flow Rate                        N/A                                                                       1.3 GPM (295.3 L/h)

    Heating Water Pressure Drop                                           N/A                                                0.5 Ft/Head (1.5 kPa)

     ELECTRIC HEAT PERFORMANCE
    Max. Heating Capacity                          N/A                                         3 kW                                  N/A
     REHEAT COIL PERFORMANCE
    Hydronic Heating Capacity
                                                                          N/A                                              25172 BTU/Hr (7.38 kW)
    (EWT 1400F/60°C)

     CERTIFICATIONS

                                                                                                ETL

             Note:
             a. Assumes entering water     b. Data is based on fan running c. Data assumes specified GPM          d. All dimensions are
             temperature (EWT) of 450 F    at maximum speed @ 220V                                                approximate within 1/16 of an
             (7.220 C)                                                                                            inch of those indicated

                                                 P    303.993.5271
                                                                                                                                     August 2021
surna.com                                        E    info@surna.com                                     All data subject to change without notice
ISOSTREAM®
SURNA CASSETTE
FAN COIL
COOLING/OPTIONAL HEAT
MODELS SCFC-20-X-X-AECM-X-X X

This Surna fan coil is another addition to our full    The unit uses an electronically commutated
line of purpose-built fan coil products providing      (EC) fan motor and modulating valves can be
a wide range of choices for both ducted and            integrated to allow for maximum output at
ductless applications for small to large commercial    minimum energy consumption. The EC fan motor
indoor cannabis cultivation facilities.                also provides extremely quiet operation.

This ceiling cassette ductless fan coil can be         For simple maintenance, the air filter is easily
mounted in any comfort or process room where           removable and washable and is made from self-
wall mounting or remote ducting are not desired        extinguishing acrylic with an efficiency class Merv
taking up no extra floor or wall space.                2-4.

This unit is available in many different sizes.
These fan coils provide maximum flexibility and
application specific options, ensuring a precise
solution for your unique application.

FEATURES AND BENEFITS

 Ductless                              Versatile                         Heating Options
 Ductless application for chilled      Available in multiple sizes and   Surna’s cassette fan coils offer
 water makes installation and          can be mounted in any drop        an electric heat kit or 4-pipe
 cleaning simple.                      ceiling or ceiling recess.        hot water re-heat options for
                                                                         providing cooling and heating
                                                                         options for any space.
SPECIFICATIONS
Custom configurations and sizes may be available upon request

                                          SCFC-20-V-X-AECM-X                     SCFC-20-V-X-AECM-X-EH                        SCFC-20-P-X-AECM-X
     PHYSICAL                              2-Pipe, Cooling Only                   2-Pipe with Electric Heat                 4-Pipe with Hot Water Reheat

    Length                                                                         32-11/16 in (830 mm)

    Width                                                                          32-11/16 in (830 mm)

    Height                                                                          11-7/16 in (291 mm)

    Weight                                  110 lbs (49.9 kg)                           110.5 ibs (50.1 kg)                       110 lbs (49.9 kg)

    Water Inlet                                                                     3/4 in (19 mm) NPT

    Water Outlet                                                                    3/4 in (19 mm) NPT

    Condensate Drainage
                                                            Outside Diameter: 1 in (25 mm) / Inside Diameter: 13/16 in (21 mm)
    Connection

    Number of Fan Blowers                                                                     Single

     ELECTRICAL

    Power Supply (V/Ph/Hz)                                                                  220/1/60

    Power Input in Cooling Mode                                                              224 W

    Power Input in Heating Mode                   N/A                                                               219 W

    Fan Motor Running Current
                                                                                             2.04 A
    @220V

    Min.Circuit Ampacity (MCA)                   1.27 A                                       2.4 A                                    1.27 A

    Max. Overcurrent Protection
                                                  15 A                                         25 A                                     15 A
    (MOP)

    Full Load Amps (FLA)                         1.02 A                                       19.2 A                                   2.04 A

     CHILLED WATER COIL PERFORMANCE

    Total Airflow                                                                 1300 CFM (2208.7 m3/h)

    Cooling Capacity                                            32423 BTU/Hr (9.5 kW)                                         22318 BTU/Hr (6.54 kW)

    Sensible Cooling Capacity                                   23166 BTU/Hr (6.8 kW)                                         15307 BTU/Hr (4.49kW)

    Cooling Water Flow Rate                                      6.4 GPM (1453.6 L/h)                                           4.4 GPM (999.3 L/h)

    Cooling Water Pressure Drop                                 8.8 Ft/Head (26.4 kPA)                                         6.8 Ft/Head (20.3 kPa)

    Heating Water Flow Rate                                              N/A                                                    1.6 GPM (363.4 L/h)

    Heating Water Pressure Drop                                          N/A                                                    0.7 Ft/Head (2.1 kPa)

     ELECTRIC HEAT PERFORMANCE
    Max. Heating Capacity                         N/A                                         4 kW                                      N/A
     REHEAT COIL PERFORMANCE
    Hydronic Heating Capacity
                                                                         N/A                                                  31509 BTU/Hr (9.23 kW)
    (EWT 1400F/60°C)

     CERTIFICATIONS

                                                                                               ETL

             Note:
             a. Assumes entering water     b. Data is based on fan running c. Data assumes specified GPM             d. All dimensions are
             temperature (EWT) of 450 F    at maximum speed @ 220V                                                   approximate within 1/16 of an
             (7.220 C)                                                                                               inch of those indicated

                                                   P      303.993.5271
                                                                                                                                          August 2021
 surna.com                                         E      info@surna.com                                      All data subject to change without notice