STATIONARY LOAD BANK TECHNICAL MANUAL
←
→
Page content transcription
If your browser does not render page correctly, please read the page content below
STATIONARY LOAD BANK TECHNICAL MANUAL Customer: XXXXXX Work Order: XXXXX-XX-XX Model: XXXXX March 2012 The information herein is the property of Simplex, Inc. and/or its subsidiaries. Without written permission, any copying, transmitting to others, and other use except that for which it is loaned, is prohibited. (File: LBS-TS-120322.indd)
® STATIONARY LOAD BANK MANUAL • Touchscreen Control • page 1 of 23 Contents DESCRIPTION .............................................................................. 2 Control System ...................................................................... 3 Cooling System ...................................................................... 4 Load System ........................................................................... 4 PRIMARY INSPECTION ............................................................... 5 INSTALLATION............................................................................. 5 Location .................................................................................. 5 Procedure ............................................................................... 6 OPERATION.................................................................................. 7 Manual Operation ................................................................... 7 Numeric Load Application .................................................... 8 Load Dump ............................................................................. 8 Diagnostic Screen .................................................................. 9 FAILURE DETECTION.................................................................. 9 Thermocouples ...................................................................... 9 MAINTENANCE .......................................................................... 10 Each Operation .................................................................... 10 Every 50 Hours or 6 Months ............................................... 10 Motor Lubrication ................................................................ 11 TROUBLESHOOTING ................................................................ 12 Cooling Fan Motor Will Not Operate .................................. 12 Cooling Failure Indicated .................................................... 12 Metering System Does Not Operate Properly ................... 13 Some Load Steps Cannot Be Energized ............................ 13 DRAWINGS AND PARTS LIST .................................................. 13 APPENDIX A - ABBREVIATIONS USED IN THIS MANUAL..... 14 APPENDIX B - CALCULATIONS & FORMULAS ...................... 15 APPENDIX C - TORQUE VALUES ............................................. 18 APPENDIX D - TYPICAL LIFT EYE INSTALLATION ................ 20 APPENDIX E - SATURN BEARINGS ......................................... 21 AUTOMATIC LOAD APPLICATION ADDENDUM ..................... 24 Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-120322.indd • © 2012 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
® STATIONARY LOAD BANK MANUAL • Touchscreen Control • page 2 of 23 Part of Typical Pictorial Drawing with optional Exhaust Hood DESCRIPTION Simplex Stationary Load Banks are Power source testing is accomplished precision test instruments specifically by applying resistive load steps at unity designed to apply discrete, selectable (1.0) power factor. See the Load Bank electrical load to a power source while Specifications Sheet in the front of this measuring the response of the genera- manual for the rating of your Load Bank. tor to the applied load. They also pro- The illustrations in this manual are ex- vide a means for routine maintenance amples only and may differ from your exercise to assure long term reliability Load Bank. and readiness of the standby generator. Exercise Load Banks eliminate the det- Load application is by magnetic contac- rimental effects of unloaded operation tor. All load branch circuits are protected of diesel engine generators. by 200,000AIC class-T fuses. Simplex Stationary Load Banks are available in various cabinet designs and capacities. Standard cabinets are rated as Type 3R outdoor weatherproof but are also available as Type 1 indoor. If Never operate or service a Load desired, the Load Bank can be mounted Bank that is not properly con- on a trailer. nected to an earthground. Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-120322.indd • © 2012 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
® STATIONARY LOAD BANK MANUAL • Touchscreen Control • page 3 of 23 Part of Typical Control Section Drawing The Load Bank consists of three prin- The Control System allows the operator cipal systems: to apply a desired load to the test source 1. Control System and measure the response of the test source to the load. This Load Bank is 2. Cooling System protected against cooling failures (loss 3. Load System of cooling air flow, high intake or exhaust air temperature which could damage the Load Bank or present a safety hazard CONTROL SYSTEM to the operator). When a cooling failure Load Bank operation and status indica- occurs the automatic safety features tion is via a Operator Interface (HMI) immediately remove the load from the touchscreen mounted locally on the load source. The malfunction must Load Bank and/or housed in a remote be corrected and the Control System box. The Control System includes a must be reset by turning the Load Bank Programmable Logic Controller (PLC) “Off” then “On” before the load can be and 120V discrete componets. A 24VDC re-applied. power supply (DCS) located in the Load Control Power (120V) is supplied via Bank powers the touchscreen. Common the load source and the Control Power serviceable components include Control Transformer (T1). Control Power is Fuses (CF Series) and Power Fuses applied to the coil of the Fan Motor (F Series). The standard touchscreen Contactor (FMC) through closed Fan is composed of the following screens: Start Relay (FSR) contacts 7–4. Fan Main, Manual Load, Numeric Load, power is applied to the Fan Motor (MOT) Setup, Metering, and Diagnostic. through the Fan Circuit Breaker (FCB), the Main Disconnect Switch (DSW), the Fan Motor Contactor (FMC) contacts, and an Overload Relay (OLR). Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-120322.indd • © 2012 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
® STATIONARY LOAD BANK MANUAL • Touchscreen Control • page 4 of 23 COOLING SYSTEM Resistive Load Elements are cooled by a forced air system consisting of an aluminum fan blade directly driven or belt driven by a TEFC motor. The fan motor is energized by a 600V, 3 pole contactor and protected by a three pole, 100A frame circuit breaker. Reactive Load Elements (inductive or capacitive) are convection cooled or cooled by a forced air system. LOAD SYSTEM The Load System consists of indepen- dently controlled resistive and/or reac- tive load elements specifically designed for Load Bank systems. They are pro- tected by 200,000AIC, 600VAC fuses. Simplex Resistive Load Elements con- servatively operate at approximately half the maximum temperature rating of the alloy (1080°F vs. 1920°F). For Part of Typical Tray Layout Drawing example: Alloy: FeCrAl Reactive Load Elements are iron-core, non-saturable, air gap calibrated and air Ratings: 3333W@120V cooled. Standard elements are varnish 4170W@139V coated. Epoxy coatings are available Connections: 120V wye (208V), for severe environments. 139V wye (240V, 3ø), 277V wye (480V, 3ø), 240 delta (240V, 3ø), or 480 delta (480V, 3ø). Always remove all power from See Parts Legend Drawing for specific the load bus and all fan/control elements used. power before servicing the Load Bank. Never operate or service These elements are rigidly supported a Load Bank that is not properly by high-temperature, ceramic-clad, connected to an earthground. stainless-steel supports. Element-to- element short circuits are virtually elimi- nated. The elements are assembled in discrete trays which are assembled in a vertical “stack”. Each tray is indepen- Do not store or operate in rain dently serviceable without disturbing or spray unless unit is designed adjacent trays. for this service or adequate protection is provided. Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-120322.indd • © 2012 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
® STATIONARY LOAD BANK MANUAL • Touchscreen Control • page 5 of 23 PRIMARY INSPECTION If any problems are observed Preventative visual inspections of the during Primary Inspection call shipping crate and Load Bank is ad- the Simplex Service Manager at vised. Physical or electrical problems 217-483-1600 (24hrs.) due to handling and vibration may oc- cur. Never apply power to a Load Bank before performing this procedure. The 8. Inspect bottom of crate/enclosure following Nine Point/30 Minute Inspec- for any components that may have tion is recommended before installa- jarred loose during shipment such as tion, as part of the 50 hour / 6 month indicator light lenses, switch knobs, maintenance schedule and whenever etc. the Load Bank is relocated: 9. Visually inspect element chamber 1. If crate shows any signs of damage for foreign objects, broken ceramic examine the Load Bank in the cor- insulators, mechanical damage. responding areas for signs of initial problems. 2. Check the entire outside of the INSTALLATION cabinet for any visual damage which could cause internal electrical or LOCATION mechanical problems due to reduced Type 3R Load Banks are intended for clearance. outdoor installation. Type 1 Load Banks 3. Inspect all hinged panels and doors must be installed indoors. The load ele- for smooth and safe operation, try all ments in this Load Bank are cooled by latches and knobs. a forced air system which discharges 4. Rotate and push all switches through through the top, sides or the back of the all positions to ensure smooth opera- cabinet. This Load Bank will produce a tion. large quantity of exhaust air. Location of 5. Check cooling system by inspect- the Load Bank is of prime importance ing fan motor and blade. Check fan and should be done by trained person- blades for stress fractures. Slowly nel. It is one of the most critical factors rotate blade by hand and note clear- involved in safe operation. The Load ance of blade tip through its rotation Bank must be positioned and installed near the housing. Observe free rota- according to large airflow requirements. tion of motor shaft. • Horizontal airflow Load Banks require 6. Inspect all relays, timers, and control a minimum clearance of 25 feet on modules by opening all accessible the discharge side, and 6 feet on all panels. Make sure all components other sides. are secure in their bases and safety • Vertical airflow Load Banks require bails are in place. Spot check electri- a mimimum clearance of 6 feet on cal connections for tightness. If any all sides. loose connections are found inspect and tighten all remaining connections. • Load Banks installed indoors must be 7. Examine all accessible internal equipped with an exhaust air duct of electrical components such as fuses, minimum back pressure (supplied by contactors and transformers. Check others) which routes all Load Bank lugged wires at these components. hot exhaust air outdoors. Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-120322.indd • © 2012 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
® STATIONARY LOAD BANK MANUAL • Touchscreen Control • page 6 of 23 • Never install any structure or object at any height above the Load Bank. • Always locate the Load Bank in a secure area accessible by trained personnel only. • Use the eyehooks and forklift chan- nels provided to position the Load Bank. • Never move the Load Bank with the exhaust hood attached (if equipped). • Never point the exhaust at a nearby surface or object which may be ad- versely affected by high temperature. Footprint - Part of Typical Pictorial Drawing • Never operate the Load Bank in a confined space without regard for PROCEDURE adequate intake of air and provision Unless specified on the drawing, make for exit of high temperature exhaust. all connections in compliance with NEC. • Consider that the Load Bank and a 1. Confirm the test source is properly nearby generator set may have to grounded and ground the Load Bank. compete for cooling air. 2. Confirm the Main Disconnect Switch • Never bounce hot exhaust air off (DSW) is in the “Off” position. nearby objects and allow it to recir- culate through the cooling system. 3. Using the slots and holes provided mount the remote box (if applicable). • Never operate the Load Bank in proximity to a sprinkler system. 4. Per PLC Control drawing connect TB‘COM’ contacts on the Load Bank Failure to properly install this Load to TB‘R’ contacts on the remote box Bank may result in substantial damage as shown (if applicable). to or the destruction of the Load Bank, adjacent equipment and the building in 5. Per load connection drawings cable which the Load Bank is installed. the load source to the Load Bank. 6. If the Load Dump feature is desired, remove the factory installed jumper at TB‘LD’ 1–2 and connect customer supplied Load Dump contacts to Damage to the Load Bank due to TB‘LD’ 1–2 as shown. improper installation is not cov- Open contacts to dump load. ered by the Simplex Warranty. Close contacts to enable load. 7. Place the Main Disconnect Switch (DSW) in the “On” position. Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-120322.indd • © 2012 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
® STATIONARY LOAD BANK MANUAL • Touchscreen Control • page 7 of 23 OPERATION The touchscreen is composed of the following screens: Main, Manual Load, Numeric Load, Setup, Metering, and Diagnostic. Pressing the “Status” button when available opens the Main Screen. MANUAL OPERATION 1. Start-up generator or bring other test source on line. 2. Adjust power source voltage and frequency. 3. Press the “Control Power On” button to energize the cooling fan. “Control Power is On” will be indi- Main Screen cated and Load Bank status indica- tors will appear. 4. Verify normal operation before proceeding. 5. Visually observe correct fan opera- tion and investigate any unusual fan related noises. 6. Check air intake for obstructions and confirm positive air flow. 7. Press the “Manual Load” button. 8. Select the desired load steps by pressing the appropriate button. If needed press the “Steps 11-21” button to access the additional steps. Manual Load Application Screen 9. Press the “Master Load” button. This simultaneously applies all of Shutdown the load steps which are in the “On” position. 1 De-energize the load. Trim is achieved by turning the 2. Run the cooling fan for 5 minutes to load steps “On” and “Off” while the assure a thorough cool down of all “Master Load” is in the “On” position. load elements (optional). 10. Adjust source voltage and load. 3. Press the “Control Power Off” button Monitor as needed. on the Main screen. Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-120322.indd • © 2012 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
® STATIONARY LOAD BANK MANUAL • Touchscreen Control • page 8 of 23 NUMERIC LOAD APPLICATION 1. Start-up generator or bring other test source on line. 2. Adjust power source voltage and frequency. 3. Press the “Control Power On” button to energize the cooling fan. “Control Power is On” will be indi- cated and Load Bank status indica- tors will appear. 4. Verify normal operation before proceeding. 5. Visually observe correct fan opera- tion and investigate any unusual fan related noises. Main Screen 6. Check air intake for obstructions and confirm positive air flow. 7. Press the “Numeric Load” button. 8. Press the “Enter KW Value to Apply” button and enter the desired value in the numeric pop-up screen. 9. Press the “Apply Numeric Load” button. 10. Adjust source voltage and load via the apply and remove buttons. Monitor as needed. Shutdown 1 De-energize the load. 2. Run the cooling fan for 5 minutes to assure a thorough cool down of all load elements (optional). Numeric Load Application Screen 3. Press the “Control Power Off” button be disabled. If desired, the customer on the Main screen. may install automatic transfer switch contacts, a manual pushbutton or cir- LOAD DUMP cuit breaker for this use. If this feature This Load Bank contains a Load Dump is used the factory installed jumper at feature which de-energizes all applied TB‘LD’ 1–2 must be removed (See load when customer supplied contacts Installation Procedure). open. Normally closed to run, they The operator also has the option of are rated at 2A @ 24VDC and should bypassing these contacts and enabling be wired to TB‘LD’ 1–2. When these the load section by pressing the “Load contacts open all applied load will be Dump Active Press To Bypass” button de-energized and the load section will on the Setup screen. Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-120322.indd • © 2012 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
® STATIONARY LOAD BANK MANUAL • Touchscreen Control • page 9 of 23 DIAGNOSTIC SCREEN The Diagnostic Screen is accessed via the “Diagnostic” button on the Manual Load Screens and Setup Screen. The intake and exhaust setpoints are factory set but may be modified via the Setup Screen (see Failure Detection section below). FAILURE DETECTION If a failure occurs the corresponding status indicator will be present and the load will be de-energized. Before reapplying a load, the failure must be Diagnostic Screen corrected and the system must be reset by turning the Load Bank “Off” then “On”. This is a permissive/energize-to-run circuit in which all safety sensors must energize their control relays on normal operation before load can be applied. This system will include the following components: 1. Thermocouples into Programmable Logic Controller (PLC) for intake and exhaust 2. Pressure Switch (PS) Thermocouples The thermocouples setpoints have Setup Screen been factory adjusted for precise Load Bank over temperature protection under normal operating conditions. Unusual operating conditions may require field adjustment. The setpoints may be changed via the touch panel. Consult the Simplex Service Department (217- 483-1600 24hrs) before changing the temperature switch setpoint. Do Not allow the Load Bank to operate unattended for extended periods. Metering Screen Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-120322.indd • © 2012 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
® STATIONARY LOAD BANK MANUAL • Touchscreen Control • page 10 of 23 MAINTENANCE EVERY 50 HOURS The Load Bank has been designed OR 6 MONTHS to require minimum maintenance. All Check the tightness of the electrical components have been chosen for a connections. The expansion and con- long, reliable life. Two basic intervals traction caused by Load Bank operation of maintenance are required: each op- may result in loose connections. The eration and every 50 hours or 6 months vibrations caused by the cooling fan (whichever comes first). may also loosen electrical connections. If the Load Bank is transported “over EACH OPERATION the road”, the electrical connections The air intake screens and louvers, should be checked for tightness at a fan and cooling chamber, and exhaust shorter-than-normal time interval. See openings must be checked for any “Primary Inspection”. obstructions or foreign objects. Check fan blades for stress fractures. Due to the high volume of air circulated, paper and other items can be drawn into the air intakes. During Load Bank opera- Overgreasing is a major cause tion insure that air is exiting from the of bearing and/or motor failure. exhaust vent. The amount of grease added The load branches should be checked should be carefully controlled. for blown fuses or opened load resistors. Also make sure dirt and con- To check the fuses or load resistors, taminants are not introduced operate the Load Bank from a balanced when adding grease. 3-phase source and check the three line currents. The three current read- ings should be essentially the same. If a sizeable difference is noted one or more load fuses or load resistors may If motor is nameplated for haz- have malfunctioned. ardous locations, do not run motor without all of the grease or drain plugs installed. If lubrication instructions are shown on the motor nameplate, they will supersede this general instruction. For continued safety and for maximum equipment protec- tion, always replace fuses with one of equal rating only. The bearings which are used on Saturn Load Banks require special installation and relu- brication. See Appendix E - Saturn Bearings for additional information. Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-120322.indd • © 2012 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
® STATIONARY LOAD BANK MANUAL • Touchscreen Control • page 11 of 23 MOTOR RELUBRICATION TIME INTERVAL LUBRICATION for motors with regreasing provisions. Motors are properly NEMA Frame Size lubricated at the time 140 – 180 210 – 360 400 – 510 of manufacture. It is not necessary to lubricate 1800 RPM Over 1800 1800 RPM Over 1800 1800 RPM Over 1800 and less RPM and less RPM and less RPM at the time of installa- tion unless the motor Standard 3 yrs. 8 mo. 2 yrs. 8 mo. 1 yr. 3 mo. has been in storage for a period of 12 months Severe 1 yr. 3 mo. 1 yr. 3 mo. 6 mo. 1 mo. or longer (refer to lubri- Seasonal See Note 2. cation procedure that follows). Standard: Up to 16 hours of operation per day, indoors, 100°F maximum ambient. Inspect the fan motor Severe: Greater than 16 hours of operation per day. Continuous operation under high supplied with your Load ambient temperatures (100° to 150°F) and/or any of the following: dirty, moist loca- tions, high vibration (above NEMA standards), heavy shock loading, or where shaft Bank for grease fittings. extension end is hot. If the motor contains grease fittings you must Seasonal: The motor remains idle for a period of 6 months or more. lubricate the motor. If Note: lubrication instructions 1. For motors nameplated as “belted duty only” divide the above intervals by 3. are shown on the mo- 2. Lubricate at the beginning of the season. Then follow service schedule above. tor nameplate, they will supersede this general instruction. Belt driven cooling fans RELUBRICATION AMOUNTS have bearings which should be lubri- for motors with regreasing provisions. cated. Bearings should be lubricated every 50 hours of operation or 6 months NEMA Volume whichever comes first. Frame Size cu. in. (fluid oz.) Lubrication Procedure 140 .25 (.14) 180 .50 (.28) 1. Stop motor. Disconnect and lock out of service. 210 .75 (.42) 2. Remove contaminants from grease 250 1.00 (.55) inlet area. 280 1.25 (.69) 3. Remove filler and drain plugs. 320 1.50 (.83) 4. Check filler and drain holes for block- 360 1.75 (.97) age and clean as necessary. 400 2.25 (1.2) 5. Add proper type and amount of 440 2.75 (1.5) grease. See the Relubrication Time 500 3.00 (1.7) Intervals table for service schedule and Relubrication Amounts table for volume of grease required. 7. Motor is ready for operation. 6. Wipe off excess grease and replace Warning: If motor is nameplated for filler and drain plugs. hazardous locations, do not run mo- tor without all of the grease or drain plugs installed. Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-120322.indd • © 2012 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
® STATIONARY LOAD BANK MANUAL • Touchscreen Control • page 12 of 23 Grease Type Unless stated otherwise on the motor nameplate, the motors on this Load Bank are pregreased with a polyurea When troubleshooting Load mineral oil NGLI grade 2 type grease. Bank systems always remove Some compatible brands of polyurea all test source power, fan/con- mineral base type grease are: trol power, anti-condensation heater power, etc. • Chevron SRI #2 • Rykon Premium #2 • Exxon Polyrex EM • Texaco Polystar RB If a failure occurs the corre- sponding status indicator will TROUBLESHOOTING be present and the load will be de-energized. Before reapplying This section is designed to aid the a load, the failure must be cor- electrical technician in basic Load Bank rected and the system must be system troubleshooting. All of the prob- reset by turning the Load Bank lems listed can be verified with a basic “Off” then “On”. test meter and/or continuity tester. For safety reasons, when troubleshooting Load Bank systems always remove all COOLING FAILURE test source power, fan/control power, INDICATED anti-condensation heater power, etc. Exhaust temp above EXTS setpoint: COOLING FAN MOTOR WILL 1. Over temperature sensor failure NOT OPERATE 2. Fan failure 1. Inoperative Fan Circuit Breaker 3. Air restriction (intake or exhaust) (FCB) 4. Overvoltage condition present 2. Fan/Control Power not available/ incorrect Exhaust temp below EXTS setpoint: 3. Inoperative Fan Motor (MOT) 1. Restriction of air (intake or exhaust) 4. Fan Motor Contactor (FMC) de-energized 2. Fan pressure switch inoperative 5. Restriction of air (intake or ex- 3. Overtemperature sensor failure haust) Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-120322.indd • © 2012 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
® STATIONARY LOAD BANK MANUAL • Touchscreen Control • page 13 of 23 METERING SYSTEM DOES NOT OPERATE PROPERLY 1. Meter voltage switch failure 2. Improper positioning of meter volt- age selector switch 3. Current transformer or current transformer wiring failure 4. Test meter failure 5. Meter fuses open SOME LOAD STEPS CANNOT BE ENERGIZED 1. Open load step resistor(s) 2. Inoperative load step relays 3. Inoperative load step contactors 4. Open load step fuses DRAWINGS AND PARTS LIST The drawings included in this manual are the most accurate source of part numbers for your Load Bank. When ordering replacement parts for Simplex Load Banks, always consult the Parts Drawing. When contacting the Simplex Service Department always have your work order and drawing number ready for reference. The Load Bank Specifica- tions Sheet in the front of this manual lists all of the drawings included in this manual. The Work Order Number and the Drawing Numbers are also located on each drawing legend. A typical draw- ing legend and parts list is illustrated at right. Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-120322.indd • © 2012 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
® STATIONARY LOAD BANK MANUAL • Touchscreen Control • page 14 of 23 APPENDIX A - ABBREVIATIONS USED IN THIS MANUAL Listed below are abbreviations of terms found on Simplex Load Bank Systems. When following a load bank drawing utilize this guide to define abbreviated system and component names. As this is a master list, draw- ings and text pertaining to your equipment may not contain all these terms. AC-Alternating current GFB-Ground fault breaker OVR-Overvoltage relay-relay used in overvoltage failure sys- AIC-Ampere interrupting GBTR-Ground breaker tripped tem, located on relay sub-panel current-maximum short circuit relay fault current a component can OLR-Overload relay-used for safely interrupt HMI-Operator Interface motor protection AM-Ammeter HVR-High voltage relay OTR-Overtemperature relay- Hz-Hertz-cycles per second, used in failure system AMSW- Ammeter selector switch-selects any phase for measurement of frequency PF-Power factor-in resistive current reading IFCV-Incorrect fan/control voltage only loads expressed as unity (1.0), in inductive loads ex- CF-Control fuse INTS-Intake air temperature pressed as lagging, in capaci- CFM-Cubic feet per minute- switch tive loads expressed as leading used to rate fan air flow ca- K-Relay coil/contact designation PAR-Control power available pacity and load bank cooling KVA-Kilovolt amperes relay-relay energized when requirement control power is available CFR-Cooling failure relay-nor- KVAR-Kilovolt amperes-reactive PFM-Power factor meter mally energized relay in cooling KW-Kilowatts failure subsystem PS-Pressure switch-switch KWM-Kilowatt meter used to detect fan failure CPC-Control power contactor KWT-Kilowatt meter transducer RR-Reset relay CPF-Control power fuse LM-Louver motor RTM-Running time meter- CT-Current transformer- used LMC-Louver motor contactor keeps time log of equipment in metering circuits use. DC-Direct current LR-Load resistive element TB-Terminal block EXTS-Exhaust air temperature LX-Load reactive element TDR-Time delay relay-relay switch L1-Line 1 which times out before contacts FCB-Fan circuit breaker-circuit L2-Line 2 change state breaker in series with fan con- L3-Line 3 TEFC-Totally enclosed, fan trol power cooled-refers to motor enclo- FCVR-Fan control voltage MCB-Main circuit breaker sure relay-normally energized relay MDS-Main Disconnect Switch TEAO-Totally enclosed, air- on relay sub-panel MF-Meter fuse over-refers to motor enclosure FM-Frequency meter-monitors UPS-Uninterruptable power frequency of test source MLB-Main Load Bus source FMC-Fan motor contactor-con- MOT-Motor V-Voltage trols power to fan motor NEMA-National electrical manufacturer’s association VSR-Voltage sensing relay FMSW-Frequency meter switch ODP-Open, drip-proof-refers to XCB-Reactive load controlling FPS-Fan power switch-used to circuit breaker energize cooling system motor enclosure Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-120322.indd • © 2012 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
® STATIONARY LOAD BANK MANUAL • Touchscreen Control • page 15 of 23 APPENDIX B - CALCULATIONS EXAMPLES & FORMULAS Using line voltages and currents: 3 Phase The following calculations are used to determine the actual kilowatt load being Current Readings Voltage Readings applied by the Load Bank, when line A1 = 249A V1-2 = 481V voltages and currents are known (at A2 = 250A V2-3 = 479V 1.0 power factor). A3 = 254A V3-1 = 483V 3 Phase Average Current = A 1 + A2 + A3 1. Read all three line currents and find 3 the average reading. = 249+250+254 2. Read all three line-to-line voltages 3 and find the average reading. 3. Multiply the average current times = 251A the average voltage. 4. Multiply the answer of step #3 times Average Voltage = V1-2 + V2-3 + V3-1 the square root of 3 (1.732). 3 5. Divide the answer of step #4 by 1000. = 481 + 479 + 483 The answer is the actual kilowatts of 3 load being applied by the Load Bank. Single Phase = 481V 1. Determine the line current. Kilowatts = Volts x Amps x 1.732 2. Determine the line-to-line voltage. 1000 3. Multiply the line current times the line-to-line voltage. = 481 x 251 x 1.732 4. Divide the answer of step #3 by 1000. 1000 5. The answer of step #4 is the actual = 209.1KW kilowatts being applied by the load bank. Single Phase Current Reading: 150A Voltage Reading: 240V Kilowatts = Volts x Amps 1000 = 150 x 240 1000 = 36.1KW Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-120322.indd • © 2012 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
® STATIONARY LOAD BANK MANUAL • Touchscreen Control • page 16 of 23 The following calculations are used to determine the amount of current when EXAMPLES the desired amount of kilowatts is ap- plied at 1.0 power factor. When desired amount of kilowatts is applied at 1.0 PF: 3 Phase 3 Phase Applied: 50KW Operating Voltage: 480V 1. Multiply the desired amount of kilo- Amperage = KW x 1000 watts to be applied by 1000. Volts x 1.732 2. Multiply the operating voltage times the square root of 3 (1.732) = 50 x 1000 3. Divide the answer of step #1 by the 480 x 1.732 answer of step #2. = 50,000 4. The answer of step #3 is the average 831.36 line current with the desired kilowatts applied at 1.0 power factor. = 60.1 Single phase 1. Multiply the desired amount of kilo- Single Phase watts to be applied by 1000. Applied: 25KW Operating Voltage: 240V 2. Divide the answer of step #1 by the operating voltage. Amperage = KW x 1000 3. The answer of step #2 is the average Volts line current with the desired amount of kilowatts applied at 1.0 power fac- = 25 x 1000 tor. 240 The following calculations are used to = 25,000 determine a step kilowatt rating at other 240 than a rated voltage. This is accom- plished by referencing the load step to = 104.2 a KW value at a known voltage. 1. Determine the new unrated operating Determining step KW at other than rated voltage: voltage. Applied: 80KW Operating Voltage: 450V 2. Divide the new operating voltage by Rated Voltage: 480V the reference voltage. 3. Square the answer of step #2. Step KW = (Oper. Volt. ÷ Rated Volt.)2 x Applied KW 4. Multiply the answer of step #3 times = (450 ÷ 480)2 x 80 the reference kilowatt value of the load step which the new kilowatt = .93752 x 80 rating is desired. = 70.3 5. The answer of step #4 is the kilowatt rating of the load step at the new voltage. Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-120322.indd • © 2012 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
® STATIONARY LOAD BANK MANUAL • Touchscreen Control • page 17 of 23 FORMULAS Alternating Current Direct Current Kilowatts 1 phase Volts x Amps x PF* Volts x Amps 1000 1000 3 phase 1.732 x Volts x Amps x PF* 1000 *Power Factor, expressed as decimal. (Resistive Load Bank PF is 1.0) Amperes 1 phase KW x 1000 KW x 1000 (KW known) Volts x PF Volts 3 phase KW x 1000 1.732 x Volts x PF KVA 1 phase Volts x Amps 1000 3 phase 1.732 x Volts x Amps 1000 Amperes 1 phase KVA x 1000 (KVA known) Volts 3 phase KVA x 1000 1.732 x Volts KVAR 1 phase Volts x Amps x 1-PF2 1000 3 phase 1.732 x Volts x Amps x 1-PF2 1000 Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-120322.indd • © 2012 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
® STATIONARY LOAD BANK MANUAL • Touchscreen Control • page 18 of 23 APPENDIX C - TORQUE VALUES FAN BLADES CONTACTORS FAN TORQUE See torque values on the front of the contactor. PART NO. BOLT SIZE FT LBS // IN LBS 13820000 SET SCREW 11.7 // 140 ELEMENTS/TRAYS 13820500 SET SCREW 11.7 // 140 TERM/NUT TORQUE 13821000 SET SCREW 8.3 // 100 SIZE INCH LBS 13822000 1/4 — 20 7.5 // 90 #6 Rod ends 4 13823000 1/4 — 20 7.5 // 90 #10 Element Conn. 20 13824000 1/4 — 20 7.5 // 90 1/4-20 High Voltage Contact Simplex 13825100 1/4 — 20 7.5 // 90 13826000 1/4 — 20 7.5 // 90 MAIN LOAD BLOCKS- ALL SIZES 13827500 5/16” 13 // 156 WIRE TORQUE CONNECTION SIZE FT LBS // IN LBS 13827600 5/16” 13 // 156 LOAD SIDE 4-14AWG 2.9 // 35 13828000 3/8” 24 // 288 LINE SIDE 500MCM-4/0 31 // 375 3/0-4/0 20 // 240 MOTORS, BRACKETS, BUS BAR CONNECTIONS 2/0-6AWG 10 // 120 BOLT/NUT TORQUE SIZE GRADE FT LBS // IN LBS 8AWG 3.3 // 40 .250 (1/4-20) Grade 5, dry 8 // 96 .250 (1/4-20) Grade 2, dry 5.5 // 66 CIRCUIT BREAKERS .312 (5/16) Grade 5, dry 17 // 204 WIRE TORQUE STYLE SIZE INCH LBS .312 (5/16) Grade 2, dry 11 // 132 Cutler-Hammer 14-10 AWG 20 .375 (3/8) Grade 5, dry 30 // 360 1-Phase 8 AWG 25 .375 (3/8) Grade 2, dry 20 // 240 6-4 AWG 27 .437 (7/16) Grade 5, dry 50 // 600 3-1/0 AWG 45 .437 (7/16) Grade 2, dry 30 // 360 Merlin Gerin 14-1/0 50 .500 (1/2) Grade 5, dry 75 // 900 3-Phase .500 (1/2) Grade 2, dry 50 // 600 .562 (9/16) & up Grade 5, dry 110 // 1320 .562 (9/16) & up Grade 2, dry 70 // 840 Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-120322.indd • © 2012 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
® STATIONARY LOAD BANK MANUAL • Touchscreen Control • page 19 of 23 APPENDIX C - TORQUE VALUES CONT’D FUSEBLOCKS TAPER-LOCK BUSHINGS MANUF. WIRE TORQUE BUSHING NUMBER TORQUE PART NO. SIZE INCH LBS 1008, 1108 55 IN LBS BM6031SQ, 10-18 AWG 20 1210, 1215, 1310, 1610, 1615 15 FT LBS BM6032SQ, BM6033SQ; 2012 23 FT LBS 600V, 30A 2517, 2525 36 FT LBS T60060-2SR 10-18 AWG 20 3020, 3030 67 FT LBS 600V, 60A 3535 83 FT LBS T60030-3CR, 10-14 AWG 35 600V, 30A 4040 142 FT LBS 8 AWG 40 T60060-3CR, 4545 204 FT LBS 600V, 60A 4-6 AWG 45 60100-3CR, 5050 258 FT LBS 2-3 AWG 50 600V, 100A 6050, 7060, 8065 652 FT LBS 10085, 12010 1142 FT LBS MISCELLANEOUS-TERMINALS, METERS, SWITCH- ES, COILS, RELAYS, XFORMERS CAM-LOK STUDS CONNECTION TORQUE SIZE INCH LBS THREADED MAXIMUM STUD TORQUE 4 5 5/16” – 18 15 FT LBS 6 10 1/2” – 13 40 FT LBS 8 19 10 31 1/4-20” 66 Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-120322.indd • © 2012 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
® STATIONARY LOAD BANK MANUAL • Touchscreen Control • page 20 of 23 APPENDIX D - TYPICAL LIFT EYE INSTALLATION ITEM DESCRIPTION 1/2" 5/8" 3/4" 7/8" A LIFT EYE 15465000 15470000 15471000 15472000 B O-RING 16750500 16750600 16750610 16750620 C FLAT WASHER 20424200 20427000 20427100 20427200 D RUBBER WASHER 20431000 20431001 20431002 20431003 Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-120322.indd • © 2012 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
® STATIONARY LOAD BANK MANUAL • Touchscreen Control • page 21 of 23 APPENDIX E - SATURN BEARINGS These instructions pertain to the bearings used on Saturn Load Banks. See Parts Legend Drawing for the specific bearing used for your unit. It is important that these instructions are read in their entirety before attempting installation and removal. The procedures indicated should be carefully followed. Failure to do so can result in improper installation which could cause bearing performance problems as well as serious personal injury. Bearings In Bolt-On Housings (Units) 6. Monitor Installed Bearing* - After bearing has been run for several 1. Check Area - Clean and organize minutes, and again after several bearing installation area, keep well hours, check bearing for excessive lighted. Be sure mounting surfaces noise or vibration. Shutdown ma- are clean and flat. chine and check housing tempera- 2. Check Shaft - Shaft should be within ture: typical applications operate at tolerance range shown in Table #1, 100°F – 150°F (38°C –66°C) (Similar clean and free of nicks and burrs. feel to household hot tap water tem- Mount bearing on unused section perature). Tighten all locking devices of shaft or repair/replace shafting as after 500 hours or 3 months, which required. ever comes first. 3. Install Unit - Slide unit onto shaft. If it TABLE #1 - SHAFTING is difficult to mount bearing on shaft, use a piece of emery cloth to reduce Shaft Diameter Shaft Tolerance any high spots on the shaft. Do not hammer on any component of the 2–3 3/16 in. +0 to -0.0010 in. bearing. (50–80 mm) (+0 to -.25 mm) 4. Fasten Unit In Place - Install hous- ing mounting bolts, check and align TABLE #2 - SKWEZLOC® COLLAR TIGHTENING bearing and tighten mounting bolts to recommended fastener torques. English Screw Hex Torque Exercising extreme caution and Size Size (in-lbs.) (N-m) safety, rotate shaft slowly to center #8-32 T-25 65 – 70 7–8 bearing. #10-24 T-27 90 – 100 10 – 11 5. Skwezloc Inserts 1/4-20 T-30 220 – 240 25 – 27 a) Be sure that the Skwezloc® collar is fitted square and snug against 5/16-18 T-45 450 – 495 51 – 56 the shoulder on the inner ring. b) Torque the Skwezloc® collar cap screw to torque recommended in Table #2. Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-120322.indd • © 2012 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
® STATIONARY LOAD BANK MANUAL • Touchscreen Control • page 22 of 23 APPENDIX E - SATURN BEARINGS CONT’D Relubrication Instructions TABLE #3 - LUBRICATION SCHEDULE FOR SEALMAS- TER® GOLDPLEX™-HP Sealmaster® GoldPlex™-HP has been developed based on the performance Contamination Level - Clean to Light characteristics of Sealmaster® brand bearings. Sealmaster® brand bearings Bearing Temperature 500 RPM to 1000 RPM are factory filled with GoldPlex™-HP -50°F to -30°F 12-24 Months and do not need to be greased upon initial installation. GoldPlex™-HP -30°F to 120°F 12-24 Months lithium complex base, petroleum oil, 120°F to 180°F 6-12 Months NLGI grade 2 consistency. If not using GoldPlex™-HP grease, Table #3 is 180°F to 250°F 3-6 Months given as a very general recommenda- Contamination Level - Medium tion for typical lithium or lithium complex, petroleum oil, NLGI#2 greases. Contact Bearing Temperature 500 RPM to 1000 RPM the grease supplier for a more specific -50°F to 120°F 1 Week - 1 Month lubrication schedule. 120°F to 250°F Daily - 2 Weeks Relubricatable SealMaster® brand bear- ings are supplied with grease fittings or Contamination Level - Heavy zerks for ease of lubrication with hand Bearing Temperature 500 RPM to 1000 RPM or automatic grease guns. Always wipe the fitting and grease nozzle clean. For -50°F to 250°F Daily - 2 Weeks safety stop rotating equipment. Add one half the recommended amount shown TABLE #4 - RECOMMENDED RELUBRICATION in Table #4. Start bearing, and run a GREASE CHARGE few minutes. Stop bearing and add the second half of the recommended Shaft Size (in.) Oz. Shaft Size Grams amount. A temperature rise, sometimes 30°F, after relubrication is normal. Bear- 2 to 2 7/16 0.30 55-60 8.51 ing temperatures should not exceed 250°F (121°C). For any applications Compatibility of grease is critical, that are not in the ranges of the table, therefore, if not using Sealmaster® contact Sealmaster® for suffix modified GoldPlex™-HP, consult your grease bearings that can handle temperatures supplier to ensure compatibility. up to 400°F (204°C). GoldPlex™-HP is a lithium complex Note: The tables on this page state base grease, petroleum oil, NLGI grade general lubrication recommendations 2 consistency. based on our experience and are in- tended as suggested or starting points only. For best results, specific applica- tions should be monitored regularly and lubrication intervals and amounts adjusted accordingly. Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-120322.indd • © 2012 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
® STATIONARY LOAD BANK MANUAL • Touchscreen Control • page 23 of 23 APPENDIX E - SATURN BEARINGS CONT’D Application Assistance: Please contact Application Engineering at: Phone: (219) 465-2211 Fax: (219) 465-2263 Email: sealmaster.engineering@emerson-ept.com Sealmaster® brand ball bearings now incorporate a unique, color-coding system to help identify the type of grease in the bearings. Each relubricatable Sealmaster® brand bearing features colored fitting cap to help indicate the type of grease used in the individual bearings. Below is a list of the colored fitting caps and the type of grease they represent. Yellow - Yellow grease fitting caps indicate that bearings are filled with Sealmaster ® GoldPlex™-HP high performance mounted bearing grease. Red - Red grease fitting caps indicate that bearings are filled with factory standard high-temperature grease. (Lithium complex base with synthetic hydrocarbon oil) White - White grease fitting caps indicate that bearings are filled with factory stan- dard good grade grease. (Aluminum complex with synthetic oil) Black - Black grease fitting caps indicate that bearings are filled with a non-standard grease. Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-120322.indd • © 2012 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
STATIONARY LOAD BANK MANUAL • Touchscreen Control • Addendum AUTOMATIC LOAD APPLICATION Warning: When Load Bank is in Au- tomatic Mode the fan may start and stop without notice. 1. Start-up generator or bring other test source on line. 2. Adjust power source voltage and frequency. 3. Press the “Automatic Load” button. 4. Press the “Automatic Setup” button to open the Automatic Load Application Setup screen. 5. Enter the desired values and press the “Back” button. Automatic Load Application Screen 6. Press the “Start” button to initiate automatic operation. When Load Bank is in Auto- matic Mode the fan may start and stop without notice. Automatic Setup Screen Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 LBS-TS-110119.indd • © 2011 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
You can also read