Selecting Current Transformers
←
→
Page content transcription
If your browser does not render page correctly, please read the page content below
Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E. Introduction: • A secondary winding around the As engineers, we are aware that electrical power core systems have grown. How much have they • Insulating material grown? When was the last time you specified a When current travels through a current 2400-volt system, a 4160-volt 250 MVA system, caring device, such as a cable or bus duct it a 15 kV 500 MVA system or specified a 2000- develops a magnetic field at right angles to amp 480-volt system? An industrial plant now the flow of current. The strength of the requires a larger and more complex system than magnetic field varies as the current magitude was required just a few years ago. The 2400-volt changes during all operating conditions. As systems have all but disappeared; 4160-volt learned in transformer theory, when a systems have expanded from 350 MVA to 63 kA magnetic field strikes a wire, it will cause a (equivalent to 500 MVA). The 15 kV systems current to flow in the wire. By using the also have expanded to 63 kA (equivalent to 1500 strength of the magnetic field and knowing MVA). Has all of the electrical system the turns ratio, we can obtain a value of expanded? current that is useable for meters, relays and other current sensing device. In order to monitor and to protect the power system we must measure the energy flow. To In order to scale a value of high current connect a meter, relay or other current sensing flowing in a conductor, the engineer needs device in series with a large current source to introduce a specific number of would be impractical. The industry has a device uniformally distributed turns of wire around that has been around for a long time and will the core to scale down the system current. allow the engineer to monitor the electrical This will ensure that the output current is power system. The current transformer is an always proportional to the current flowing in engineer’s main measuring device to determine the conductor. The current-caring conductor current flow in a power system. Engineers tend is referred to as the primary or H1 and the to think of a current transformer as an ideal ends of the wire surrounding the core are device; however, it is ideal only up to a point. referred to as the secondary or X1 and X2 for single winding current transformer. Ideal Current Transformer Remember, on multi-ratio current An ideal current transformer would transformers there are several secondary proportionally scale down the value of the power outputs. system current to a useable known value. Second, the scale-down output should faithfully The current transformer can provide a reproduce the power system current waveform. constant current or voltage output. This An ideal current transformer should perform paper will cover only current transformers these two tasks over the range of a few amps up that provide a current output. through tens of thousands amps. The ideal current transformer should be able to meet these In the past, there were two main values of requirements. In reality, a current transformer secondary current typically used in has limitations. measuring current. In the United States, engineers typically use a 5-amp output. Today’s current transformer hasn’t changed Other countries have adopted a 1-amp since it was developed more than 80 year ago. A output. With the advent of microprocessor current transformer consists of the following meters and relays, the industry is seeing the components: 5-amp or 1-amp secondary being replaced • A laminated steel core with a mA secondary. Typically, devices
Selecting Current Transformers Part 1 with mA output are called “current sensors,” as opposed to current transformers. Type of Current Transformers Current transformers are available in several different styles. Engineers can choose from the following: • Bushing type, Window or Donut • Wound type • Bar type By far, the most common one is the wound type current transformer. The wound type provides excellent performance under a wide operating range. Typically, the wound type is insulated to Typical Bar Type Current Transformer only 600 volts. The bushing type is typically used around the bushing on circuit breakers and Bar type current transformers are insulated transformers and may not have a hard protective for the operating voltage of the system. outside cover. Bar types are available with higher insulation levels and are usually bolted to Current transformers are applied in two very the current caring device. different functions, metering and/or protection. Metering Accuracy The accuracy class of a current transformer is expressed as the percent error for a known burden, current and power factor. ANSI C57.13-1993 Table 11 defines the standard burdens for current transformers with 5-amp secondary. The standard percent error expressed in Table 11 are 0.3, 0.6, and 1.2, and the standard metering burdens are 0.1, 0.2, 0.5, 0.9 and 1.8 ohms at 60 Hz, 90% power factor lagging. In order to study the Typical Donut Type Current Transformer full range of normal operation, engineers should determine the accuracy at 10% and Donut type current transformers are typically 100% load conditions. insulated for 600 volts. To ensure accuracy, the conductor should be positioned in the center of As an example, a current transformer with a the current transformer opening. meter accuracy of 0.6B0.5 would indicate a standard burden of 0.5 ohms and a load power factor between 0.6 and 1.0. First, at 100% primary current the error in the meter reading due to the current transformer will be less than +/- 0.6%. Second, at 10% primary current the error in the meter reading due to the current transformer will GE Consumer & Industrial May 2008 Specification Engineer Series
Selecting Current Transformers Part 1 be less than +/- 1.2%. The code allows the error be considered a standard accuracy current at 10% primary current to be no more than twice transformer. Another selection might be a the error at 100% primary current. GE ITI 785-301 300:5 current transformers is rated as a C100. This current transformer Relay Accuracy has a core thickness of about 6.5 inches. In a For relay classification engineers rely on the switchgear application, one could install two secondary terminal voltage, which the current 780-301 300:5 on each phase of the transformer can maintain at 20 times rated switchgear; although, only one 785-301 secondary current without exceeding 10% ratio 300:5 current transformer could be installed correction. For a 5-amp current transformer on each phase. secondary, that would be 100-amps. ANSI C57.13-1993 offers the following standard Many times when engineers read a terminal voltage ratings as 10, 20, 50, 100, 200, specification that requires a 100:5 current 400, and 800 volts. ANSI C57.13 only indicated transformer and states, “all current the current transformer is capable of supplying transformers shall have a minimum of C200 the value indicated. A current transformer with a rating,” they are puzzled as how to proceed. 50-volt rating will supply at least 50 volts but is When the specification requires a supplier to not capable of supplying 100 volts. It may very furnish one set of current transformers for well be able to supply 95 volts. Always calculate each of the functions shown below, it may the actual voltage capability for the current not be possible to provide C200 rated transformer in use. current transformers for each function: • Transformers differential In addition to voltage classification, ANSI • Bus differential C57.13 assigns a letter to precede the voltage • Phase over current protection classification. It uses a “C” or “T” to define the • Metering manner in which the rating is established. When the leakage reactance is low and does not have Burden an appreciable effect on the ratio the standard The burden can be expressed in two ways. assigns a “C” for calculated value. Bar-type and The burden can be expressed as the total window-type current transformers, which impedance in ohms of the circuit or the total typically have fully distributed windings, are a volt-amperes and power factor at a specified good example of these types of current value of current or voltage and frequency. transformers. The engineer can convert a volt-amperes value to total impedance in ohms by When the leakage reactance has an appreciable dividing the volt-amperes by the square of effect on the ratio, the standard assigns a “T”. the secondary amperes. A typical calculation The accuracy of these current transformers can would be to convert 50 volt-amperes to total only be determined by testing. Typically, wound- impedance in ohms. Dividing 50 volt- primary current transformers which have non- amperes by 52 (25) would be an impedance distributed windings fit in this category. of 2 ohms. The ability of a current transformer to produce To determine the total impedance, both the necessary voltage classification is directly active and reactive, one must sum the determined by the current transformer ratio. A burden of the individual devices connected GE ITI 780-301 300:5 current transformer is to the current transformer. The individual rated as a C20. This current transformer has a devices may only be the current transformer, core thickness of just over three inches. It would a short run of wire and a meter. In contrast, GE Consumer & Industrial May 2008 Specification Engineer Series
Selecting Current Transformers Part 1 the circuit may have the current transformer, a algorithms the microprocessor relay have a lone run of wiring, a relay, a meter, an auxiliary very small burden. In addition, the burden current transformer and a transducer. While the does not vary with relay tap setting. latter configuration would not be used today, one may be required to make this calculation on an In order to determine the correct current existing system. All manufacturers can supply transformer for the application, the engineer the burden of their individual devices. must sum the impedances of all the devices connected in series with the current Although not used very often these days, transformer. Engineering studies have induction disk over-current devices always gave shown that a sufficiently accurate value can the burden for the minimum tap setting. To be obtained by adding the individual device determine the impedance of the actual tap setting impedances arithmetically, which allows for being used, first square the ratio of minimum the power factor to be ignored. If using divide by the actual tap setting used and, second these procedures yields a borderline result, it multiply this value by the minimum impedance. is recommended that application be avoided. A GE IFC 51 time over-current relay (50/51 device) has an impedance of 1.47 + 5.34j at the The resistance of the terminal connection 1-amp tap. To apply the relay at the 4-amp tap may be neglected in calculating burden. In the engineer would multiply the impedance at the applications where the wiring is confined to 1-amp tap setting by (1/4)2. The impedance at the inside of a switchgear cubical, the the 4-amp tap would be 0.0919 + 0.3338j or engineer may neglect lead resistances. 0.3462 Z at 96.4 power factor. However, on long switchgear lineups applying bus differential and application Compare the GE IFC 51 over-current relay, involving outdoor switchgear lead length which has only two functions with the GE SR- (lead resistance) should not be neglected. 750 Feeder Protection Relay with 16 current related functions. The SR750 relay has a burden Unless a study involves the use of the of only 0.20 VA at 5-amp input. The SR750 current transformer excitation curve, it is burden of 0.008 ohms is 43.3 times lower than acceptable to delete the current transformer the 0.3462 for the two function GE IFC51 relay. internal resistance. The use of ANSI accuracy rating has already factored in the Side Bar Note internal resistance of the current The modern microprocessor relay takes the transformer. analog waveform from the current transformer and digitalizes the data before processing. To Auxiliary Current Transformers: compensate for current transformer saturation the Because of the advent of microprocessor microprocessor relays utilized many algorithms relays and meters, the use of auxiliary to identify a saturation condition. Few power current transformers may not be needed. In engineers are familiar with terms like Discrete the event an auxiliary current transformer is Fourier transform, cosine filters, Digital Signal required, the lowest ampere-rated auxiliary Processing, Finite Impulse Response, and current transformer that meets the circuit MIMIC filters, just to name a few. These terms thermal requirement should be selected. By are used to explain the operation of the selecting the lowest ampere rating, a smaller microprocessor relay under saturated current wire can be applied, thereby allowing many transformer conditions. Because the more turns to occupy the same space. This microprocessor digitalizes the input current will result in a higher output voltage before signal, and employees a host of filters and the current transformer becomes saturated. GE Consumer & Industrial May 2008 Specification Engineer Series
Selecting Current Transformers Part 1 To illustrate this point, when the main current from a manufactures would be GE ITI 780- transformer is over sized and a 2-to-1 step-up of 302, 3000:5, C200, 1.105 ohms at 75 deg C. current is required, the auxiliary current transformer should be rated 2.5 to 5 amps. This Using the ANSI accuracy classification is different than the 5:10 amps one would expect. assigned to a current transformer alone with The use of auxiliary current transformers should the circuit burden impedance will offer an be studied completely before applying in the approximate check on the selection of a secondary of a current transformer. current transformer. This is due to the fact that the ANSI accuracy classification is Relay Accuracy Calculation based on a single current value. The Engineers are required to demonstrate the standard has selected 20 times secondary suitability of their system in order to provide current (100 amps for a 5 amp secondary) personal and equipment safety. When it comes to with standard burdens. The following steps relay accuracy calculation, three avenues are will outline a systematic approach to offered. As an engineer involved only with validate the current transformer selection. industrial power systems, I am not familiar with “T” rated current transformer application; ANSI Accuracy Classification Step 1 therefore, my discussion will be limited to “C” Use the maximum short circuit current rated current transformers. available from the short circuit study as a starting point. Depending on the type of One method, which utilizes over-current ratio- grounding, the ground fault current may be correction curves, applies only to “T” rated different than the phase-to-phase short current transformers. Should additional circuit current. In most cases, knowledge of information on this subject be required, please the instantaneous and time over-current contact the local GE sales office for a list of values is required. names and telephone numbers. ANSI Accuracy Classification Step 2 The remaining two methods are as follows. One Determine the impedance of all devices method will involve the comparison of current connected in the current transformer circuit transformer accuracy rating with the secondary at the ideal current transformer value. The terminal voltages the current transformer can ideal secondary current is the primary produce under all expected operating conditions. current divided by the current transformer Another method available to the engineering ratio. In older induction disk relays, the community requires the current transformer impedances of the instantaneous and time secondary excitation curves to calculate the over-current function will be different. actual ratio correction the current transformer Typically, on older induction disk relays the will experience for a given condition. The first calculation should be preformed for function that must be performed in any of the instantaneous, time over-current and ground methods is to determine the total burden on the fault settings. As described earlier, current transformer. The total ohmic burden must microprocessor relays have a single include all relays, meters, transducers and wiring impedance value, which applies over the resistance, when appropriate. complete range of operation. This greatly simplifies the number of calculations Using ANSI Accuracy Classification required to verify the suitability of the The current transformer manufactures will current transformer in question. supply the burden impedance, the ANSI accuracy classification and ratio. Typically, data ANSI Accuracy Classification Step 3 GE Consumer & Industrial May 2008 Specification Engineer Series
Selecting Current Transformers Part 1 Utilize the ANSI classification assigned to the Typical Secondary Excitation Curve current transformer. These data are available The secondary-excitation curve shown is for from the current transformer manufacturer. a 600:5, C200 current transformer. ANSI Accuracy Classification Step 4 Secondary-excitation curves are available Depending on the type of relay selected the from the current transformer manufacturer. process will involve one or more calculations. First, determine the total burden impedance (Zb) Using this method will require the engineer for the current transformer secondary circuit. to obtain the actual burden impedance and Second, calculate the current transformer actual primary current magnitude that the secondary voltage (V’t). current transformer will measure. As a V’t = (Ip/N) * Zb result, this method is more complex than Ip = Primary current applying the ANSI classification for a single N = Current transformer turn ratio fixed current magnitude. This method can Zb = Total burden impedance indicate a current transformer is suitable for Finally, compare V’t to the current transformer the application when the ANSI classification rating. If the voltage rating is greater than or method demonstrated it was not suitable. equal to the calculated secondary voltage, the Follow the four-step method to apply the current transformer is acceptable for the secondary excitation curve calculations. application. If V’t is greater than the ANSI classification, additional calculations should be Step 1: Secondary-excitation performed before rejecting the current Ascertain the maximum primary fault transformer. current for the system under investigation. In the absence of a completed short circuit Using Excitation Curves study, a quick method to obtain a system’s Engineers have another method to determine the short circuit is to sum the transformer full suitability of a selected current transformer, load amps divided by the transformer which method requires the use of the current impedance (transformer contribution), plus transformer excitation curve. The method the transformer full load amps divided by provides a more accurate assessment of the .017 (motor contribution). This will performance by calculating the actual secondary represent the maximum expected short current for given primary current and burden circuit value for that system. Using this impedance. As stated earlier, this method method will provide a more realistic short applies only to “C” classified current circuit value as opposed to using the transformer. equipment bracing value. Step 2: Secondary-excitation After determining all the devices that will be connected in series with the current transformer, obtain the impedance for each device and then total the impedance for this circuit. Step 3: Secondary-excitation From the current transformer manufacturer, secure the secondary excitation curve and secondary winding resistance. GE Consumer & Industrial May 2008 Specification Engineer Series
Selecting Current Transformers Part 1 American National Standards Institute, Step 4: Secondary-excitation “Requirement For Instrument Use the conditions identified in Step 1 to Transformers”, ANSI C57.13-1999 determine the current transformer ratio correction using the steps below: Louis Powell, “Current Transformer Burden and Saturation”, IEEE–IAS Publication Vol 4.a Calculate the total burden impedance Zt 1A-15, No. 3 seen by the current transformer. Dave West, “Current Transformer 4.b Determine the primary current measured Application Guide”, I&CPS Conference by current transformer, which is labeled as Is. Record, 1977 First, in order to proceed with the calculation a value for Ie must be assumed. A good starting W.J. Smolinski, “Design Consideration In point would be to assume Ie is equal to zero. The Application Of Current Transformers Based on Ie equals zero, the equation Is = Ip/N For Protective Relaying Purposes”, IEEE becomes valid. Power Engineering Society Paper T 73 036- 1 4.c Use the equation Es = Is * Zt to calculate the current transformer secondary voltage DW Houghtaling, “Power/Vac Metalclad Switchgear Current Transformer 4.d Use the value for Es and the secondary Application Guide”, General Electric excitation curve to identify a value for Ie. Company 4.e Calculate the percent excitation current General Electric Company, “Instrument using the equations %Ie = (Ie/Is) * 100. Transformer Accuracy Standards”, Somersworth, NH, 1971 GEC-1526B If the percentage of Ie is negligible the assumption of Ie = 0 in step 4.b is acceptable. General Electric Company, “Instrument Transformer Basic Technical Information Should the calculated value prove not to be And Application”, Somersworth, NH, 1961 negligible, return to 4.b and select another value GET-6544 for Ie and follow the same procedure again. General Electric Company, “Instrument Summary Transformer Burden Data”, Somersworth, This paper has offered a window into the NH, 1961, GET1725D complexity of selecting the correct current transformer for the application. It will provide a basis to go deeper into the selection procedure. The following references list many publications that can be used to broaden one’s knowledge. The following papers explore in greater details the art of selecting the correct current transformers. Reference: GE Consumer & Industrial May 2008 Specification Engineer Series
You can also read