Model YR Twin-Screw Compressor Liquid Chillers Design Level C - ASHRAE 90.1

Page created by Matthew Rogers
 
CONTINUE READING
FORM 160.81-EG2 (511)

Model YR Twin-Screw Compressor Liquid Chillers
               Design Level C

              200 through 430 tons (60 Hz)
              700 through 1500 kW (50 Hz)         ASHRAE
              170 through 365 tons (50 Hz)          90.1
              600 through 1280 kW (50 Hz)        COMPLIANT
                   Utilizing HFC-134a
FORM 160.81-EG2 (511)

Table of Contents
Contents
FORM 160.81-EG2 (511)........................................................................................................................................................................................ 1
Introduction............................................................................................................................................................................................................ 3
Ratings................................................................................................................................................................................................................... 4
OptiView Control Center....................................................................................................................................................................................... 5
Mechanical Specifications.................................................................................................................................................................................. 12
Accessories and Modifications.......................................................................................................................................................................... 17
SI Metric Conversion........................................................................................................................................................................................... 19
Application Data.................................................................................................................................................................................................. 20
Unit Components................................................................................................................................................................................................. 26
Dimensions.......................................................................................................................................................................................................... 28
Dimensions (Ft.-In.) – Nozzle Arrangements.................................................................................................................................................... 30
Dimensions (mm) – Nozzle Arrangements........................................................................................................................................................ 36
Dimensions (inches) – Floor Layout.................................................................................................................................................................. 42
Dimensions (mm) – Floor Layout....................................................................................................................................................................... 43
Weights................................................................................................................................................................................................................. 45
Guide Specifications........................................................................................................................................................................................... 47

                                                                                    NOMENCLATURE

                                             The model number denotes the following characteristics of the unit:

                                                           YR             TD             TD             T0            –            46            C           S

Model                                                                                                                                                                                      Special Features
                                                                                                                                                                                           (optional)

        Evaporator Code                                                                                                                                                                     Design Level

                Condenser Code                                                                                                                                                    Motor Code

                          Compressor Code                                                                                                                            Power Supply:
                                                                                                                                                                      – for 60 Hz
                                                                                                                                                                      5 for 50 Hz

2                                                                                                                                                                                    JOHNSON CONTROLS
FORM 160.81-EG2 (511)

Introduction
The YORK MaxE™ YR Chiller offers a complete combina-            HIGH‑EFFICIENCY HEAT EXCHANGERS
tion of features for total owner satisfaction.
                                                                MaxE chiller heat exchangers offer the latest tech­nology
                                                                in heat transfer surface design to give you maxi­mum
MATCHED COMPONENTS MAXIMIZE EFFICIENCY
                                                                efficiency and compact design. Waterside and refriger-
Actual chiller efficiency cannot be determined by ana­lyzing    ant‑side design enhancements minimize both energy
the theoretical efficiency of any one chiller com­ponent.       consumption and tube fouling. The “skip-fin” design at all
It requires a specific combination of heat exchanger,           intermediate tube supports provides maximum tube wall
compressor, and motor performance to achieve the op-            thickness at the support area to extend tube life.
timized system performance (IPLV/NPLV). YORK MaxE
chiller technology matches chiller system components to         FACTORY PACKAGING REDUCES FIELD LABOR
provide maximum chiller efficiency under actual – not just      COSTS
theoretical – operating conditions.
                                                                YORK MaxE screw chillers are designed to keep in-
                                                                stallation costs low. Where installation access is not a
REAL-WORLD ENERGY PERFORMANCE                                   problem, the unit can be shipped completely packaged,
                                                                requiring minimal piping and wiring to complete the
“Real-World Energy” illustrates the energy-saving poten-
                                                                installation.
tial of focusing on chiller performance during off-design
conditions. Off-design is not only part-load, but full-load
                                                                For those units utilizing a factory installed Solid‑State
operation as well, with reduced entering condenser water
                                                                Starter, the three power leads pro­vide all power to the
temperatures (ECWTs). This is where chillers operate 99%
                                                                chiller and its auxiliaries.
of the time, and where operating costs add up.
                                                                TAKE ADVANTAGE OF COLDER COOLING TOWER
The YR MaxE chillers are the only screw chillers designed
                                                                WATER TEMPERATURES
to operate on a continuous basis with reduced ECWT and
full condenser flow at all load points, taking full advantage   YORK MaxE screw chillers are de­signed to take full
of Real-World weather conditions. This type of operation        advantage of colder cooling tower water temperatures,
benefits the cooling tower as well; reducing cycling of the     which are naturally available dur­ing most operating hours.
fan motor and ensuring good coverage of the cooling fill.       Considerable energy savings are available by letting tower
                                                                water temperature drop, rather than artificially holding it
YORK MaxE chillers offer the most efficient Real-World          above 75°F (23.9°C), especially at low load, as some
operation of any chiller, meaning lower operating costs         chillers require.
and an excellent return on your chiller investment.
                                                                THIRD PARTY ACCEPTANCE – YOUR ASSURANCE
HIGH-EFFICIENCY OIL SEPARATOR                                   OF RELIABILITY
MaxE YR Screw Chillers utilize high-efficiency oil sepa-        YORK MaxE screw chillers are approved for listing by
ration, limiting oil carry-over to less than 500 ppm. Oil is    Underwriter’s Laboratories for the United States and
vital in screw compressors for lubrication, rotor sealing       Canada. CE certification required for European Union,
and cooling. However, oil in the evaporator can lead to         and SELO for mainland China requirements. Recogni-
reduced heat transfer and reduced system performance.           tion of safety and reliability is your assurance of trouble‑
The high-efficiency oil separator keeps the oil in the lube     free performance in day‑to­-day building operation.
circuit and maximizes heat transfer efficiency.

JOHNSON CONTROLS                                                                                                          3
FORM 160.81-EG2 (511)

Ratings
                               Rated in accordance with         pass arrangement. Computerized ratings are available
                               the latest issue of AHRI         through each Johnson Controls sales office. These ratings
                               Standard 550/590.                can be tailored to specific job requirements, and are part
                                                                of the ARI Certification Program.

                                                                OFF-DESIGN PERFORMANCE
AHRI CERTIFICATION PROGRAM                                      Since the vast majority of its operating hours are spent
                                                                at off‑design conditions, a chiller should be chosen not
The performance of YORK MaxE chillers is certified to
                                                                only to meet the full‑load design, but also for its ability to
the Air Conditioning, Heating, and Refrigeration Insti­tute
                                                                perform efficiently at lower loads and lower tower water
(ARI) complying with the certification sections of the latest
                                                                temperatures. It is not uncommon for chillers with the
issue of AHRI Standard 550/590. Under this Certifi­cation
                                                                same full‑load kW/TON to have an operating cost differ-
Program, chillers are regularly tested in strict compli-
                                                                ence of over 10% due to part‑load operation.
ance with this Standard. This provides an inde­pendent,
third‑party verification of chiller performance.                Part‑load information can be easily and accurately gener-
YORK YR screw chillers are designed to comply with              ated by computer. And because it is so important to an
ASHRAE Standard 90.1-2004 (and earlier editions). The           owner’s operating budget, this informa­tion is now standard
superior part-load performance of the YORK YR chillers          within the AHRI Certifi­cation Program in the form of an
far exceeds the IPLV/NPLV requirements of ASHRAE                Integrated Part‑Load Value (IPLV), and Non-Standard
90.1, providing superior Real World Energy savings for          Part‑Load Value (NPLV).
efficiency conscious owners.
                                                                The IPLV / NPLV formulas from AHRI Standard 550/590
COMPUTERIZED PERFORMANCE RATINGS                                closely track chiller operations, and provide a more ac-
                                                                curate indication of chiller performance than the previ-
Each chiller is custom‑matched to meet the individual           ous IPLV / APLV formula. A more detailed analysis must
building load and energy requirements. A large number           take into account actual build­ing load profiles, and local
of standard heat exchangers and pass arrangements are           weather data. Part‑load performance data should be ob-
available to provide the best possible match.                   tained for each job using its own design criteria.
It is not practical to provide tabulated performance for each
combination, as the energy requirements at both full- and
part‑load vary significantly with each heat exchanger and

4                                                                                                  JOHNSON CONTROLS
FORM 160.81-EG2 (511)

OptiView Control Center

OPTIVIEW CONTROL CENTER                                        During the Start Sequence and System Lockout Delay, the
                                                               system status will include a countdown timer indicating the
The YORK OptiView Graphic Display Control Center,
                                                               time remaining. The control panel is compatible with the
furnished as standard on each chiller, provides the ul-
                                                               YORK Solid State Starter (optional), Electro-mechanical
timate in efficiency, monitoring, data recording, chiller
                                                               (E-M) starter, or any customer supplied E-M starter that
protection and operating ease. The control center is a
                                                               complies with the Johnson Controls R-1131 standard.
factory-mounted, wired and tested state-of-the-art mi-
                                                               The locations of various chiller parameters are clearly
croprocessor based control system for R-134a screw
                                                               marked and instructions for specific operations are pro-
chillers. The panel is configured with a 10.4 inch diagonal
                                                               vided. The panel verbiage is available in other languages
color Liquid Crystal Display (LCD) surrounded by “soft”
                                                               as an option, with English always available. Data can be
keys, which are redefined with one keystroke based on
                                                               displayed in either English or Metric units, plus keypad
the screen display at that time. The display is rated at
                                                               entry setpoints of 0.1 increments.
450 nits. This revolutionary development makes chiller
operation quicker and easier than ever before. Instead
                                                               Security access is provided to prevent unauthorized change
of requiring keystroke after keystroke to hunt for informa-
                                                               of setpoints. This is accomplished with three different
tion on a small monochrome LCD screen, a single button
                                                               levels of access and passwords for each level. There are
reveals a wide array of information on a large, full-color
                                                               screens, displayed values, programmable setpoints and
illustration of the appropriate component, which makes
                                                               manual controls only available with service level access
performance and operation easier to monitor. This is all
                                                               to the chiller. They are only displayed when logged in at
mounted in the middle of a keypad interface and installed
                                                               the service access level. The Advanced Diagnostics and
in a locked enclosure.
                                                               troubleshooting information for the chiller and the panel is
                                                               also included at this access level.
The LCD display allows graphic animated display of the
chiller, chiller sub-systems and system parameters; this
                                                               The panel is fused through a 1-1/2 KVA transformer in the
allows the presentation of several operating parameters
                                                               compressor motor starter to provide individual over-cur-
at once. In addition, the operator may view a graphical
                                                               rent protected power for all controls. Numbered terminal
representation of the historical operation of the chiller as
                                                               strips for wiring such as Remote Start/Stop, Flow Switch,
well as the present operation. A Status Bar is displayed
                                                               Chilled Water Pump and Local or Remote Cycling Device
at all times on all screens. It contains the System -
                                                               are provided. The Panel also provides field interlocks that
Status Line and Details Line, the Control Source, Access
                                                               indicate the chiller status. These contacts include a Remote
Level, Date and Time.
                                                               Mode Ready To Start, a Cycling Shutdown, a Safety Shut-

JOHNSON CONTROLS                                                                                                         5
FORM 160.81-EG2 (511)

OptiView Control Center
down and a chiller Run Contact. Pressure transducers           Display Only:
sense system pressures and thermistors sense system             • Chilled Liquid Temperature – Leaving
temperatures. The output of each transducer is a DC volt-
                                                                • Chilled Liquid Temperature – Return
age that is analogous to the pressure input. The output of
each thermistor is a DC voltage that is analogous to the        • Condenser Liquid Temperature – Return
temperature it is sensing.                                      • Condenser Liquid Temperature – Leaving
                                                                • Motor Run (LED)
Setpoints can be changed from a remote location via
                                                                • % Full-load Amps
0-10VDC, 4-20mA, contact closures or through serial
communications. The adjustable remote reset range [up           • Operating Hours
to 20°F (11.1°C)] provides flexible, efficient use of remote
signal depending on reset needs. Serial data interface         With the “soft” keys the operator is only one touch away
to the YORK ISN Building Automation System (BAS) is            from the 8 main screens that allow access to the major
through the micro gateway, which can be mounted inside         information and components of the chiller. The 8 screens
the Control Center.                                            are the SYSTEM, EVAPORATOR, CONDENSER, COM-
                                                               PRESSOR, OIL SEPARATOR, MOTOR, SETPOINTS,
This printed circuit board requests the required data from     and the HISTORY. Also on the Home Screen is the ability
the Micro Board and makes it available for the YORK            to Log IN, Log OUT and Print. Log In and Log Out is the
ISN network. This optional board is available through the      means by which different security levels are accessed.
Johnson Controls BAS group. The operating program
is stored in non-volatile memory (EPROM) to eliminate          The SYSTEM screen gives a general overview of common
chiller failure due to AC power failure/battery discharge.     chiller parameters for both shells. This is an end view of
Programmed setpoints are retained in lithium battery-          the chiller with a 3-D cutaway of both the shells. The fol-
backed RTC memory for 11 years minimum.                        lowing can be viewed from this screen:

Thermal ice storage systems are based on the concept           Display Only:
of using off-peak, lower cost electricity to build ice for       • Discharge Temperature
handling the cooling load during peak hours. The most          	 • Chilled Liquid Temperature – Leaving
efficient way to build ice is to maximize chiller load and
                                                                 • Chilled Liquid Temperature – Return
minimize run time. Standard chiller control systems are not
designed for this operating mode. In a typical application,      • Chilled Liquid Temperature – Setpoint
chillers will load and unload to maintain a leaving chilled      • Evaporator Pressure
liquid setpoint. When the YORK YR chiller operates in the        • Evaporator Saturation Temperature
thermal storage control mode, the unit will remain at 100%
                                                                 • Condenser Liquid Temperature – Leaving
load until the setpoint shutdown temperature is reached.
To add greater operating flexibility and eliminate unnec-        • Condenser Liquid Temperature – Return
essary chiller cycling, two different Low Water (Liquid)         • Condenser Pressure
Temperature Restart Thresholds can be programmed, one            • Condenser Saturation Temperature
for the ice mode and one for the standard cooling mode.
                                                                 • Oil Temperature
This control enhancement is standard on all YR chillers.
The chiller can also be left in the standard control mode        • Differential Oil Pressure
for temperatures ranging between 20 and 70°F (-6.7 and           • % Full-load Amps
21.1°C), for applications involving a process or comfort         • Current Limit
cooling duty that requires leaving chilled liquid tempera-
ture setpoint control.                                         The EVAPORATOR screen displays a cutaway view of
                                                               the chiller evaporator. All setpoints relating to the evapo-
When power is applied to the chiller, the HOME screen is       rator side of the chiller are maintained on this screen.
displayed. This screen displays a visual representation        Animation of the evaporation process indicates whether
of the chiller and a collection of data detailing important    the chiller is presently in RUN condition (bubbling) and
operations and parameters. When the chiller is running,        liquid flow in the pipes is indicated by alternating shades
the flow of chilled liquid is animated by the alternating      of color moving in and out of the pipes. Adjustable limits
shades of color moving in and out of the pipe nozzles. The     on the low water temperature setpoints allow the chiller
primary values that need to be monitored and controlled        to cycle on and off for greater efficiency and less chiller
are shown on this screen. They are as follows:                 cycling. The chiller cycles off when the leaving chilled
                                                               water temperature is below setpoint and is adjustable

6                                                                                                JOHNSON CONTROLS
FORM 160.81-EG2 (511)

from 1°F (0.55°C) below to a minimum of 38°F (2.22°C).          • High Pressure Switch (Open/Closed)
Restart is adjustable from setpoint up to a max. of 80°F        • Condenser Liquid Flow Switch
(26.6°C). The Panel will check for flow to avoid freeze-
                                                                • Condenser Liquid Pump (Run/Stop)
up of the tubes. If flow is interrupted, shutdown will occur
after a minimum of two seconds. The following can also
                                                               Programmable:
be performed through this screen:
                                                                • High Pressure Warning Threshold
Display Only:
 • Chilled Liquid Flow Switch (Open/Closed)                    The COMPRESSOR screen displays a cutaway view of
 • Chilled Liquid Pump (Run/Stop)                              the chiller compressor, revealing the rotary screw, and
                                                               shows all conditions associated with the compressor. The
 • Evaporator Pressure
                                                               slide valve positioning is animated and with the proper
 • Evaporator Saturation Temperature                           Access level, it can be manually controlled. Animation
 • Return Chilled Liquid Temperature                           of the compressor rotors indicates whether the chiller is
 • Leaving Chilled Liquid Temperature                          presently in a RUN condition. This screen also serves as
                                                               a gateway to sub-screens for calibrating the slide valve
 • Small Temperature Difference
                                                               or configuring the optional Hot Gas Bypass. From this
 •   Leaving Chilled Liquid Temperature Setpoints –            screen you can view the following:
		   Setpoint
 •   Leaving Chilled Liquid Temperature Setpoints –            Display Only:
		   Remote Range                                               • Differential Oil Pressure
 •   Leaving Chilled Liquid Temperature Setpoints –             • Oil Temperature
		   Shutdown
                                                                • Discharge Temperature
 •   Leaving Chilled Liquid Temperature Setpoints –
                                                                • Discharge Superheat
		   Shutdown Offset
                                                                • Oil Return Solenoid (LED)
 •   Leaving Chilled Liquid Temperature Setpoints –
		   Restart                                                    • Full-load Amps (E.M. Starter Only)
 •   Leaving Chilled Liquid Temperature Setpoints –             • Phase A, B, C Current (SSS Only)
		   Restart Offset
                                                               Programmable:
 •   Ice Storage Active (LED)
                                                                • Slide Valve Load (Manual)
Programmable:
                                                                • Slide Valve Hold (Manual)
 • Local Leaving Chilled Liquid Temperature – Range
                                                                • Slide Valve Unload (Manual)
 • Local Leaving Chilled Liquid Temperature – Setpoint
                                                                • Slide Valve Auto
 • Leaving Chilled Liquid Temperature Cycling Offset –
                                                                • Max. Load Temperature
		 Shutdown
                                                                • Minimum Load FLA
 • Leaving Chilled Liquid Temperature Cycling Offset –
		 Restart                                                      • Minimum Load Control Source

The CONDENSER screen displays a cutaway view of the            The HOT GAS BYPASS screen, accessed from the
chiller condenser. The liquid flow is animated to indicate     COMPRESSOR screen, displays a pictorial of the by-
flow through the condenser. All setpoints relating to the      pass line and solenoid valve location on the chiller. The
condenser side of the chiller are maintained on this screen.   Hot Gas ON and OFF Setpoints are programmed on this
With the proper access level this screen also serves as a      screen and system parameters pertinent to Hot Gas By-
gateway to controlling the Refrigerant Level. The following    pass operation are displayed. An LED illuminates when
can also be viewed through this screen:                        the Hot Gas solenoid is ON. If the chiller is equipped with
                                                               the Hot Gas Bypass option, operation must be enabled
Display Only:                                                  on the OPERATIONS screen. From this screen you can
 • Leaving Condenser Liquid Temperature                        perform the following:
 • Return Condenser Liquid Temperature
                                                               Display Only:
 • Condenser Pressure
                                                                • Return Chilled Liquid Temperature
 • Condenser Saturation Temperature
                                                                • Leaving Chilled Liquid Temperature
 • Small Temperature Difference
                                                                • Hot Gas Solenoid (LED)
JOHNSON CONTROLS                                                                                                        7
FORM 160.81-EG2 (511)

OptiView Control Center
Programmable:                                                 Display Only:
 • On Setpoint                                                 • Input Power kW
 • Off Setpoint                                                • kW Hours
                                                               • Starter Model
The OIL SEPARATOR screen displays a close-up view
                                                               • Voltage – Phase A, B, C
of the chiller oil separator/sump.
                                                               • Current – Phase A, B, C
Display Only:                                                  • Temperature – Phase A, B, C
 • Discharge Temperature
                                                              Programmable:
 • Discharge Superheat
                                                               • Full-load Amps
 • Oil Pressure
                                                               • Voltage Range
 • Discharge Pressure
                                                               • Starting Current
 • Differential Oil Pressure
                                                               • Open SCR
 • Differential Filter Pressure
                                                               • Shorted SCR
 •   Oil Return Solenoid (LED)
                                                               • kWH Reset
 •   Evaporator Pressure
 •   Condenser Pressure                                       The SETPOINTS screen provides a convenient location
 •   Condenser Saturation                                     for programming the most common setpoints involved
                                                              in the chiller control. The Setpoints are shown on other
The MOTOR “soft” key on the HOME screen, when                 individual screens, but to cut down on needless search-
pressed, shows a picture of either a YORK Electro-            ing, they can all be found on this screen. This screen also
Mechanical Starter or a Solid State Starter, depending        serves as a gateway to a sub-screen for defining the setup
on chiller configuration. The Programmable pulldown           of general system parameters. From this screen you can
demand to automatically limit motor loading can be used to    perform the following:
minimize building demand charges. Pulldown time period
control over four hours, and verification of time remaining   Display Only:
in pulldown cycle from display readout. Separate digital       • Leaving Chilled Liquid Temperature – Setpoint
setpoint for current limiting between 30 and 100%.
                                                               • Leaving Chilled Liquid Temperature Cycling –
                                                              		 Shutdown
The ELECTRO-MECHANICAL STARTER (E–M) screen
displays a picture of the starter and the following values.    • Leaving Chilled Liquid Temperature Cycling –
The ones below are common among both offerings and            		 Restart
the values will be displayed on both types of starter          • Current Limit Setpoint
screens. From this screen you can perform the following:
                                                              Programmable:
Display Only:
                                                               • Local Leaving Chilled Liquid Temperature – Range
 • Motor Run (LED)
                                                               • Local Leaving Chilled Liquid Temperature –
 • Motor Current % Full-load Amps                                Setpoint
 • Current Limit Setpoints                                     • Leaving Chilled Liquid Temperature Cycling Offset
 • Pulldown Demand Time Left                                     – Shutdown
                                                               • Leaving Chilled Liquid Temperature Cycling Offset
Programmable:                                                    – Restart
 • Local Motor Current Limit                                   • Remote Analog Input Range
 • Pulldown Demand Limit                                       • Local Motor Current Limit
 • Pulldown Demand Time                                        • Pulldown Demand Limit
                                                               • Pulldown Demand Time
The SOLID STATE STARTER (SSS) screen displays a
picture of the starter and the following values, which are     • Print
displayed in addition to the common ones listed above.
From this screen, you can perform the following:

8                                                                                              JOHNSON CONTROLS
FORM 160.81-EG2 (511)

The SETUP is the top level of the general configura-            Programmable:
tion parameters. It allows programming of the time and           • Chiller ID
date, along with specifications as to how the time will be
                                                                 • COM 2 Baud Rate
displayed. In addition, the chiller configuration as deter-
mined by the Micro Board program jumpers and program             • COM 2 Data Bit(s)
switches is displayed. From this screen you can perform          • COM 2 Parity Bit(s)
the following:                                                   • COM 2 Stop Bit(s)
                                                                 • Printer Baud Rate
Display Only:
                                                                 • Printer Data Bit(s)
 • Chilled Liquid Pump Operation (Displays Standard or
   Enhanced)                                                     • Printer Parity Bit(s)
 • Anti-Recycle (Displays Disabled or Enabled)                   • Printer Stop Bit(s)
 • Power Failure Restart (Displays Manual or Automatic)
                                                                The PRINTER screen permits the user to define com-
 • Liquid Type (Displays Water or Brine)                        munications Parameters for the Printer.
                                                                Display Only
Programmable:
                                                                 • Time Remaining Until Next Print
 • Set Date
 • Set Time                                                     Programmable
 • Clock (Enabled/Disabled)                                      • Log Start Time
 • 12/24 Hour                                                    • Output Interval
                                                                 • Automatic Printer Logging (Enabled/Disabled)
The following six subscreens can be accessed from
                                                                 • Print Type
the SETUP screen:
                                                                 • Print Report
The SCHEDULE screen contains more programmable                   • Print All Histories
values than a normal display screen. Each programmable
value is not linked to a specific button; instead, the select   The SALES ORDER screen allows definition of the order
key is used to enable the cursor arrows and check key to        parameters. Note: This information is loaded at the factory
program the Start/Stop times for any day of the week up         or by the installation service technician.
to 6 weeks in advance. The user has the ability to define
a standard set of Start/Stop times that are utilized every      Display Only
week or specify exceptions to create a special week.             • Model Number
                                                                 • Panel Serial Number
Programmable:
                                                                 • Chiller Serial Number
 • Exception Start/Stop Times
                                                                 • YORK Order Number
 • Schedule (Enable/Disable)
                                                                 • System Information
 • Repeat Sunday Schedule
                                                                 • Condenser and Evaporator Design Load Information
 • Standard Week Start/Stop Times
                                                                 • Nameplate Information
 • Reset All Exception Days
 • Select                                                       The OPERATIONS screen permits definition of pa-
 • Print                                                        rameters pertaining to operation of the chiller. What is
                                                                defined is whether the control of the chiller will be Local,
The USER screen allows definition of the language for the       Digital Remote, Analog Remote, Modem Remote or ISN
chiller to display and defines the unit of measure.             Remote.

Programmable:                                                   Programmable
 • System Language                                               • Control Source
 • English/Metric Units
                                                                The HISTORY screen allows the user to browse through
The COMMS screen allows the user to define communi-             the last ten faults; either safety or cycling shutdowns with
cations parameters.                                             the conditions, while the chiller is running or stopped.

JOHNSON CONTROLS                                                                                                          9
FORM 160.81-EG2 (511)

OptiView Control Center
The faults are color coded for ease in determining             The TREND SETUP screen is used to configure the trend-
the severity at a glance, recording the date, time and         ing screen. The parameters to be trended are selected
description. (See Display Messages for Color Code              from the Trend Common Slots screen, accessed from
meanings.)                                                     the Slot Numbers button or the Master Slot Numbers
                                                               List found in the Operating Manual. The interval at which
Display Only                                                   all the parameters are sampled is selected under the
 • Last Normal Shutdown                                        Collection Interval button. The data point minimum and
                                                               maximum values may be adjusted closer to increase
 • Last Fault While Running
                                                               viewing resolution.
 • Last Ten Faults
                                                               Programmable:
Programmable:                                                   • Chart Type (select continuous or one screen)
 • Print History                                                • Collection Interval
 • Print All Histories                                          • Select
                                                                • Data Point Slot Number (1 - 6)
By pressing the VIEW DETAILS key you will move to the
HISTORY DETAILS screen. From these screens you                  • Data Point Min. (1 - 6)
are able to see an on-screen printout of all the system         • Data Point Max (1 - 6)
parameters at the time of the selected shutdown.
                                                               The TREND COMMON SLOTS screen displays the Mas-
Display Only:                                                  ter Slot Numbers List of the monitored parameters.
 • History Printout
                                                               Display Only:
Programmable:                                                   • Slot Numbers
 • Page Up
                                                               Programmable:
 • Page Down
                                                                • Page Up
 • Print History
                                                                • Page Down
Also under the HISTORY screen is the TRENDING                   • Print
screen, accessible by the key marked the same. On
this screen, up to six operator-selected parameters, se-       DISPLAY MESSAGES
lected from a list of over 140, can be plotted in an X/Y
graph format. The graph can be customized to record
                                                               The Control Center continuously monitors the operating
points once every second up to once every hour. There
                                                               system, displaying and recording the cause of any shut-
are two types of charts that can be created: single
                                                               downs (Safety, Cycling or Normal). The condition of the
screen, or continuous screen. The single screen col-
                                                               chiller is displayed at the System Status line that contains
lects data for one screen width (450 data points across
                                                               a message describing the operating state of the chiller;
the X-axis), then stops. The continuous screen keeps col-
                                                               whether it is stopped, running, starting or shutting down.
lecting the data, but the oldest data drops off the graph
                                                               A System Details Line displays Warning, Cycling, Safety,
from left to right at the next data collection interval. For
                                                               Start Inhibit and other messages that provide further
ease of identification, each plotted parameter, title and
                                                               details of the Status Bar messages. Messages are color-
associated Y-axis labeling is color coordinated.
                                                               coded: Green – Normal Operations; Yellow – Warnings;
                                                               Orange – Cycling Shutdowns; and Red – Safety Shut-
Display Only:
                                                               downs to aid in identifying problems quickly.
 • This screen allows the user to view the graphical
   trending of the selected parameters and is a gateway        Status messages include:
   to the graph setup screens.
                                                                • System Ready To Start
Programmable:                                                   • Cycling Shutdown – Auto Restart
 • Start                                                        • Safety Shutdown – Manual Restart
 • Stop                                                         • Start Sequence Initiated
 • y-axis                                                       • System Run (with countdown timers)
 • x-axis                                                       • Start Inhibit

10                                                                                               JOHNSON CONTROLS
FORM 160.81-EG2 (511)

 • Slide Valve Closing Before Shutdown           Solid State Starter Only (LCSSS)
 • System Lockout Delay                           • Initialization Failed
                                                  • Serial Communications
Run Messages include:                             • Requesting Fault Data
 • Leaving Chilled Liquid Control                 • Stop Contacts Open
 • Motor Pulldown Limit                           • Power Fault
 • Motor – High Current Limit                     • Low Phase (X) Temperature Sensor
                                                  • Run Signal
Start Inhibit Messages include:
                                                  • Invalid Current Scale Selection
 • Anti-Recycle XX min/sec.
                                                  • Phase Locked Loop
 • Motor Current >15% FLA
                                                  • Low Supply Line Voltage
 • LCSSS – High-Temperature Phase X - Stopped
                                                  • High Supply Line Voltage
Warning Messages include:                         • Logic Board Processor
 •   Real Time Clock Failure                      • Logic Board Power Supply
 •   Setpoint Override                            • Phase Loss
 •   Condenser – High Pressure Limit             Safety Shutdown Messages include:
 •   Evaporator – Low Pressure Limit              • Evaporator – Low Pressure
 •   Freeze Threat, Condenser Flow Switch Open    • Evaporator – Transducer or Leaving Liquid Probe
 •   Low Discharge Superheat Limit                • Evaporator – Transducer or Temperature Sensor
 •   Low Discharge Superheat Detected             • Condenser – High Pressure Contacts Open
 •   Maximum Load – Load Limit                    • Condenser – High Pressure
 •   Minimum Load – Load Limit                    • Condenser – Pressure Transducer Out of Range
 •   Oil – Dirty Filter                           • Auxiliary Safety – Contacts Closed
 •   Oil – High Temperature                       • Discharge – High Temperature
                                                  • Discharge – Low Temperature
Routine Shutdown Messages Include:
                                                  • Oil – Low Differential Pressure
 • Remote Stop
                                                  • Oil or Condenser Transducer Error
 • Local Stop                                     • Oil – Clogged Filter
 • Place Compressor Switch In Run Position        • Oil – High Pressure
                                                  • Control Panel – Power Failure
Cycling Shutdown Messages Include:
                                                  • Watchdog – Software Reboot
 • Multiunit Cycling – Contacts Open
 • System Cycling – Contacts Open                Solid State Starter Only (LCSSS)
 • Control Panel – Power Failure                  • Shutdown – Requesting Fault Data . . .
 • Leaving Chilled Liquid – Low Temperature       • High Instantaneous Current
 • Leaving Chilled Liquid – Flow Switch Open      • High Phase (X) Heatsink Temperature – Running
 • Condenser – Flow Switch Open                   • 105% Motor Current Overload
 • Motor Controller – Contacts Open               • Motor or Starter – Current Imbalance
 • Motor Controller – Loss of Current             • Open SCR
 • Power Fault                                    • Phase Rotation
 • Control Panel – Schedule

JOHNSON CONTROLS                                                                                      11
FORM 160.81-EG2 (511)

Mechanical Specifications
GENERAL                                                          to automatically remove oil which may have migrated to
                                                                 the evaporator, and return it to the compressor. The oil
Each YORK MaxE YR Screw Chiller will be completely
                                                                 separator will be of a vertical design with no moving parts,
factory-packaged including evaporator, condenser, com-
                                                                 and will provide high-efficiency oil separation before the
pressor, motor, OptiView control center and all intercon-
                                                                 refrigerant enters the heat exchangers. The oil separator
necting unit piping and wiring. The chiller will be painted
                                                                 will be designed, tested, and stamped in accordance with
prior to shipment and will be packaged to protect the unit
                                                                 the ASME Boiler and Pressure Vessel Code, Section VIII
during shipment.
                                                                 Division 1. Liquid refrigerant injection will be provided to
                                                                 maintain satisfactory oil temperatures and allow operation
Performance will be certified in accordance with ARI
                                                                 of the chiller over the full range of conditions.
Standard 550/590.
                                                                 EVAPORATOR
The initial charge of refrigerant and oil will be supplied
for each unit.                                                   Evaporator will be of the horizontal shell-and-tube, flooded
                                                                 type; the heat exchanger tubes are located in the lower
DRIVELINE                                                        half of the shell, along with the refrigerant liquid distribution
                                                                 system. This offers uniform liquid distribution of refrigerant,
The compressor will be twin-screw, rotary-screw type.
                                                                 throughout the shell length, to yield optimum refrigerant
The compressor housing will be of cast iron, precision
                                                                 side heat transfer. To remove the liquid droplets from
machined to provide minimal clearance for the rotors.
                                                                 the vapor, the space above the tube bundle is for liquid
The rotors will be manufactured from forged steel and
                                                                 vapor separation; it contains a baffled suction chamber
use asymmetric profiles operating at a maximum speed of
                                                                 with slots in the baffle, controlling the vapor flow into the
3570 RPM (60 Hz) or 2975 RPM (50 Hz). The compressor
                                                                 suction connection. The shell is fabricated from carbon
will incorporate a complete anti-friction bearing design to
                                                                 steel, rolled plate, with fusion welded seams, or for the
reduce power and increase reliability; cylindrical roller
                                                                 smaller sizes, carbon steel pipe; it has carbon steel tube
bearings to handle radial loads; and 4 point angular con-
                                                                 sheets with drilled, and reamed holes to accommodate the
tact ball bearings to handle axial loads. The compressor
                                                                 heat exchanger tubes; 1/2 inches (12.7 mm) thick, carbon
will have an internal oil reservoir to assure a constant sup-
                                                                 steel, intermediate tube supports, spaced no more than
ply of oil to the bearings at all times. A check valve will be
                                                                 four feet (1.22 m) apart, are provided to support the tubes
incorporated to prevent rotor backspin during shutdown.
                                                                 between the tube sheets. The refrigerant side is designed
                                                                 for a maximum working pressure of 235 psig (1620 kPa);
Capacity control will be achieved by use of a slide valve to
                                                                 it is designed, tested, and stamped in accordance with
provide fully modulating control from 100% to 20% of full-
                                                                 the ASME Boiler and Pressure Vessel Code, Section
load. The slide valve will be actuated by system differential
                                                                 VIII, Division 1. The cooler shell will have a refrigerant
pressure, controlled by external solenoid valves through
                                                                 dual relief valve assembly, to meet the requirements of
the OptiView control center. The unit will be capable of
                                                                 ASHRAE 15, Safety Code for Mechanical Refrigeration.
operating with off-design cooling tower water during part-
                                                                 Heat exchanger tubes are high efficiency, internally and
load operation in accordance with ARI Standard 550/590.
                                                                 externally enhanced type of seamless copper alloy; tubes
                                                                 have plain copper lands at all intermediate support, to
The motor will be 2-pole, continuous-duty, cage-induction
                                                                 provide maximum wall thickness at all the supported tube
type, and will utilize suction gas cooling (semi-hermetic
                                                                 area. Tubes are 0.75 inch (19.1 mm) O.D., nominal 0.025
design). Motor full-load amperes at design conditions will
                                                                 inches (0.635 mm) wall thickness and are individually re-
not exceed chiller nameplate (FLA). Motor will be designed
                                                                 placeable. Each tube is roller expanded, into a 1-1/2 inch
for use with the type starter specified.
                                                                 (3.79 cm) thick steel tube sheet, providing a leak proof
                                                                 seal. Water velocity through the tubes will not exceed 12
LUBRICATION SYSTEM
                                                                 ft. per sec (3.66 m/sec). A 2-1/4 inch (5.72 cm) diameter,
An adequate supply of oil will be available to the compres-      glass sight port is located on the side of the shell, to aid in
sor at all times. During operation, oil will be delivered by     establishing the R-134A liquid level, for the proper YR Unit
positive system pressure differential.                           refrigerant charge. The R-134A, 3/4 inch (19.1 mm) charg-
                                                                 ing valve is located in the liquid line below the evaporator.
An immersion oil heater will be provided, (temperature
actuated), to effectively remove refrigerant from the oil dur-   Water boxes will be removable to permit tube cleaning and
ing the chiller off-cycle. An external, replaceable cartridge,   replacement. Stubout water connections having victaulic
oil filter will be provided, along with manual isolation stop    grooves will be provided. Vent and drain connections with
valves for ease of servicing. An oil eductor will be provided    plugs will be provided on each water box.

12                                                                                                   JOHNSON CONTROLS
FORM 160.81-EG2 (511)

CONDENSER                                                       fabricated from carbon steel wtih necessary integral steel
                                                                pass baffles, and gaskets, for the water flow circuit; boxes
Condenser will be horizontal shell and tube type, with a
                                                                are 150 psig (1034 kPa) design working pressure, and
discharge gas baffle to prevent direct high velocity gas
                                                                hydro pressure tested at 1.5 times the DWP.
impingement on the tubes, and distribute the gas flow. An
integral refrigerant sub-cooler is located under the con-
                                                                REFRIGERANT SYSTEM
densing tube bundle section for improved thermodynamic
cycle efficiency. Baffles direct the liquid refrigerant flow    A modulating variable orifice controlled by the OptiView
back-and-forth, across the sub-cooler tubes, as it travels      Control Center to accommodate varying head and load
the length of the shell. The shell if fabricated from carbon    conditions will meter refrigerant flow to the evaporator.
steel, rolled plate, with fusion welded seams, or for the
smaller sizes, carbon steel pipe; it has carbon steel tube      The condenser shell will be capable of storing the entire
sheets with drilled, and reamed holes to accommodate the        system refrigerant charge during servicing. Service valves
heat exchanger tubes; 3/8 inch (9.53 mm) thick, carbon          will be provided to facilitate removal of refrigerant charge
steel, intermediate condenser tube supports, spaced no          from the system.
more than four feet (1.22 m) apart, are provided to sup-
port the tubes between the tube sheets. The refrigerant         The unit will be equipped with a suction strainer to pre-
side is designed for a maximum working pressure of 235          vent any foreign debris introduced to the system during
psig (1620 kPa), it is designed, tested, and stamped in         maintenance or service to be allowed into the motor
accordance with the ASME Boiler and Pressure Vessel             housing. Motors cooled by refrigerant must be protected
Code, Section VIII, Division 1. The condenser shell will        by means of filter or strainer to protect the motor and
have a refrigerant dual relief valve assembly, to meet the      prolong motor life.
requirements of ASHRAE 15, Safety Code for Mechanical
Refrigeration. Heat exchanger tubes are high efficiency,        OPTIVIEW CONTROL CENTER
internally and externally enhanced types of seamless cop-
                                                                General
per alloy; tubes have plain copper lands at all intermedi-
ate tube supports, to provide maximum wall thickness at         The chiller will be controlled by a stand-alone micropro-
the supported tube area. Tubes are 0.75 inch (19.1 mm)          cessor based control center. The chiller control panel will
O.D., nominal 0.025 inch (0.635 mm) wall thickness and          provide control of chiller operation and monitoring of chiller
are individually replaceable. Each tube is roller expanded,     sensors, actuators, relays and switches.
into one inch (2.54 cm) thick steel tube sheet, providing a
leak proof seal. Water velocity through the tubes will not      Control Panel
exceed 12 ft. per sec. (3.66 m/sec.).
                                                                The control panel will include a 10.4 inch diagonal color
                                                                liquid crystal display (LCD) surrounded by “soft “ keys
WATER BOXES
                                                                which are redefined based on the screen displayed at that
The compact style water boxes for the cooler, and con-          time. It will be mounted in the middle of a keypad interface
denser heat exchangers, are removable (bolted-on) at the        and installed in a locked enclosure. The screen will detail
tube sheet, to permit direct access for tube inspection,        all operations and parameters, using a graphical repre-
mechanical tube cleaning, and tube replacement. To suit         sentation of the chiller and its major components. Panel
the project's water range, and pressure drop requirements,      verbiage is available in other languages as an option with
most water boxes are available with 1, 2, or 3 - passes,        English always available. Data can be displayed in either
and with a variety of nozzle arrangments. Stub-out water        English or Metric units. When needed, Hot Gas Bypass
connections are provided with a Victaulic groove­—suit-         is available as an option. The panel displays countdown
able for field welding, flanges or Victaulic couplings­­­—and   timer messages so the operator knows when functions
capped for shipment. Each nozzle is furnished with a            are starting and stopping. Every programmable point will
copper thermo-well, to allow the OptiView control center        have a pop-up screen with the allowable ranges, so that
to control and/or read the fluid's temperature. The sub-        the chiller can not be programmed to operate outside of
cooler is located below the condensing tube bundle in the       its design limits.
condenser; the entering (inlet) condenser water nozzle,
which has the coldest temperature, and must physically          The control panel is provided with a thermal ice storage
be the lowest connection, to supply the coldest water to        control mode to enhance system performance during ice
the sub-cooler on the first pass. The outlet chilled water      building operation. In the thermal storage control mode,
connection must always leave at the top of the evaporator       the chiller will stay at 100% load until the setpoint shut-
tube bundle, where the refrigerant temperature is coldest.      down temperature is reached. To add greater operating
Plugged 3/4 inch (19.1 mm) drain and vent connections           flexibility and eliminate unnecessary chiller cycling, two
are furnished on each water box. Compact boxes are              different Low Water (Liquid) Temperature Restart Thresh-
JOHNSON CONTROLS                                                                                                           13
FORM 160.81-EG2 (511)

Mechanical Specifications
olds are programmable, one for the ice mode and one for        		   a.   evaporator – low pressure
the standard cooling mode. The chiller has the capability      		   b.   evaporator – transducer or leaving liquid probe
to remain in the standard control mode for temperatures
                                                               		   c.   evaporator – transducer or temperature sensor
between 20 to 70°F (-6.6 to 21.1°C) for applications involv-
ing a process or comfort cooling duty that requires leaving    		   d.   condenser – high pressure contacts open
chilled liquid temperature setpoint control.                   		   e.   condenser – high pressure
                                                               		   f.   condenser – pressure transducer out of range
The chiller control panel also provides:
                                                               		   g.   auxiliary safety – contacts closed
 1. System operating information including:
                                                               		   h.   discharge – high temperature
		 a. return and leaving chilled liquid temperature
                                                               		   i.   discharge – low temperature
		 b. return and leaving condenser liquid
                                                               		   j.   oil – low differential pressure
			 temperature
                                                               		   k.   oil or condenser transducer error
		 c. evaporator and condenser saturation
			 temperature                                                		   l.   oil – clogged filter
		 d. oil pressure at compressor and oil filter                		   m.   oil – high pressure
			 differential                                               		 n. control panel – power failure
		 e. percent motor current                                    		 o. watchdog – software reboot
		 f. evaporator and condenser saturation                      5.1. Safety shutdowns with a Solid State Starter (LCSSS)
			 temperature                                                     will include:
		 g. compressor discharge temperature                         		 a. shutdown – requesting fault data…
		 h. oil temperature                                          		 b. high instantaneous current
		 i. operating hours                                          		 c. high phase (X) heatsink temperature - running
		 j. number of unit starts                                    		 d. 105% motor current overload
 2. Digital programming of setpoints through the univer-       		 e. motor or starter – current imbalance
    sal keypad including:                                      		 f. phase (X) shorted SCR
		 a. leaving chilled liquid temperature                       		 g. open SCR
		 b. percent current limit                                    		 h. phase rotation
		 c. pull-down demand limiting                                 6. Cycling shutdowns enunciated through the display
		 d. six-week schedule for starting and stopping the               and the status bar, and consists of system status,
        chiller, pumps and tower                                    system details, day, time, cause of shutdown, and
		 e. remote reset temperature range                                type of restart required. Cycling shutdowns with a
                                                                    fixed speed drive will include:
 3. Status messages indicating:
                                                               		 a. multiunit cycling – contacts open
		 a. system ready to start
                                                               		 b. system cycling - contacts open
		 b. system running
                                                               		 c. control panel - power failure
		 c. system coastdown
                                                               		 d. leaving chilled liquid - low temperature
		 d. system safety shutdown-manual restart
                                                               		 e. leaving chilled liquid - flow switch open
		 e. system cycling shutdown-auto restart
                                                               		 f. condenser – flow switch open
		 f. start sequence initiated
                                                               		 g. motor controller – contacts open
		 g. start inhibit
                                                               		 h. motor controller – loss of current
 4. The text displayed within the system status and sys-
    tem details field will be displayed as a color coded       		 i. power fault
    message to indicate severity: red for safety fault,        		 j. control panel - schedule
    orange for cycling faults, yellow for warnings, and
                                                               6.1. Cycling shutdowns with a Solid State Starter (LCSSS)
    green for normal messages.
                                                                    will include:
 5. Safety shutdowns enunciated through the display and
                                                               		 a. initialization failed
    the status bar, and consist of system status, system
    details, day, time, cause of shutdown, and type of         		 b. serial communications
    restart required. Safety shutdowns with a fixed speed      		 c. requesting fault data
    drive will include:                                        		 d. stop contacts open
14                                                                                               JOHNSON CONTROLS
FORM 160.81-EG2 (511)

		   e. power fault                                                STARTUP AND OPERATOR TRAINING
		   f. low phase (X) temperature sensor                           The services of a factory­trained, field service represen-
		   g. run signal                                                 tative will be provided to supervise the initial startup and
		   h. invalid current scale selection                            conduct concurrent operator instruction.
		   i. phase locked loop
                                                                   CODES AND STANDARDS
		   j. low supply line voltage
                                                                    • ASME Boiler and Pressure Vessel Code – Section
		   k. high supply line voltage
                                                                      Vlll Division 1.
		   l. logic board processor
                                                                    • ARI Standard 550/590
		   m. logic board power supply
                                                                    • c/U.L. – Underwriters Laboratory
		   n. phase loss
                                                                    • ASHRAE 15 – Safety Code for Mechanical Refrigera-
 7.  Security access to prevent unauthorized change of                tion
     setpoints, to allow local or remote control of the chiller,
                                                                    • ASHRAE Guideline 3 – Reducing Emission of Halo-
     and to allow manual operation of the slide valve. Ac-
                                                                      genated Refrigerants in Refrigeration and Air-Condi-
     cess is through ID and password recognition, which is
                                                                      tioning Equipment and Systems
     defined by three different levels of user competence:
     view, operator, and service.                                   • NEC – National Electrical Code
 8. Trending data with the ability to customize points of           • OSHA – Occupational Safety and Health Act
     once every second to once every hour. The panel shall
     trend up to 6 different parameters from a list of over 140,   ISOLATION MOUNTING PADS
     without the need of an external monitoring system.            Four vibration isolator pads provide the YR unit's foot print.
 9. The operating program stored in non-volatile memory            The floor contact area size depends upon the specific unit
     (EPROM) to eliminate reprogramming the chiller due            operating weight. These mounts are located at the four
     to AC power failure or battery discharge. Programmed          corners of the unit, under the heat exchanger tube sheets;
     setpoints will be retained in lithium battery-backed RTC      welded to the bottom of the tube sheets are 5/8 inch (15.9
     memory for a minimum of 11 years with power removed           mm) thick steel foot supports (which spreads the weight).
     from the system.                                              The mounts consist of 3/4 inch (19.05 mm) thick, bridge
10. A fused connection through a transformer in the com-           bearing neoprene pads, adhesive bonded to 3/8 inch (9.53
     pressor motor starter to provide individual over-current      mm) thick steel plates. The mounts are shipped loose, for
     protected power for all controls.                             field mounting under the heat exchanger foot supports.
11. A numbered terminal strip for all required field interlock     Galvanized shims are provided to level the unit. The neo-
     wiring.                                                       prene pad, rated load, static deflection is 0.10 inches (2.54
                                                                   mm). The pads are suitable for typical equipment rooms
12. An RS-232 port to output all system operating data,            located on the ground floor. No provisions for anchoring
     shutdown / cycling message, and a record of the last 10       to the floor are required. (For upper floor installations,
     cycling or safety shutdowns to a field-supplied printer.      one inch (2.54 cm) deflection, spring isolator mounts are
     Data logs to a printer at a set programmable interval.        applied­—see Accessories)
     This data can be preprogrammed to print from 1 minute
     to 1 day.
13. The capability to interface with a building automation         REFRIGERANT CONTAINMENT
     system to provide:                                            The standard unit has been designed as a complete and
		 a. remote chiller start and stop                                compact factory packaged chiller. As such, it has mini­
		 b. remote leaving chiller liquid temperature adjust             mum joints from which refrigerant can leak. The entire
                                                                   assembly has been thoroughly leak tested at the factory
		 c. remote current limit setpoint adjust                         prior to shipment. The YORK chiller includes service
		 d. remote ready to start contacts                               valves conveniently located to facilitate transfer of refrig­
		 e. safety shutdown contacts                                     erant to a remote refrigerant storage/recycling system.
		 f. cycling shutdown contacts                                    Optional condenser isolation valves permit storage of the
                                                                   charge in the condenser.
		 g. run contacts

JOHNSON CONTROLS                                                                                                              15
FORM 160.81-EG2 (511)

Mechanical Specifications
PAINT                                                           frigerant charge in place. The oil charge, relief device and
                                                                other miscellaneous materials shall be packed separately.
Exterior surfaces are protected with one coat of Carib­
bean blue, durable alkyd‑modified, vinyl enamel, ma­
                                                                Protective covering is furnished on the Control Center
chinery paint.
                                                                and unit‑mounted controls. The entire unit is then shrink-
                                                                wrapped with high-quality reinforced plastic to provide
SHIPMENT                                                        maximum protection during transit. Water nozzles are
                                                                capped with fitted plastic enclosures.
The unit shall be completely assembled, with all main,
auxiliary, and control piping installed, controls wired, leak
tests completed, functional run tests completed, and re-

16                                                                                                JOHNSON CONTROLS
FORM 160.81-EG2 (511)

Accessories and Modifications
SOLID STATE STARTER                                             FACTORY INSULATION OF EVAPORATOR
The Solid State Starter is a reduced voltage starter that       Factory-applied thermal insulation of the flexible, closed-
controls and maintains a constant current flow to the motor     cell plastic type, 3/4" (19mm) thick is attached with
during startup. It is compact and mounted on the chiller at     vapor-proof cement to the evaporator shell, flow cham-
the motor terminals. Power and control wiring is factory        ber, evaporator tube sheets, suction connection, and (as
supplied. Available for 200-600 volts, the starter enclosure    necessary) to the auxiliary tubing. Not included is the
is NEMA-1 with a hinged access door with lock and key.          insulation of water boxes and nozzles. This insulation
Electrical lugs for incoming power wiring are provided.         will normally prevent condensation in environments with
                                                                relative humidities up to 75% and dry bulb temperatures
Standard features include: digital readout at the OptiView      ranging from 50° to 90°F (10° to 32°C). 1-1/2" (38mm)
Control Center of the following:                                thick insulation is also available for relative humidities up
                                                                to 90% and dry bulb temperatures ranging from 50° to
Display Only:                                                   90°F (10° to 32°C).
 • 3-phase voltage A, B, C
                                                                WATER FLANGES
 • 3-phase current A, B, C
 • Input power (kW)                                             Four 150 Ib. ANSI raised-face flanges, for condenser and
                                                                evaporator water connections, are factory welded to water
 • kW Hours
                                                                nozzles. Companion flanges, bolts, nuts and gaskets are
 • Starter Model                                                not included.
 • Motor Run (LED)
 • Motor Current % Full-load Amps                               SPRING ISOLATION MOUNTING
 • Current Limit Setpoints                                      For all upper floor locations, four spring-type vibration
 • Pulldown Demand Time Left                                    isolator mounts must be used, instead of the standard
                                                                heat exchangers foot supports, and neoprene mounting
Programmable:                                                   pads. These spring-type isolator mounts offer about ten
 • Local Motor Current Limit                                    times more static deflection than neoprene pads; this
                                                                increases the "isolation efficency". Thus, reducing the
 • Pulldown Demand Limit                                        vibration force being transmitted to the building floor.
 • Pulldown Demand Time                                         Spring isolator mounts can also be applied to ground
                                                                floor locations, if desired. The spring isolator mount ca-
Other features include: low line voltage; 115-volt control      pacity & size, with related foot print or floor contact area,
transformer; three-leg sensing overloads; phase rotation        depends upon the specific unit operating weight. The
and single-phase failure protection; high temperature           spring isolator mounts are located at the four corners of
safety protection; motor current imbalance and undervolt-       the YR unit, on the backside of the heat exchangers tube
age safeties; open and close SCR protection; momentary          sheets. For each specific size (to carry the unit operating
power interruption protection. The LCSSS is cooled by a         weight) spring isolator mount, four heght saving brackets
closed-loop, fresh water circuit consisting of a water-to-      are factory furnished, and welded to the back of the tube
water heat exchanger and 1/25 HP circulating pump. All          sheets. These un-housed spring vibration isolator mounts
interconnecting water piping is factory installed and rated     have a one-inch (2.54 cm) static deflection, at rated load;
for 150 PSIG working pressure. Optional unit-mounted            a 1/4 inch (6.35 mm) thick, acoustical non-skid pad on
circuit breaker includes ground fault protection and            the bottom; and features a level adjusting bolt. The four
provides 65,000 amp short-circuit withstand rating in ac-       mounts are shipped loose for field installation. No provi-
cordance with UL Standard 508. A non-fused disconnect           sions for anchoring to the floor are required. Equipment
switch is also available. Both options are padlockable.         room floor spans over twenty feet (6.1 mm), will typically
                                                                need special higher deflection isolation mounts.
BAS REMOTE CONTROL
A communication interface permitting complete exchange of       WATER FLOW SWITCHES
chiller data with any BAS system is available with optional     Paddle-type, vapor-proof water flow switches suitable
ISN translator. ISN translator also allows BAS system to        for 150 psig (1034 kPa) DWP for chilled and condenser
issue commands to the chiller to control its operation. ISN     water circuits. Switch for 115V-1-50/60 Hz service. A
translators come in two models, controlling up to four chill-   chilled water flow switch is required. Condenser water
ers and eight chillers respectively.                            flow switch is optional.

JOHNSON CONTROLS                                                                                                          17
You can also read