IZM63 / IN63 low voltage air circuit breaker - Instruction Manual MN013014EN - Eaton
←
→
Page content transcription
If your browser does not render page correctly, please read the page content below
Instruction Manual MN013010SC Purpose Safety This instruction booklet is expressly intended to cover the All safety codes, safety standards, and/or regulations must installation, operation, and maintenance of IZM63 air circuit be strictly observed in the installation, operation, and main- breakers. These circuit breakers may be supplied as part of tenance of this equipment. complete switchboard assemblies or as separate compo- nents. This booklet applies only to the circuit breaker and (if drawout) its mating cassette. In the case of fixed circuit WARNING breakers, certain sections of this leaflet, referring to such The warnings and cautions included as part of the pro- items as position interlocks and the drawout mechanism, cedural steps in this leaflet are for personnel safety and will not apply. protection of equipment from damage. An example of a Trip units associated with the IZM Air circuit breakers will be typical warning label heading is shown above to famil- addressed in a general manner in this leaflet. Specific trip iarize personnel with the style of presentation. This will unit details and time-current characteristic curves are help to ensure that personnel are alert to warnings. In covered in separate documents specific to the trip units. addition, cautions are all uppercase and boldface. IZM circuit breaker accessory items are not discussed in All possible contingencies that may arise during installation this leaflet. Field installation instructions for such items, operation or maintenance, and all details and variations however, are covered in individual instruction leaflets specif- of this equipment, do not purport to be covered by these ic to the accessory. instructions. If further information is desired by purchaser regarding particular installation, operation, or maintenance of This information is also available from the Eaton Web site at particular equipment, contact the local Eaton representative. www.eaton.com For application information, consult Eaton or see applica- ble Product Guides, Technical Documents, and Industry Standards. ii IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn
Instruction Manual MN013010SC Contents SECTION 1: INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1-1 General information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1-2 Safety features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1-3 Safe practices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1-4 Qualified personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 SECTION 2: RECEIVING, HANDLING, AND INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2-1 General information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2-2 Suggested tools. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2-3 Unpacking circuit breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2-3.1 Storing circuit breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2-4 Lifting circuit breaker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 2-5 Circuit breaker inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 2-6 Adapting cassette . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2-6.1 Rejection interlocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2-6.2 Installing secondary jumpers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2-7 Installing drawout circuit breaker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2-7.1 Circuit breaker positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2-7.2 Levering circuit breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 2-8 Fixed circuit breaker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 2-9 Circuit breaker operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 2-10 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 SECTION 3: CIRCUIT BREAKER DESCRIPTION AND OPERATION . . . . . . . . . . . . . . . . . . . . . . 15 3-1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 3-2 Basic circuit breaker assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 3-3 Operating mechanism. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 3-3.1 Manual operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 3-3.2 Electrical operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 3-3.3 Anti-pump feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 3-4 Electronic tripping system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 3-4.1 Microprocessor-based trip unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 3-4.2 Rating plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 3-4.3 Current sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 3-4.4 Frame rating module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 3-4.5 Trip actuator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 3-4.6 Fixed high instantaneous non-adjustable trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 3-4.7 Non-automatic device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 3-5 Secondary contacts and connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn iii
Instruction Manual MN013010SC SECTION 4: DIMENSIONAL DRAWINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 SECTION 5: PROTECTIVE CHARACTERISTIC CURVES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 SECTION 6: WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 SECTION 7: INSPECTION AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 7-1 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 7-2 General cleaning recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 7-3 When to inspect. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 7-4 What to inspect. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 7-4.1 Functional field testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 7-4.2 Arc chute inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 7-4.3 Primary contact inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 SECTION 8: TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 8-1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 iv IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn
Section 1: Introduction Section 1: Introduction When withdrawn on captive compartment cassette exten- sion rails, IZM63 / IN63 circuit breakers can be inspected, accessory items added, and minor maintenance performed. The inside of the compartment can also be inspected with 1-1 General information the circuit breaker on its extension rails. The IZM63 / IN63 air circuit breaker is a fixed or drawout air circuit breaker design using an electronic tripping system. It is designed and tested for use at nominal voltages of NOTICE AC380/415V, 440V and 500/690V. IZM63 / IN63 circuit Please read and understand these instructions before breakers are available with continuous current ratings from attempting to unpack, install, operate, or maintain this 5000 to 6300A. The withdrawable & fixed frame sizes have equipment. Study the breaker and its mechanism carefully common height and depth dimensions. The circuit breaker before attempting to operate it on an energized circuit. nameplate provides complete rating information. All IZM63 circuit breakers are 100% rated, and are built and tested in an ISOT 9002 certified facility to applicable IEC and BS WARNING standards (Figure 1-2). IZM63 / IN63 circuit breakers should not under any cir- IZM63 / IN63 circuit breakers use a rigid frame housing of cumstances be applied outside their nameplate ratings. engineered thermoset composite resins, which has Operation outside of these ratings could result in death, high-strength structural properties, excellent dielectric bodily injury, or property damage. characteristics, and arc-tracking resistance. The drawout IZM63 / IN63 circuit breaker is a through- the-door design having three breaker positions with the compartment door closed (CONNECT, TEST, DISCONNECT) and one position out of its compartment on extension rails (REMOVE). The operating mechanism is a two-step stored energy mechanism, either manually or electrically operated. IZM63 Figure 1-1 IZM63 / IN63 low voltage circuit breakers (5000-6300A) IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn 1
Section 1: Introduction 1-2 Safety features WARNING IZM63 / IN63 circuit breakers and associated drawout equip- ment are manufactured with built-in interlocks and safety-re- Type IZM63 / IN63 circuit breakers are robust and are lated features. They are provided to reduce hazards to oper- provided with safety features. nevertheless, the voltages, ating personnel and provide proper operating sequences. currents, and power levels available in and around this equipment when it is in operation are extremely danger- ous and could be fatal. under no circumstances should interlocks and other safety features be made inoperative, A IZM63H3-V63W-1 as this may result in death, bodily injury, or property damage. B 6300A 1-3 Safe practices To protect personnel associated with the installation, operation, and maintenance of this equipment, the following practices must be followed: C 1. Only qualified electrical personnel familiar with the equipment, its operation, and the associated haz- ards should be permitted to work on the equipment. Additionally, only qualified personnel should be permitted to install or operate the equipment. 2. Always be certain that the primary and secondary D circuits are de-energized or the circuit breaker is removed to a safe work location before attempting any maintenance. 21 3. For maximum safety, only insert a completely assem- bled breaker into an energized cell. 4. Always ensure that drawout circuit breakers are in one of their designed cell positions, such as CONNECT, TEST, DISCONNECT, or REMOVE. A circuit breaker per- A) Low Voltage Air Circuit Breaker Family Name mitted to remain in an intermediate position could result B) Breaker Family Size in Amperes in control circuits being improperly connected, resulting C) Interrupting Capacity Rating in electrical failures. D) Factory Equipped Accessories 1-4 Qualified personnel For the purpose of operating and maintaining low voltage air Figure 1-2 Typical IZM63 / IN63 nameplate circuit breakers, a person should not be considered qualified if the individual is not thoroughly trained in the operation of the circuit breaker and how it interfaces with the assembly in which it is used. For the purpose of installing and inspecting circuit breakers and their associated assembly, a qualified person should also be trained with respect to the hazards inherent to working with electricity and the proper way to perform such work. The individual should be able to de-energize, clear, and tag circuits in accordance with established safety practices. 2 IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn
Section 2: Receiving, handling, and installation Section 2: Receiving, handling, and installation 2-1 General information IZM63 / IN63 air circuit breakers, when supplied as part of an assembly, may be shipped already installed in their respective breaker compartments. Receiving and handling of this equipment is addressed in an assembly instruction manual supplied with the assembled equipment. This instruction booklet applies to only the circuit breakers. Shipping 2-2 Suggested tools clamp A large number of different tools are not required to properly install and maintain circuit breakers. The following tools are, however, suggested: • Flat-blade screwdriver Figure 2-1 Shipping clamps for drawout circuit breaker • Phillips head screwdriver • 3/8-inch socket (ratchet) wrench On empty cassettes, remove the four or five lag screws and/or machine screws that pass through the floor pan of • 10 mm socket the cassette holding it to the wooden pallet. On drawout • 17 mm socket breakers shipped in a cassette, first remove the breaker from the cassette using the levering mechanism and • Secondary wiring removal tool drawout rails. After the breaker is removed, the machine screws passing through the floor pan can be removed. On fixed breakers, remove the lag screws passing through the 2-3 Unpacking circuit breaker mounting feet that hold the breaker to the pallet. Circuit Before beginning to unpack new IZM63 / IN63 circuit breakers are designed to be easily lifted from the wooden breakers, read and understand these directions. Following pallet using an appropriate lifting yoke and an overhead or a the directions will ensure that no damage is caused. portable lifting device. Shipping containers should be inspected for obvious signs of rough handling and/or external damage incurred during 2-3.1 Storing circuit breaker the transportation phase. Record any observed damage for reporting to the transportation carrier and Eaton, once the If it is necessary to store a circuit breaker before installation, inspection is completed. do so in its original shipping container. Keep the circuit breaker in a clean dry place. Ensure that there is ample air All reports and claims should be as specific as possible and circulation and heat, if necessary, to prevent condensation. It include the order number and other applicable nameplate is very important that the circuit breaker not be exposed to information. Every effort is made to ensure that circuit dirt or moisture. breakers arrive at their destination undamaged and ready for installation. Care should be exercised, however, to protect the breakers from impact at all times. Do not NOTICE remove protective packaging until the breakers are ready for A circuit breaker that has been stored for any length of time inspection, testing, and/or installation. should be operated a minimum of five times before it is When ready to inspect and install the circuit breaker, placed in service. carefully remove the banding straps and lift off the cardboard box. Remove any additional packing material and internally packed documentation. The circuit breaker and/or cassette are mounted to a wooden shipping pallet. On drawout circuit breakers shipped without a cassette, two shipping clamps hook into the breaker side plates and are held to the pallet with four lag screws (Figure 2-1). Remove the lag screws and clamps. Save the screws and clamps for future shipment of the breaker. IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn 3
Section 2: Receiving, handling, and installation 2-4 Lifting circuit breaker Table 2-1 IZM63 basic circuit breaker weights CAUTION Weights (kg) Weights (kg) Fixed Drawout Do not attempt to lift circuit breakers with ordinary crane hooks, ropes, chains, or other such devices. Failure to follow Breaker model 3P 4P 3P 4P this caution could result in damage to vital parts, such as arc IZM63N…50… 125.20 163.30 157.40 200.00 chutes, barriers, and wiring or the entire circuit breaker. IZM63N…63… 125.20 163.30 157.40 200.00 IZM63H…50… 125.20 163.30 157.40 200.00 To closely examine, install, or just become more familiar with IZM63H…63… 125.20 163.30 157.40 200.00 the circuit breaker, carefully lift and place the circuit breaker on a solid work surface capable of handling the circuit break- er’s weight (Table 2-1) or on the captive drawout extension rails of the breaker compartment. This is accomplished by using the appropriate lifting yoke and lifter. The lifting yoke consists of two steel hooks specially shaped to hook under the integral molded lifting handles on both sides of the cir- cuit breaker. Every effort should be made during lifting to minimize circuit breaker swing and tilt. If the circuit breaker is to be lifted onto compartment exten- sion rails, follow the instructions in Section 2-7, “Installing drawout circuit breaker.” 2-5 Circuit breaker inspection All circuit breakers, once removed from their shipping containers, should be visually inspected for any obvious damage. The current rating of the rating plug installed in the trip unit should match the current rating of the sensors mounted on the lower primary stabs of the circuit breaker. Check to make sure that this match exists. The sensor rating can be viewed through the viewing windows at the rear of the circuit breaker (Figure 2-2). 4 IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn
Section 2: Receiving, handling, and installation Molded rail supports Extension rail cutout Figure 2-2 Rear view showing current sensor rating Figure 2-3 One side of drawout circuit breaker properly through viewing window seated on extension rail 2-6 Adapting cassette The rejection interlocks are steel pins in the floor of the Drawout circuit breaker cassettes are built and shipped in circuit breaker cassette. As the circuit breaker is pushed a “basic” configuration that can be adapted in the field to into the structure, the mating pins on the bottom of the mate with specific circuit breakers. Specifically, the rejection circuit breaker move past a set of corresponding pins in the interlock must be configured to the specific circuit breaker cassette if the circuit breaker and cassette are compatible. to be mated with the cassette, and the automatic secondary If the circuit breaker and the cassette are mismatched, the connections may have to be installed or upgraded. These rejection pins will block the insertion of the circuit break- operations are described in the following sections. er into the cassette before the levering-in mechanism is engaged. Before attempting to push the circuit breaker into the 2-6.1 Rejection interlocks DISCONNECT position, compare the positioning of rejection Within any one physical frame size, the drawout circuit interlock pins in the cassette with the information supplied breakers come in a variety of continuous current and on the circuit breaker’s nameplate. Proceed if the circuit interruption ratings, some of which are incompatible with breaker and the cassette are compatible. others. Double-wide circuit breakers also come with several phase sequence options that are also incompatible. To prevent the insertion of circuit breakers with (1) inadequate 2-6.2 Installing secondary jumpers interrupting capability, (2) with physically incompatible On drawout and fixed circuit breakers, the automatic primary disconnects, or (3) with an incompatible phase secondary connector between the circuit breaker and the sequence, rejection interlock key plates are provided on cassette is coming as a complete set of control circuit both the circuit breaker and the cassette. The key plate terminals (Terminal blocks and jumpers wires installed); on the circuit breaker is pre-assembled at the factory; but These parts can be ordered separately and installed by the the cassette-side rejection plate and key pattern must be customer well. If the necessary connections are not pre- assembled and installed by the switchboard builder. installed, please contact an Eaton representative. These kits can also be used to add additional secondary wiring to CAUTION upgrade circuit breakers in the field. Do not disable rejection interlocks. Doing so and using a lower capacity circuit breaker in an incompatible cassette could result in an electrical fault that could result in death, bodily injury, and/or equipment damage. IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn 5
Section 2: Receiving, handling, and installation 2-7 Installing drawout circuit breaker 2-7.1 Circuit breaker positioning In structures equipped for drawout circuit breakers, a bolted- The IZM63 / IN63 drawout circuit breaker has four normal in cassette with movable extension rails supports the circuit positions: breaker. The extension rails must first be pulled all the way out. Once the rails are fully extended, the circuit breaker can • REMOVE (withdrawn) (Figure 2-4) be carefully placed on the extension rails. • DISCONNECT (Figure 2-5) • TEST (Figure 2-6) CAUTION • CONNECT (Figure 2-7) It is important to take great care when placing a drawout cir- cuit breaker on its extension rails. If the circuit breaker is not The REMOVE position is a position outside the compart- properly seated on the extension rails, it could fall from the ment on the cassette’s drawout rails where the circuit rails, causing equipment damage and/or bodily injury. breaker is not engaged with the levering mechanism. The DISCONNECT, TEST, and CONNECT, positions are reached Carefully lower the circuit breaker down onto the extension by means of the levering mechanism. rails. Be certain that the circuit breaker’s four molded dra- wout rail supports are fully seated in the extension rail With the breaker solidly positioned on the cassette’s cutouts on both sides (Figure 2-3). Do not remove the extension rails and levering-in mechanism in the lifting yoke from the circuit breaker until it is properly DISCONNECT position, carefully and firmly push the circuit seated on the rails. breaker into the compartment as far as it will go. The outer (recessed) portion of the circuit breaker faceplate should Once the circuit breaker is on the extension rails and the align with the GREEN target line (labeled DISC) on the inside lifting yoke is removed, proceed with the rest of the circuit top-left wall of the cassette (Figure 2-8). breaker installation. Compartment Secondary Connection Front Door Not Made Rear of Compartment Circuit Primary Breaker Connections Side View Not Made Circuit Breaker Out of Compartment On Extension Rails • No Electrical Connections Made • Breaker On Extension Rails • Remove or Inspection Position Figure 2-4 REMOVE position 6 IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn
Section 2: Receiving, handling, and installation Secondary Connection Not Made Rear of Compartment Compartment Front Door Circuit Primary Breaker Connections Side View Not Made • Only Ground Connection Made • Breaker Still Behind Door • Typical Storage Position Figure 2-5 DISCONNECT Position Secondary Connection Made Rear of Compartment Compartment Front Door Circuit Breaker Primary Side View Connections Not Made • Breaker and Trip Unit Testing • Primary Connection Not Made • Secondary and Ground Connections Made Figure 2-6 TEST position IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn 7
Section 2: Receiving, handling, and installation Secondary Connection Made Rear of Compartment Compartment Front Door Circuit Breaker Primary Side View Connections Made • Full Breaker Operation • Primary, Secondary, and Ground Connections Made • Fully Racked into Cassette (compartment) Figure 2-7 CONNECT position CAUTION 2-7.2 Levering circuit breaker The circuit breaker is now ready to be levered. With the Make certain that the circuit breaker is fully inserted into its circuit breaker OPEN, the levering device access door can compartment before any attempt is made to lever the circuit be raised. The levering device is hand operated using a breaker. Attempting to lever the circuit breaker in before it is standard 3/8-inch square drive and ratchet, which is not fully positioned inside its compartment can result in damage provided (Figure 2-9). As long as the levering access door to both the circuit breaker and the compartment. is raised, the circuit breaker is held trip-free. Begin by rotating the levering-in screw to the full counterclockwise (DISCONNECT) position. Close the compartment door and begin levering the break- er into its different positions using a clockwise ratcheting motion. The circuit breaker can be levered with the compart- ment door open or closed, but it is advisable to close the door prior to levering. The position of the circuit breaker within its compartment is indicated by color-coded position indicators (red = Connect, yellow = Test, green = Disconnect) (Figure 2-12). When the circuit breaker is levered fully to the DISCONNECT or CONNECT position, the levering shaft hits a hard stop; do not exceed 34.2 Nm of torque or the levering mechanism may be damaged. To remove the circuit breaker from its compartment, follow the procedure just described using a counterclockwise ratcheting motion. NOTICE The circuit breaker mechanism is interlocked such that charged closing springs are automatically discharged if the circuit breaker is levered into or out of the cell. Discharge Figure 2-8 Cassette label showing disconnected, test, takes place between the DISCONNECT and the TEST and connected position of recessed cover position. 8 IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn
Section 2: Receiving, handling, and installation Drawout cassette Drawout circuit breaker dimensions A drawout circuit breaker is used in combination with a fixed The drawout circuit breaker connects to the fixed primary drawout cassette (Figure 2-9); the drawout circuit breaker is stabs of the drawout cassette through the primary finger equipped with automatic primary disconnects (Figure 2-10). clusters attached to the rear of the circuit breaker. Two dif- The cassette provides all of the necessary interfaces to the ferent frame sizes cover all circuit breakers from an overall drawout circuit breaker, including automatic primary and sec- dimensional standpoint. ondary connections. For the IEC circuit breaker, a cassette style using horizontal stabs and horizontal customer busbar terminals is available as standard (Figure 2-11). The cassette terminal connections can be adapted to vertical busbar connections with a variety of optional vertical adapters. Mounting locations for cell (TOC) switches, safety shutters, mechanical interlocks, and key interlocks are provided on the cassette. Figure 2-9 Drawout circuit breaker in cassette Figure 2-10 Drawout circuit breaker with automatic pri- mary disconnects IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn 9
Section 2: Receiving, handling, and installation 4 3 6 (Front View) 9 2 1 Extension Rails 2 2 Extension Rail Cutout 9 1 1 3 Secondary Plug-in Connectors 7 4 Secondary Terminal Blocks 8 5 Arc Hood 6 Optional Cell (TOC) Switch 4 7 Optional Key Interlock 8 Earthing Bar 5 9 Open Safety Shutters 10 Primary Terminals 6 (Rear View) 10 7 10 Figure 2-11 Drawout cassette features (front and rear views) 10 IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn
Section 2: Receiving, handling, and installation Mounting foot Figure 2-12 Levering position indication Figure 2-13 Typical fixed circuit breaker 2-8 Fixed circuit breaker The fixed-type circuit breaker differs from the drawout ver- sion in that it has no levering device, primary disconnects, and secondary disconnects (Figure 2-13). In addition, a fixed circuit breaker does not have a standard feature to hold the breaker in a trip-free position. Fixed circuit breakers can be mechanically interlocked using either the optional key inter- Vertical lock (that is mounted through the front panel) or with Horizontal connection optional cable interlocks that operate on the tripper bar connection (Figure 3-1). Circuit breaker terminals have holes for making bolted hor- izontal primary bus connections. Adapters are available for making vertical primary bus connections. Secondary con- nections can be made through standard terminal blocks or a special connector compatible with the drawout circuit break- er’s type secondary connector. Both secondary connection devices are mounted at the top front of the circuit breaker. The fixed circuit breaker frame has two mounting feet, one on each side, to permit the fixed circuit breaker to be securely mounted. Each mounting foot has two slotted mounting holes that are used to bolt the circuit breaker securely in place. Use either M10 or 3/8-inch bolts for this purpose. Refer to the dimensional drawings referred to in Figure 2-14 Fixed circuit breaker with available vertical Section 5 “Fixed circuit breakers” for circuit breaker and bus adapter stab dimensions. NOTICE startup. To check circuit breaker operation, follow the oper- ational procedures outlined in Section 3 for both manually Refer to the circuit breaker weights in table 2-1 to ensure operated and electrically operated circuit breakers. that the panel on which a fixed circuit breaker is to be mounted is capable of supporting the weight. Fixed circuit breaker dimensions 2-9 Circuit breaker operation The standard fixed circuit breaker is supplied with Circuit breakers should be operated manually and/or elec- horizontally mounted primary connections (Figure 2-14). trically before they are put into service. This can be done Optional vertical primary adapters are available for different during the installation process or some later date prior to bus configurations. IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn 11
Section 2: Receiving, handling, and installation 2-10 Technical data Ambient temperature Derating coefficients are given in the table below when the circuit breaker is operating at different internal ambient tempera- tures inside the panel. The ambient temperature inside the panel is determined with IEC8900, calculation methods or equivalent methods. Rated currents of the circuit breakers at different ambient temperature Continuous Ambient temperature (°C) current A Breaker model 40 45 50 55 60 70 IZM63 5000A 5000 5000 5000 5000 5000 5000 IZM63 6300A 6300 6300 6200 6000 5600 5100 Bus bar dimensions The bus bar sizes are shown in the table below. This table uses data specified by IEC 60947-1 or obtained by Eaton in their circuit breaker testing. They are 3-meter-long bus bars with the faces vertical and painted flat black. For other bus bar config- urations, larger bus bar sizes may be required or the breaker may have to be de-rated. Refer to the table (Rated currents of the circuit breakers at different ambient temperature) presented in this section for de-rating information at higher ambient temperature. Two example diagrams are recommended below. Max. operating current A Circuit breaker frame size Recommended bus bar quantities and sizes (ambient temperature 40°C) (IZM63) (mm) (In) 5000 50 (5) 10 x 100 (5) .25 x 6 6300 63 (6) 10 x 100 (6) .25 x 6 (T) (5mm) ) ) T = Thickness of bus bar (W m (60m w = Width of bus bar 2 stacked 5mm × 60 mm bus bars to carry 800A Example 1 Example 2 12 IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn
Section 2: Receiving, handling, and installation Derating factors IZM63 / IN63 circuit breakers can be applied at their full voltage and current ratings up to a maximum attitude of 2000 meters above sea level. When installed at higher attitudes, the ratings are subject to correction factors. Rated short-circuit current is not affected as long as the voltage is rated in accordance with the table below. Power consumption data It is recommended to use IZM63 / IN63 resistance and power consumption data table, calculated to IE (890) temperatures. Altitude derating factors IZM63 / IN63 resistance and power consumption data Altitude (m) Voltage Current Breaker frame RDC RDC AC watt loss AC watt loss correction correction (mW/pole) (mW/pole) (3 pole sum) (3 pole sum) 2000 1.000 1.000 Fixed type Drawout type Fixed type Drawout type 2150 0.989 0.998 IZM63N3..V/P50 4 10 400 1000 2300 0.976 0.995 IZM63H3..V/P50 4 10 400 1000 2450 0.963 0.993 IZM63N3..V/P63 4 10 620 1550 2600 0.950 0.990 IZM63H3..V/P63 4 10 620 1550 2750 0.933 0.987 Based on RAC/RDC = 1.30, the total loss is under the full rated current. 2900 0.917 0.983 3050 0.900 0.980 3200 0.883 0.977 3350 0.867 0.973 3500 0.850 0.970 3650 0.833 0.967 3800 0.817 0.963 3950 0.800 0.960 5000 0.700 0.940 IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn 13
Section 2: Receiving, handling, and installation Electrical clearance The following information about electrical clearance is intend- ed to provide a guideline for the installation of fixed type or drawout type circuit breakers in an enclosure. The diagram and related dimensions can be used for reference. Electrical clearance dimension (mm) Breaker Enclosure To insulated To grounded With cell type clearance surface metal surface switch or locking facilities Withdrawable A 0 0 0 B 25 25 25/75 Fixed A 150 250 - B 30 70 - Recommended safety clearances 100 A A Cell switch (optional) B B Locking facilities (optional) Ventilation openings (do not cover!) Recommended enclosure clearance and ventilation The typical enclosure drawing and dimension table is intend- W Top or rear vent ed as a guideline for designing a circuit breaker enclosure. V The enclosure dimensions and required ventilation openings should be considered at the designing phase. Recommended enclosure/ventilation opening dimen- H sions W Width Width of cassette + 75 mm H Height 550 mm D Depth 450 mm (front control panel bay) V Ventilation holes 320 cm² (4000-6300A) D V Rear or lower vent 14 IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn
Section 3: Circuit breaker description and operation Section 3: Circuit breaker description and Double-wide frame circuit breakers use six (or eight) sets of rear primary connections; these circuit breakers are available operation from the factory with several different phase sequences. The phase sequence is also labeled on the rear of the circuit breaker (Figure 3-3). For drawout breakers, phase sequence 3-1 Introduction labels are also supplied with the cassette and must be IZM63 / IN63 circuit breakers are available in two physical applied by the switchgear builder. Circuit breakers with dif- frame sizes and in both drawout and fixed mounting config- ferent phase sequences are not interchangeable. Drawout urations (Figure 3-1 and Figure 3-2). A majority of features breakers with differing phase sequence are prevented from are common to both configurations, and will be discussed insertion into the cassette by properly assembled rejection in this section. The mounting features unique to the drawout key plates (see Section 2-6.1). and the fixed configurations will be covered individually in Sections 4 and 5 respectively. Controls and indicators for both drawout and fixed circuit breakers are functionally grouped on the front of the circuit breaker. The front escutcheon (faceplate) covers all continuous current ratings through 6300A. 6 Primary disconnect finger cluster 1 7 Arc chamber 5 8 8 Tripper bar 9 Levering device bearing plate 4 10 Padlockable levering device access door 3 11 Circuit breaker nameplate 11 10 9 2 1 5 7 6 1 Baffled arc chute cover 4 2 Secondary disconnects (contacts) 3 Faceplate (front cover) 4 Drawout rail supports 5 Integral lifting handle 6 9 Figure 3-1 Typical double-wide drawout circuit breaker features (front and rear views) IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn 15
Section 3: Circuit breaker description and operation 1 6 Fixed primary terminal (with optional vertical adapter) 7 Arc chamber 4 10 8 Mounting foot 9 Circuit breaker nameplate 10 Tripper bar 9 3 8 2 1 4 1 Baffled arc chute cover 7 2 Secondary disconnect 6 5 3 Faceplate (front cover) 4 Integral lifting handle 5 Fixed horizontal primary terminal Figure 3-2 Typical fixed circuit breaker features (front and rear views) 16 IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn
Section 3: Circuit breaker description and operation 1 4 10 3 6 Arc chamber 8 7 Mounting foot 8 Circuit breaker nameplate 7 9 Phase identification labels 10 Tripper bar 2 1 1 Baffled arc chute cover 4 2 Secondary contact connector 3 Faceplate (front cover) 6 9 9 9 9 10 4 Integral lifting handle 5 Fixed vertical primary terminals 5 (with optional vertical adapter) 7 Figure 3-3 Typical double-wide standard frame fixed circuit breaker features (front and rear views) IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn 17
Section 3: Circuit breaker description and operation 2 3 1 4 5 6 7 14 13 8 9 11 10 1 Trip flag (pop-out indicator) 8 Manual charge handle 2 Three accessory windows 9 Optional operation counter 3 Trip unit 10 Padlockable levering device access door for drawout breaker 4 Contact status (open-close) 11 Color-coded breaker position indicator 5 Spring status (charged-discharged) 12 Nameplate 6 Manual OFF button (push) 13 Trip unit test port 7 Manual ON button (push) 14 Trip unit cover. Plastic cover is provided which allows the settings to be viewed but not changed. Figure 3-4 Typical double-wide drawout circuit breaker front cover 18 IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn
Section 3: Circuit breaker description and operation 3-2 Basic circuit breaker assembly 2 (Case) IZM63 circuit breakers use a rigid frame housing construc- 1 (Front cover) tion of engineered thermoset composite resins. This con- struction provides high-strength structural properties, excel- lent dielectric characteristics, and resistance to arc tracking. The three-piece construction approach provides support while isolating and insulating power conductors. A two-piece engineered thermoset composite resin case encloses current paths and arc chambers. The chambers act to channel arc gases up and out of the circuit breaker during interruption. The operating mechanism sits on the front of the case and is electrically isolated and insulated from current contact struc- tures. It is covered by an insulating front cover. 3-3 Operating mechanism The IZM63 / IN63 operating mechanism is based on the proven cam and spring design. It is easily accessed by removing few cover screws and the front cover (Figure 3-6). The mechanism is a two-step stored energy mecha- nism. Potential energy is stored to close the circuit breaker. Figure 3-5 Typical construction (right side view) Sufficient energy to open the circuit breaker remains avail- able after a closing operation. 1 Secondary wiring points 1 2 Field installable accessories (3 maximum) 3 Trip unit 2 4 Electric charging motor 3 5 Manual charge handle 5 6 Operations counter (optional) 7 Padlockable levering device access door 6 8 Breaker position indicator 4 8 7 Figure 3-6 Electrically operated drawout circuit breaker with front cover removed IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn 19
Section 3: Circuit breaker description and operation 3-3.1 Manual operation 3-3.2 Electrical operation On manually operated circuit breakers, the closing spring For electrically operated circuit breakers, the springs are can only be charged manually. To manually charge the spring, normally charged through the use of an electrical operator insert one finger in the recess behind the charging handle (Figure 3-8). The springs can, however, be charged manually and pull out. This permits a gloved hand to grasp the handle as just described in the previous paragraph(Figure 3-7). and begin charging. It takes from five to seven downward strokes on the charging handle to complete the manual Like the manually operated circuit breaker in the previous charging process. It is possible to manually recharge the paragraph, electrically operated circuit breakers can also spring immediately after closing the circuit breaker and be manually closed and opened through the use of the before it has been tripped open. Standard manually operated front-mounted Manual ON and Manual OFF buttons. circuit breakers are closed and opened by hand using the An electrically operated circuit breaker from the factory is Manual ON and Manual OFF buttons respectively located on also equipped as standard with a spring release to close the the front of the circuit breaker (Figure 3-4). circuit breaker electrically. An optional shunt trip and under- Performing either operation is accomplished by pressing and voltage release are also available to trip (open) an electrically releasing the appropriate button. Access to these pushbut- operated circuit breaker. Refer to Section 4-1 for more details tons can be limited by the use of an optional, padlockable on both standard and optional devices. cover. In addition, complete access to the ON button can be prevented with an optional prevent close cover. The status of the springs and the primary contacts is always indicated in 3-3.3 Anti-pump feature an indicator window just above the pushbuttons. The circuit breaker has both mechanical and electrical antipump features. If the circuit breaker is closed on a Electrically operated optional devices are available to auto- fault condition (and trips open while the CLOSE signal is matically close or trip a manually operated circuit breaker. An maintained), using either the mechanical pushbutton or electrical spring release is available to close a manually oper- the electrical close coil, it will not make another attempt to ated circuit breaker. Two optional devices, a shunt trip, and close until the close command is removed and reapplied. an undervoltage release, are available to automatically trip For electrical closing, a Latch Check Switch (LCS) option (open) a manually operated circuit breaker. These optional is available (see “Plug-in electrical accessories” on page devices can be installed easily in the field. For more details 35) that will block the application of the electrical close on these devices, refer to Section 4-1 and 4-2 in this booklet. command until the breaker is ready to close (Section 4-1). An electrical operator that is used to charge the closing spring automatically can be added to a manually operated circuit breaker in the field (Figure 3-8). Manually operated cir- cuit breakers are pre-wired to accept this addition. Figure 3-7 Electrical motor operator to charge closing Figure 3-8 Charging motor can be installed in the field spring (installed) 20 IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn
Section 3: Circuit breaker description and operation 3-4 Electronic tripping system Table 3.1 Series PXR trip units. Series IZM63 / IN63 circuit breakers use a three-part tripping Functions PXR 20 PXR 25 system: LSIG protection Yes Yes • Microprocessor-based trip unit connected to a frame rat- Disable (I) Yes Yes ing module; GF protection Option Option • Rogowski coil type current sensors; and GF alarm Option Option • Trip actuator. Display Yes Yes Programmable No No All three parts of the tripping unit are discussed here in general. For detailed information pertaining to the different Current metering Yes Yes available trip unit models and other breaker or accessory Power/energy metering No Yes information, refer to PXR release instruction leaflet. Power quality metering No No See important frame rating module information on next Communication Yes Yes page regarding the tripping system. 3-4.1 Microprocessor-based trip unit 3-4.2 Rating plug Series IZM63 / IN63 circuit breakers utilize the PXR family of A rating plug is not required with PXR trip units. See frame electronic trip units whose main features are summarized in rating module description. Table 3.1. The electronic trip units are self-powered devices. The pro- tection settings can be set from the front panel. When the 3-4.3 Current sensors circuit breaker is closed, no external power is required to Rogowski coil type current sensors are installed on the operate their protective systems. Current signal levels and load terminals at the bottom rear of the circuit breaker. The the control power are derived from the current sensors. All sensors furnish the trip unit with a signal and the energy trip units are true RMS current sensing devices. required to trip the circuit breaker. A functional local test of the trip unit’s primary electronic cir- An external neutral current sensor is available for customer cuitry and the circuit breaker’s mechanical tripping action can installation, and must be ordered separately. be performed through the trip unit’s USB receptacle. 3-4.4 Frame rating module The PXR frame rating module is mounted just behind the trip unit and stores data related to the breaker’s ratings (includ- ing the maximum continuous RMS current), manufacturing information, and health of the breaker frame. The interchangeable trip unit attaches to the permanent frame rating module. Since the PXR trip unit no longer requires a fixed type rating plug, the continuous current (In) rating is factory programmed in the frame rating module. The programmed value of In is shown on the trip unit’s LCD display and printed on the Battery cover at the lower right corner of the trip unit. The In rating displayed and pro- grammed will be equal to or less than the breaker frame’s maximum rated current as listed on the nameplate. The breaker’s In rating can be re-programmed by interfacing with the USB port on the trip unit. Please contact your Eaton sales representative for details on proper re-programming of Figure 3-9 Installed PXR trip unit the trip unit. IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn 21
Section 3: Circuit breaker description and operation Frame rating modules installed on series 3-4.7 Non-automatic device IZM63 / IN63 air circuit breakers with PXR are perma- Series IZM63 / IN63 is available in a non-automatic configura- nent and SHOULD NEVER BE REMOVED. The frame tion. It is derived from the corresponding IZM63 / IN63 auto- rating module battery cover with printed In rating should matic breaker but does not include the trip unit, Rogowski not be changed without proper reprogramming of the coil type current sensors, and the high instantaneous trip trip unit. The In rating programmed from the factory feature. The overall dimensions and the capability of mount- is displayed in the lower left hand corner of the LCD ing most accessory items are maintained. Non-automatic screen whenever power is applied to the trip unit. The device are tested in keeping with IEC 60947-2 requirements. In displayed on the LCD reflects the actual In rating of the breaker, while the value on the battery cover is for reference only when the LCD is not powered. The In rat- 3-5 Secondary contacts and connection diagrams ing displayed on the LCD screen and In rating printed on A maximum of 96 secondary wiring connection points are the frame rating module battery cover MUST ALWAYS available on the standard frame circuit breaker each dedicat- AGREE. ed to a specific function. The wiring points are finger safe with no more than two wires per terminal. 3-4.5 Trip actuator The low-energy trip actuator is a small electromagnetic device that provides the necessary mechanical force to ini- tiate the tripping action of the circuit breaker. The electronic trip unit provides a pulse to the coil of the trip actuator, allowing the mechanical tripping action to take place. The trip actuator is reset by the operating mechanism. 3-4.6 Fixed high instantaneous non-adjustable trip Series IZM63 circuit breakers have a fixed instantaneous non-adjustable setting. This fixed instantaneous trip will initi- ate a trip at a high current peak which depends on the circuit breaker type and rating. This setting is always active, regard- less of the instantaneous setting. 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 ZCOM CMM1 2CMM CMM3 2CMM MODG OT1C PTVC OT1B MODB ARCO OT2C N1 ALMC E01 + + 24V PTVA G1 ALM2 ZIN E02 OT1M OT2B SC 2CMM N2 2CMM OT2M CMM2 MODB PTVN PTVB AGND CMM4 ARCO G2 ALM1 ALM3 ARMS ARCO ZOUT - 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95 C2 C3 B1 C1 C4 C5 B3 C6 B5 C11 C7 C8 C10 B11 C12 LCC UV1+ SR1 B7 C9 B9 LCB ST1 A1 A2 UV2 SR2 B2 LCM A4 A5 B10 A11 A12 A3 B4 ST2 B6 A6 A8 A10 B12 A7 B8 A9 - - 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 Figure 3-10 Secondary connector top view 22 IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn
Section 3: Circuit breaker description and operation Drawout type circuit breakers: Compatible secondary plug-in connectors are mounted on the top front portion of the drawout cassette (Figure 3-11). These connectors match and plug into the circuit breaker mounted connectors. Contact points are wired from the cassette’s plug-in connectors to cassette mounted terminal blocks. The terminal blocks are also mounted on the top front portion of the cassette. The secondary terminals have finger-proof hinged covers with small holes for probe testing. Fixed type circuit breakers: There are two secondary connection options: (1) Without terminal block Figure 3-11 Cassette-mounted secondary wiring (2) With terminal block 1. Without terminal block—If a terminal block for customer use is not required, the circuit breaker is supplied with both plug-in connectors (male and female) just described in the two previous paragraphs. The plug-in connectors are joined and attached to the top portion of the circuit breaker. The customer can plug secondary wiring with crimp-on connectors into the back of the plug-in connec- tors; subsequently the connections to the circuit breaker can be quickly joined or separated as required. 2. With terminal block—For those customers preferring to wire to a terminal block, terminal blocks with fin- Secondary terminal AMP secondary ger-proof hinged covers are added to the secondary wiring removal tool configuration just described for a fixed circuit breaker “without a terminal block.” The terminal blocks are wired to the plug-in connectors and also permanently attached Figure 3-12 AMP secondary wiring removal tool to the upper rear portion of the circuit breaker. A standard tool is available from the plug-in connector man- ufacturer (AMP) to facilitate the removal of secondary wiring from a plug-in connector, or contact Eaton for assistance (Figure 3-12). The connector halves must be separated to use this tool. IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn 23
Section 4: Dimensional drawings IZM63 / IN63 fixed type dimensions and horizontal board dimensions (3P, 5000~6300A) 24 IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn
Section 4: Dimensional drawings IZM63 / IN63 fixed type dimensions and horizontal board dimensions (4P, 5000~6300A) IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn 25
Section 4: Dimensional drawings IZM63 / IN63 fixed type panel cutout and external vertical board dimensions (3P and 4P, 5000~6300A) mounting hole Door panel Door cut out Max. distance to isolation surface Door panel mounting hole Door cut out 26 IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn
Section 4: Dimensional drawings IZM63 / IN63 Withdrawable Type Dimensions (3P and 4P, 5000~6300A) d e f Notes: de Drawer switch position f Recommended minimum mounting space IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn 27
28 6.50 165.10 11.50 292.10 Door cut out Mounting hole 19 Test position Connected position Section 4: Dimensional drawings Disconnected position Withdrawn position Mounting hole Door cut out Mounting hole 0 12.7 54 Mounting hole 76.2 Front View Right View 527.1 IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn IZM63 / IN63 withdrawable type panel cutout dimensions (3P and 4P, 5000~6300A) Panel cutout size and circuit breaker position Note: 1. Mperial dimensions are Inches on top metric dimensions are [mm] bottom. 2. All dimensions are reference only 3. Tolerance range is shown as follow:
Required mounting locations Ø11 6 places 384.1 Preferred mounting positioning Ø11 6 places 10.2 177.8 177.8 120.7 177.8 177.8 38.1 Mounting plane Rear view 210 621.5 143.2 Mounting plane Optional mounting locations Ø.32 [Ø8.2] 2 places Earth contact access hole Ø22.4 25.4 279.4 Optional earth bus mounting 231.9 location. replace existing Required mounting 25.4 with M8x25 hex. bolts for locations use with 1/4 ( 6mm) bus Ø.32 [Ø8.2] 4 places IZM63 / IN63 withdrawable type cassette dimensions and mounting dimensions (3P, 5000~6300A) 4 x 8.9 6.4 4 x 19.1 322.5 153.6 4 x 13.5 322.5 IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn 50.3 Bottom view 3 pole mounting locations 29 Section 4: Dimensional drawings
30 Ø11 6 places Section 4: Dimensional drawings 384.1 Preferred mounting positioning Ø11 6 places 10.2 241.3 241.3 120.7 241.3 241.3 38.1 Rear view Mounting plane 337 475.5 475.5 127.8 41.6 Mounting plane Preferred mounting positioning Ø8.2 4 places Earth contact access hole 25.4 Ø22.4 25.4 279.3 IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn 231.9 Required mounting locations Ø8.2 Optional earth bus mounting 4 places location. replace existing 4 x 13.3 with M8x25 hex. bolts for 6.4 4 x 19.1 use with 1/4 ( 6mm) bus 4 x 8.9 50.3 351.4 350 351.3 IZM63 / IN63 withdrawable type cassette dimensions and mounting dimensions (4P, 5000~6300A) Bottom view 4 pole mounting locations
Section 4: Dimensional drawings IZM63 / IN63 withdrawable type cassette horizontal board wiring dimensions (3P - 5000~6300A) Maximum distance 101.6 Busbar fixture Item IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn 31
Section 5: Protective characteristic curves Section 5: Protective Characteristic Curves IZM63 / IN63...V(P)...PXR20/25 Long Delay(L) and Short Delay(S) Curves L-Protection: I²t-Characteristic curve and S-Protection: Flat characteristic curve 10000 9000 8000 7000 6000 5000 4000 3000 2000 1000 900 800 700 600 500 400 300 200 100 90 80 70 60 50 Time in Seconds 40 30 24 20 15 10 9 0.5 8 1 7 7 6 5 4 10 2 4 2 3 2 3 2 1 7 1 4 5 .9 .8 1.5 .7 8 .6 2.5 .5 0.5 .4 0.4 .3 6 0.3 .2 0.2 .1 3 .09 .08 0.1 .07 .06 .05 .04 .03 0 .02 .01 100 10 20 30 40 50 60 70 80 90 1 2 3 4 5 6 7 8 9 .1 .2 .3 .4 .5 .6 .7 .8 .9 Current in Multiples of Long Delay Pickup (Ir) Notes: 1. Short slope: Flat, the actual pickup point has 100% ±10% tolerance. 2. Long delay I²T slopes flattens out at 6x of Ir. 3. Short time delay from 0(50ms) to 0.5s, with +0 / -80ms tolerance except 0.1s and 0s setting 0.1s setting, trip time is 0.06s to 0.1s 0s settting, nominal clear time is 60ms with auxiliary power and 120ms without. 4. If long delay thermal memory is enabled, trip times may be shorter than indicated in this chart. 5. Curves applies from -20°C to +70°C ambient. Temperatures above +85°C will cause over temperature trip. 6. This curve is for 50Hz, 60Hz applications. 7. These curves are comprehensive for series IZM63 / IN63 circuit breakers including all frame sizes, ratings, and constructions. The total clearing times shown include the response time for trip unit, the breaker opening and the interruption of the current 32 IZM63 / IN63 low voltage air circuit breaker MN013014EN May 2021 www.eaton.com.cn
You can also read