White Paper SSTI - VGB PowerTech
←
→
Page content transcription
If your browser does not render page correctly, please read the page content below
White Paper SSTI Consideration of possible impacts of the operation of HVDC systems in the grid on the shaft trains of turbine-generator sets in power plants 1st edition October 2020 Prepared by power plant operators in VGB PowerTech and by the German transmission system operators, with the involvement of universities and manufacturers As of 1 August 2021
Contents 1 Introduction, objective .......................................................................................... 5 1.1 Scope ............................................................................................................... 5 2 Overview of grid restructuring/grid modification due to HVDC systems .......................... 6 3 Necessary exchange of information (relevant HVDC systems, relevant transmission system operator, relevant power plant connections) ................................... 7 3.1 Objective .......................................................................................................... 7 3.2 Information exchange for the grid connection process ................................................. 7 3.2.1 Information exchange in the context of necessary studies ....................................... 7 3.2.2 Information exchange in the context of the operational notification procedure .................................................................................................... 8 3.3 Information exchange during the entire operational lifetime .......................................... 8 4 Analyses necessary for the study of SSTI phenomena in connection with HVDC systems .................................................................................................... 9 4.1 National and European regulations......................................................................... 9 4.2 Analyses ............................................................................................................ 9 4.2.1 UIF screening ............................................................................................. 10 4.2.2 Detailed analyses ........................................................................................ 11 4.2.3 Demands on the models ............................................................................... 13 4.3 Summary ......................................................................................................... 15 4.4 Brief description of models .................................................................................. 16 4.4.1 Shaft train models........................................................................................ 16 4.4.2 Equivalent circuit diagrams of generators for the calculation of SSTI ....................... 18 5 Requirements for HVDC controls and HVDC protection systems................................... 20 5.1 Introduction ...................................................................................................... 20 5.2 Definition of the basis for the classification of HVDC systems ...................................... 21 5.2.1 Technical design ......................................................................................... 21 5.2.2 Control systems used in terms of their application and the control modes utilized ............................................................................................ 22 5.2.3 Specifications of the Europeans rules and regulations ......................................... 22 5.2.4 Standards applied to the operation of turbomachinery and generators ................... 23 5.2.5 Control and protection tasks in relation to the avoidance of torsional vibrations................................................................................................... 23 5.3 I&C design concepts for control............................................................................ 25 5.3.1 Concepts utilized for control .......................................................................... 25 5.3.2 Monitoring of control (e.g. self-monitoring for hardware faults) .............................. 25 5.3.3 Assumed faults and conditions and constraints for the design of a robust control ........................................................................................... 25 3
5.4 Measures intended to verify the robustness of the control ........................................... 25 5.4.1 Necessary input criteria ................................................................................ 25 5.4.2 General requirements for software testing (scenarios and assumed faults) ................ 26 5.4.3 Consideration of the interaction between different HVDC systems ......................... 26 5.4.4 General requirements for hardware tests .......................................................... 26 5.4.5 Feedback effect on power plant control ........................................................... 26 5.5 Classification and recommendations for damping sub-synchronous resonances....................................................................................................... 27 5.5.1 Classification of HVDC systems ...................................................................... 27 5.5.2 Definition of recommendations for assuring the robustness of the overall system ........................................................................................ 28 6 Literature .......................................................................................................... 29 7 List of abbreviations ........................................................................................... 31 8 List of figures..................................................................................................... 33 9 Annex ............................................................................................................. 34 10 Authors ............................................................................................................ 41 As of 1 August 2021: Update of the list „power plants, page 38, and maps „HVDC connection nodes“, pages 39 and 40. 4
1 Introduction, objective As the feed-in of renewable energy increases, the number of power electronic control elements in Europe, and especially in Germany, also increases, and power generation by thermal power plants decreases. Electricity transport by high-voltage direct current (HVDC) transmission is becoming increasingly important with the growing use of both offshore and onshore wind turbines. The grid topology also changes accordingly. In the following the aforesaid technical facilities are subsumed under the heading “HVDC systems”, unless a deliberate distinction is required. Existing generation systems, e.g. thermal power plants and their control systems, interact with the controls of HVDC systems. Thermal power plants feature rotating (inertial) masses with the appurtenant control systems. HVDC systems can implement control processes quickly. The interaction of torsional vibrations of the shaft train of a power plant with other operating equipment connected via the transmission network, such as HVDC systems, is termed sub-synchronous torsional interaction (SSTI). If the design and parametrization of the engaged control systems do not take the characteristics of the other components into account, impermissible loads on the shaft trains of power plants can occur, among other things. Consequently, HVDC systems must be designed so safely that no additional negative loads on a power plant shaft train can result due to torsional vibration. To enable integrating HVDC transmission technology safely and uniformly into the grid, in August 2018 VDE|FNN published the application rule “Technical Connection Rule for the connection of HVDC systems and generation plants connected via HVDC systems”, in implementation of the current European Network Code High Voltage Direct Current (NC HVDC). This White Paper was jointly prepared by the German transmission system operators and power plant operators with the involvement of universities and manufacturers. It provides an overview of current grid modifications in the German transmission system. In addition, procedures and practices for the integration of HVDC systems through information exchange and cooperation between transmission system operators (TSOs), HVDC system operators and power plant operators are presented. Analyses necessary to verify the design of HVDC system controllers are described and explained. In conclusion, a brief overview of the demands on HVDC controls and protection systems is provided. This White Paper describes the fundamental relationships and provides joint recommendations for steps to avoid impermissible SSTI stresses. It creates a basis on which the parties involved (HVDC system operators, TSOs and power plant operators) should conclude project-specific agreements to make future energy supply, including the changes in store for it, robust and safe, and to enable proper feedback of experience from the operation of HVDC systems. Commercial expenditures possibly arising from the application of the White Paper are not dealt with in the paper and, if necessary, are to be agreed in the project between the involved parties. 1.1 Scope Electrical disturbances caused, for example, by switching action, short circuits or disruptions in the electrical system can induce torsional vibrations in the shaft trains of turbine-generator sets in power plants. The associated mechanical strain on the shaft depends both on the level, type and duration of the excitation and on its decay behaviour, i.e., on the properties of the coupled electromechanical vibration system. 5
In the case of natural torsional frequencies of the turbine-generator set in the sub-synchronous frequency range, interaction of the HVDC system with the power plant turbine-generator set via the surrounding grid is possible under certain conditions: In transmission systems with series compensation, the phenomenon of sub-synchronous resonance (SSR) can occur if the armature voltage components induced by sub-synchronous torsional vibration lie near a natural frequency of the series-compensated transmission system. Active network elements or control devices (e.g. voltage regulator and power system stabilizer, turbine governor, HVDC control, etc.) can give rise to the phenomenon of SSTI, in which case the active network elements influence the damping behaviour of the torsional vibrations. In the following the SSTI phenomenon is considered in connection with HVDC systems and the analyses necessary to avoid negative SSTI phenomena are shown. However, it is pointed out that: the SSTI phenomenon must not be considered as being exclusively connected with HVDC systems, but generally can be caused by active network elements. Examples are shown, inter alia, in [1]. active network elements can influence the damping behaviour of torsional vibrations both positively and negatively, whereas solely negative interactions must be avoided. 2 Overview of grid restructuring/grid modification due to HVDC systems The general overview (map and list) as of October 2020 of the installed and planned HVDC systems and flexible AC transmission systems (FACTS), contained in Annex 1, gives an impression of the expected local distribution of said systems and permits an initial assessment which power plants might be affected by an interaction. The precise marking of the effective radius of each HVDC system within which interaction can occur between the power plants lying within the radius and the HVDC system was not possible during the elaboration of this paper. A statement about this necessitates concrete analyses in project-specific studies. The 380 kV and 220 kV voltage levels are considered. Should anything be of relevance to the power plants on the underlying voltage level 110 kV, it is included in the analyses. For technical explanations the reader is referred to chapter 4, “Analyses necessary for the study of SSTI phenomena in connection with HVDC systems”. Notes: Unlike the other HVDC systems considered, the grid connection of onshore wind farms is not subject to VDE-AR-N 4131, but to VDE-AR-N 4130 for the connection of generating plants. The FACTS are independently constructed and operated by the transmission system operators based on valid VDE specifications and standards. Necessary studies are carried out, if need be, in consultation between the relevant transmission system operator and the relevant power plants. 6
3 Necessary exchange of information (relevant HVDC systems, relevant transmission system operator, relevant power plant connections) 3.1 Objective This section of the report is concerned with the necessary exchange of information between HVDC systems, power plants and, where applicable, other grid connections for the purpose of ensuring safe and reliable grid operation in regard to SSTI. 3.2 Information exchange for the grid connection process With VDE application rule VDE-AR-N 4131, requirements for HVDC systems contained in the “Commission Regulation (EU) 2016/1447 of 26 August 2016 establishing a network code on requirements for grid connection of high voltage direct current systems and direct current-connected power park modules” (NC HVDC) were implemented nationally. The NC HVDC lays down rules for, among other things, the provision of proof of the observance of minimum general technical requirements and for the necessary exchange of information between connectee and connection provider as well as the purposeful exchange of information on relevant parties. 3.2.1 Information exchange in the context of necessary studies The necessary exchange of information for grid studies pertaining to interactions is described in detail in VDE-AR-N 4131 in Section 10.1.19. The necessary exchange of information for grid studies on the damping of sub-synchronous vibrations is described in detail in VDE-AR-N 4131 in Section 10.1.21. In the framework of connection studies the relevant grid operator makes the following information available to the power plants relevant to the HVDC connection being newly established (“Type 1 generating plants” according to VDE-AR-N 4131), and ensures the cooperation of the relevant power plant operators: Information to the relevant power plant about the UIF screening results with which the detailed SSTI study will be conducted. This information should be provided to the affected power plants at the earliest possible time so that the required activities of the power plant operator can be included in the planning. Active involvement of the relevant power plants (according to UIF screening) in regard to duty points and power plant data for the detailed SSTI study. Time for handover of the relevant duty points and power plant data by the power plant operator for SSTI studies. It must be noted that procurement of the relevant data can take up to 18 months. Active involvement of the relevant power plants (according to UIF screening) in talks on the essential results of the SSTI study. Information exchange in regard to the grid studies (according to VDE-AR-N 4131 the HVDC system must meet the requirements throughout the entire operating range): o Operating range and scope of utilization cases o Duty points of relevant power plants and HVDC systems o The selection of relevant grid and power plant situations is largely the responsibility of the expert who makes the study. 7
Time of and invitation to the presentation and handover of the results of the SSTI study. It must be noted that measures of the power plant operator possibly will be derived, implementation of which requires a certain amount of time prior to commissioning of the HVDC system. Interleaving with chapter Grid restructuring/grid modification due to HVDC systems (see chapter 2): The relevant information about the locations of HVDC systems is available to the public through the Grid Development Plan Power and the Offshore Grid Development Plan Power, as amended: http://www.netzentwicklungsplan.de/en This information was supplemented and suitably edited in this White Paper. Interleaving with chapter Grid analyses (see chapter 4): The information exchange necessary for the described grid analyses is already covered by the specifications of VDE-AR-N 4131 Section 10.1.21. 3.2.2 Information exchange in the context of the operational notification procedure The necessary exchange of information upon commissioning of HVDC systems is described in detail in VDE-AR-N 4131 in Section 4.2.1. The following times of the operational notification procedure are to be communicated about 3 months in advance: Time of energization operational notification (EON) – energization of plant service equipment Time of interim operational notification (ION) – beginning of active use The following times of the operational notification procedure are to be communicated in advance: Probable time of final operational notification (FON) – beginning of intended operation Duration of limited operational notification (LON) – deviations from intended operation 3.3 Information exchange during the entire operational lifetime The necessary exchange of information upon repetition of parts of the demonstration of conformity of HVDC systems is described in detail in VDE-AR-N 4131 in Section 11.4. 8
4 Analyses necessary for the study of SSTI phenomena in connection with HVDC systems The control system of an HVDC system is effective inter alia in the frequency range of the sub- synchronous torsional vibrations and therefore can influence the damping of vibrations. According to VDE-AR-N 4131 it is the task of grid operators and technical systems manufacturers to ensure that the control system of the HVDC system does not exert any negative influence on the damping of the sub-synchronous torsional vibrations. The power plant manufacturers and power plant operators supply the necessary input data and contribute their experience to the investigations. The close collaboration of all parties involved is designed to avoid negative impacts of the HVDC system on the relevant power plants. The explanations in this chapter 4 refer exclusively to the sub-synchronous frequency range. Note: Studies have shown that electrical disturbances in general – for example, caused by short circuits – can induce torsional vibrations also in the super-synchronous frequency range and, in consequence thereof, blade vibrations. Excitation by HVDC systems in this frequency range, on the basis of current knowledge, is not known to occur. Should excitation by HVDC systems be demonstrated, for example by simulations or measurements, the document will be expanded to reflect this. 4.1 National and European regulations The type and scope of the analyses carried out in connection with SSTI are defined in: Commission Regulation (EU) 2016/1447 of 26 August 2016 establishing a network code on requirements for grid connection of high voltage direct current systems and direct current- connected power park modules (NC HVDC) [2] The Network Code in turn is the basis of the national regulations and application rule: VDE-AR-N 4131, Technical Connection Rule for the connection of HVDC systems and generation plants connected via HVDC systems [3] The requirements laid down in these sets of rules are binding upon entry into force. 4.2 Analyses Grid analyses for the avoidance of SSTI phenomena always are carried out in two steps: 1. Screening, i.e., identification of relevant power plant units that require detailed analysis 2. Detailed analysis of the relevant power plant units 9
4.2.1 UIF screening Of great importance for the assessment of the risk of SSTI is the relative size (rated capacity) of the HVDC system at the point of connection as compared with the rated capacity of the power plant unit under investigation:. ெಹೇವ ௌಸೠ ଶ ܷ ܨܫൌ ቀͳ െ ቁ ெಸಶಿ ௌಸ MVAHVDC : rated apparent power of HVDC system MVAGEN : rated apparent power of the generator/power plant unit under study SCGOUT : short circuit capability at the HVDC connection point without the generator under study SCGIN: short circuit capability at the HVDC connection point with the generator under study Major influence is exerted by the “electrical distance” between the HVDC system and the power plant unit. These factors are assessed by taking the ratio of the short circuit capabilities at the grid connection point of the HVDC system without and with the power plant unit concerned. From this the so-called unit interaction factor (UIF) is determined. With the aid of the UIF, the risk of the occurrence of SSTI can be assessed for power plant units as a function of the grid state (topology, feed-in and load scenarios). According to [4], for line-commutated HVDC transmission systems a UIF smaller than 0,1 is considered non-critical. A power plant unit to which this applies therefore does not have to be subjected to detailed analysis. The UIF analysis is performed taking into account various grid states (make matrix of grid states). For self-commutated HVDC systems there currently is no defined reference value. However, no specific (control) properties of the HVDC system enter into the formula for calculation of the UIF, shown above, so that initially the same reference value can be used for self-commutated HVDC systems. Under a worst-case scenario a safety factor of 10 is added, i.e., a UIF smaller than 0,01 currently is assessed as non-critical and necessitates no further analysis in detail. As soon as new findings are available in regard to these questions, the document will be modified accordingly. Screening with UIF is state of the art and the basis for identification of the power plant units requiring detailed analysis (see inter alia [1, 4]). The screening should factor in the development of the grid short circuit capability in the next few years, and the analysis should be performed in terms of a worst case estimate. Should the grid short circuit capability at the HVDC connection point become weaker after an SSTI study has been made, and this has not yet been recognized in the existing study, screening is to be performed again and, where appropriate, necessary measures taken. 10
4.2.2 Detailed analyses Various methods can be used for detailed analysis of the identified power plant units. The most important are: Small signal perturbation analysis in the time and/or frequency range Large signal perturbation analysis in the time range (instantaneous value range) for defined disturbance scenarios and excitations Small signal perturbation analysis (frequency screening) In the investigation of small signal perturbation, vibration is induced in the system starting from a defined duty point. In the literature this method frequently is referred to as “small signal perturbation analysis (SSPA)” or ΔMe/Δω analysis. Small signal perturbation can be analysed in both the frequency range and the time range. Excitation is achieved by injecting monofrequent signals in the speed governor (reference value application) of the power plant unit being analysed. Subsequently, in the air gap moment the damping component that originates in the electric grid is evaluated. The damping component of the electric moment is that part that is in phase with the speed deviation (see Figure 1). For this the electric grid is modelled both with and without HVDC system (at the same duty points and load flows). By comparing the results it is possible to assess the influence of the HVDC system on the electric damping in the frequency range that is of interest. For ΔMe/Δω analysis no detailed shaft train model is needed. The investigation traditionally is carried out using a single-mass oscillator, while the inherent mechanical damping of the machine is neglected. Note: The elimination of the sub-synchronous fractions from the polyfrequent signal in the low sub- synchronous frequency range is suitable only as screening method. For analyses in the frequency range, a linear model of the HVDC system validated by the technical system manufacturer must be used in the relevant sub-synchronous frequency range. For small signal excitation in the sub-synchronous frequency range, sufficiently high accuracy of the linear HVDC model must be ensured. The influence of the HVDC system on the sub-synchronous vibrations also can be analysed independently with the transfer function of the HVDC system. The evaluated real component corresponds to the damping effect of the HVDC system on a vibration in the three-phase system. This permits making a general statement as to which frequency range is critical or in which frequency range there is still need for action. Small signal perturbation analysis can be performed as pre-project study or in the engineering stage of an HVDC system. It does not entirely substitute for analysis in the time range (large signal behaviour). Small signal perturbation analysis also can be used as a frequency screening method. 11
Transfer function of mechanical system (single-mass oscillator) Transfer function of electrical system incl. HVDC Speed deviation Angular deviation Change in mechanical torque Change in electric moment Fig. 1: Principle of ΔMe/Δω analysis. Vibration is induced in the turbine-generator set by injecting a monofrequent extraneous signal in the speed governor. The component of the electric moment in phase with the speed deviation is then evaluated [inter alia 4]. Analysis of large signal behaviour in the time range For analysis of large signal behaviour, a detailed simulation model of the complete system (HVDC system, power plant unit, relevant electric grid environment) is used and is analysed for defined faults and excitations in the time range (instantaneous value range). For this analysis a mechanical shaft train model is needed which reflects the dominant natural modes of the shaft train (see chapter 4.4.1). The analysis in the time range makes allowance for defined system configurations (feed-in and load scenarios, grid topology, short circuit capability, duty points of HVDC system, etc.). It has to be shown that the parallel operation of generator and HVDC system, even under most unfavourable conditions and constraints (minimal short circuit capability, radial connection of power plant and HVDC system, most unfavourable duty points and operating states, etc.) is stable and non-critical in regard to SSTI. As disturbance or excitation, among other things short circuits in the AC grid, switching action in the AC grid, or changes in duty point of the HVDC system are assumed. By performing the analysis both with and without HVDC system (at the same duty points and load flows), it is possible to assess the influence of the HVDC system on the damping of the torsional moments. Assessment of the damping of the torsional moments calculated in the time range is made difficult by the superposition of different modes. It therefore makes good sense to transform the torsional moments between the individual masses of the shaft train into the modal range and to analyse the modal torsional moments or rather the modal damping. If a negative influence of the HVDC system on the damping of the natural torsional frequencies is found, measures must be taken; for example, provision can be made for a damping control. The aim is to design the HVDC system control in such a way that a positive contribution to damping over the entire sub-synchronous frequency range is achieved from the outset. Furthermore, provision can be made in principle for a control functionality that disconnects the HVDC system or gradually reduces active power transmission when (poorly or negatively damped) sub-synchronous vibrations are detected. 12
This measure must be examined on a case by case basis: It would be counterproductive if the HVDC system previously made a positive contribution to damping and the inadequately damped sub-synchronous vibration were to have some other cause. In this case, the damping would get worse. There is a risk that the grid cannot manage the curtailment of one or more HVDC systems. This is to be compared with the shutdown of a power plant unit. Protective devices must operate selectively, safely and reliably and disconnect the protected asset as quickly as possible if impermissible loads occur. Since the asset being protected is the turbine-generator set, the power plant operator should evaluate the use of appropriate protective devices for it. The results of the performed analyses (power plant operator’s analyses and SSTI analyses) are included in this evaluation. 4.2.3 Demands on the models 4.2.3.1 Electric grid For the analyses described in 4.2.2, a sufficiently large detailed section of the AC grid should be considered. This section is determined by the screening study, which is performed on the original model (referred to below as detailed grid model). This detailed grid model must be completed with a suitable, reduced dynamic boundary grid model for representing electromagnetic transients (EMT). The additionally considered boundary grid model simulates the interconnected system, which is not modelled in detail, in such a way that the grid short circuit capabilities are properly described in the detailed section. Furthermore, it must be ensured that the requirements of VDE-AR-N 4131 Section 10.1.19 can be observed with a view to the interaction between HVDC systems. All relevant grid elements are modelled in the detailed grid model according to the frequency range being considered, making allowance e.g. for possible saturation, resonance, etc. 4.2.3.2 Power plant models Generators: Generators are modelled with their complete equivalent circuit diagram according to Park (see chapter 4.4.2). Shaft train models: The shaft train models must be able to simulate all relevant sub- synchronous natural frequencies and pertinent natural modes with sufficiently great accuracy (see chapter 4.4.1). Exact determination of the damping is possible only with great effort. The conservatively estimated modal mechanical attenuation therefore is to be specified by the power plant operator. The robustness of HVDC system behaviour is to be ensured for the natural frequencies of the shaft train according to chapter 4.4.1. This way, differences between theoretical model and the actual values of the natural frequencies and the damping are taken into account. Validation of the shaft train model through suitable measurements on the shaft train concerned is recommended before carrying out the SSTI study. 13
Control models of power plants connected in the grid section being considered: o If possible, for those power plants under study that are close to the HVDC connection point, the exact turbine-generator set control models (voltage regulation und turbine governing system) should be used. These depend on the manufacturer, are confidential, and in practice also are not available for all power plants. o An SSTI study can be carried out after verification with suitable recent IEEE models of the power plants under study, e.g. ST6B models and the corresponding PSS model (PSS – power system stabilizer). The applicability of the IEEE models to SSTI studies should be confirmed by the manufacturer of the controller. If necessary, more exact input filters for voltage measurement, speed measurement and active power measurement are to be included in the control models. This must be clarified with the manufacturer. o Not all limiters in the controllers, e.g. overexcitation limiter, underexcitation limiter or stator current limiter, play a role in SSTI studies. In very detailed studies the intervention of a limiter in the voltage regulator during SSTI inducement also is examined. o In the case of turbine governors, the basic speed governor behaviour, including the time constants of the turbines and turbine valves, is to be modelled. Load rejection identification in the turbine governing system normally plays no role in SSTI studies. Here again the manufacturer should supply the models and confirm the applicability to SSTI studies. o The control models must be capable of simulation in the instantaneous value range (e.g. suitable simulation of actual value processing; note: Most models are developed for classical stability in the RMS mode). 4.2.3.3 HVDC system models A detailed EMT model including all relevant control functions is to be used. This includes, inter alia: Higher-level control loops: o active power control o reactive power control and AC voltage regulation o … Subordinate control loops and near-converter control: o AC current control o possibly energy control or balancing control o modulator o … Measurement acquisition and processing: o phase-locked loops (PLL) o filters o … Different control modes (e.g. for grid parallel operation and grid restoration) possibly have to be considered. 14
The control functions implemented in the HVDC system are strongly dependent on the specified requirements and the specific way in which the manufacturer realizes them, so that no further statements can be made here about the modelling of the HVDC system. For the relevant control functions it is recommended that the appropriate control code implemented in the control hardware also be included in the offline simulation studies (via dll interface). Note: For this purpose ENTSO-E has developed a standard control interface for HVDC systems which, in addition to faithful mapping of the control code used in the system, permits analysing relevant signals within the HVDC control system down to the sub-module level, if necessary [18]. This makes it possible to ensure high reliability of the predictions of real-life system behaviour by the simulation model. Model verification should be carried out within the scope of the FPT/DPT (functional performance test, dynamic performance test), and the SSTI analysis should be repeated for selected scenarios. In the FPT/DPT the actual control panels are integrated in a real-time simulation environment by means of HIL (hardware-in-the-loop). 4.2.3.4 Duty points, load cases and fault scenarios Different duty points and scenarios have to be considered, among them: Heavy loads/light loads in the grid Topology changes at the point of connection, safety disconnection of electric circuits, decoupling of coupled busbars, minimal short circuit capability, possible variation of the short circuit levels Overexcited/underexcited generator operation Change in direction of HVDC power transmission Fault cases in the grid (failure situations of grid systems such as electric circuits, possibly up to the extreme case: HVDC remains connected to the power plant, but without grid connection) Power plant outages in the vicinity of the HVDC connection HVDC controller modes in fault cases Consider grid restoration studies separately if necessary 4.3 Summary Under certain conditions and constraints, HVDC systems can interact with the turbine-generator sets of power plant units in the surrounding grid, in which case the control equipment of the HVDC system influences the damping of torsional vibrations. This phenomenon is termed “sub-synchronous torsional interaction” (SSTI). However, the SSTI phenomenon also can be caused by other active (controlling) elements (e.g. faulty power system stabilizer in the voltage regulator [1], faulty turbine governor, or by converters for large motor drives in the power plant auxiliary service supply system). This chapter 4 deals with grid analyses necessary for the purpose of avoiding negative SSTI phenomena that can be initiated by HVDC systems. In a first step, power plant units are identified which require detailed analysis. According to the state of the art, this screening is done today by means of UIF analysis. In a second step, for identified power plants a detailed EMT analysis is 15
performed utilizing the reduced1 torsional vibration model and a detailed HVDC model. In the SSTI study proof is furnished that the HVDC system does not impair the damping of torsional vibrations in the cases investigated. 4.4 Brief description of models 4.4.1 Shaft train models A detailed calculation model of a shaft train under analysis usually consists of a great many individual segments (as many as 300) featuring material-specific and temperature-dependent stiffnesses, moments of inertia, and different modal damping parameters. These detailed models permit an in-depth study of the sub-synchronous torsional vibrations in the shaft train, including even an analysis of service life. In order to investigate sub-synchronous phenomena in the time range, including electric grid and HVDC system, it is necessary to reduce the detailed shaft train model to a few torsional masses. The reduced shaft train model usually is derived from the detailed shaft train model. The aim of preparing a reduced shaft train model is to keep the moments of inertia of the lumped- together shaft train segments constant and to optimize the reduced models by adjusting the torsional spring stiffnesses to the results of the detailed shaft train models, focussing on the easily excited natural torsional modes in the area of the generator rotor body. Figure 2 shows the result of such reduction [5]. Fig. 2: Comparison of a natural mode (detailed model, reduced model) The curve of the calculated natural torsional modes shows which natural frequencies and associated natural modes theoretically are at all capable of being excited by the electrical system (via the generator). Should it turn out upon reduction that the relevant natural modes and natural frequencies of the detailed shaft train model cannot be modelled with sufficient accuracy, the torsional masses will have to be further subdivided. 1 Shaft train model adapted to the highest relevant natural torsional frequency/natural torsional mode 16
A shaft train model reduced to a few torsional masses usually is not suited for calculating fatigue with acceptable accuracy. Should it turn out in a time range simulation, including relevant grid segment and HVDC system, that the damping of single or all sub-synchronous eigenvalues is reduced by the influence of the HVDC controls, the controls of the HVDC system will be adjusted to rule out any negative influence on damping. The exact effects on the shaft train can be considered by the power plant operator in a separate calculation based on a detailed shaft train model. The data of the reduced shaft train model shown below is required as minimum and is to be made available by the power plant operator (different number of turbine masses possible depending on power plant). The period of time necessary for procuring the data must be taken into account in accordance with section 3.2.1: Mass No. Description Inertia Part of starting torque [kg m2] [%]* M1 High-pressure turbine (HP) M2 Intermediate-pressure turbine (IP) M3 Low pressure A turbine (LPA) M4 Low pressure B turbine (LPB) M5 Generator (GEN) -100 M6 Exciter (ERR) 0 Coupling Description Spring rate from-to [Nm/rad] M1-M2 HP-IP M2-M3 IP-LPA M3-M4 LPA-LPB M4-M5 LPB-GEN M5-M6 GEN-ERR 17
Natural Calculated Modal damping torsional frequency [expressed as logarithmic decrement]* frequency No. [Hz] 1 2 3 4 5 … * The modal damping values made available for all relevant natural torsional frequencies of a shaft train are to be validated, if necessary, based on suitable measurements Verification of the reduced shaft train model versus the detailed shaft train model: Sub-synchronous eigenvalues and eigenvectors should be mapped with the greatest possible accuracy compared with the detailed model. The maximum deviation of the natural frequencies in individual instances must be no more than ± 0,5 Hz for the first 3 natural modes and no more than ±1 Hz for the higher modes. A comparison between reduced and detailed model is made available. The aforesaid deviations of the natural frequencies resulting from the reduction of the shaft train model are to be taken into account in designing the control. In addition, it must be borne in mind that deviations of the natural frequencies are unavoidable due to inaccuracies in the creation of the detailed shaft train model. If the manufacturer is unable to state values for this additional deviation, it is to be set at ± 0,5 Hz. 4.4.2 Equivalent circuit diagrams of generators for the calculation of SSTI The best-known model for analytical description of the synchronous generator is the Park model [6] or rather the extended model according to Park (field circuit and damper circuit in the d-axis, two damper circuits in the q-axis), which describes the operating characteristics of the synchronous generator in relation to the grid for steady-state and electromagnetic transient processes with sufficient accuracy. The parameters of the equivalent circuit diagrams according to Park are calculated in advance analytically from the geometric dimensions and material data of the generator and verified with sudden short-circuit tests. This modelling focuses on events with simple and double system frequency, which account for most transient processes. However, the model also is valid for frequencies which deviate from 50 Hz and 100 Hz and is thus suitable for SSTI studies [7]. 18
Canay shows in [8] that the assumption of equal magnetic coupling between the stator winding and the damping and field windings leads to a partly inaccurate calculation of the rotor currents in regard to the distribution of the AC components between damper winding and field winding in the case of transient processes. Canay enlarged the original model by inserting additional “Canay inductances” between the stator circuit and rotor circuit (see Figure 3). Allowance for the Canay reactance is state of the art. If the appropriate equivalent circuit diagram can be made available by the manufacturer of the generator, it should be used. If the Canay reactance is not available, the extended Park model can be used for SSTI studies. The Canay reactance generally has a negligible effect on the terminal behaviour of the generator. Fig. 3: Equivalent circuit diagrams of a synchronous generator with two damper circuits, extended according to Canay: a) d‐axis, b) q‐axis (Source: NETOMAC‐Theoriebuch) 19
5 Requirements for HVDC controls and HVDC protection systems 5.1 Introduction Torsional vibrations in turbine-generator sets of power plants can be initiated or induced by different scenarios and are known from the literature [4, 9, 10]: Possible influences of the power plant on torsional vibrations of the turbine-generator set: Out-of-phase synchronization of power plant generators Load rejection to auxiliary station supply Interaction with drive converters in the power plant auxiliary system Rectifier with static excitation Fault in the voltage regulator or power system stabilizer Fault in asynchronous machine in the plant auxiliary system Possible influences of the transmission system on torsional vibrations of turbine-generator sets: Faults or short circuits in the system Switching action in the system (planned or unplanned) Interaction with series compensation of long lines Asymmetrical phases in the system Interaction with HVDC systems Effects of lightning strikes in the system Increased rates of change of frequency (RoCoF) Basically, resonance excitation in turbine-generator sets can be calculated and also measured using models [7, 11]. The following considerations deal exclusively with possible interactions between HVDC systems and turbine-generator sets in power plants. HVDC systems use converters to couple three-phase and direct current systems. Taking into account their technical design, the converters can be operated in both directions as rectifier or inverter. As the three-phase current is generated by means of power electronic components (e.g. thyristors or IGBTs), converters can be regulated more flexibly and more quickly compared with synchronous generators. The control systems used in the converters have the purpose of ensuring the load flow between three-phase system and direct current system in accordance with the requirements of the transmission systems. If the controls are not properly designed or incorrectly parameterized, or if there are faults in the controls, the actuator or the power electronics, due to the negative damping that results from this the converter can produce interactions with the three-phase system and the turbine-generator set which lie outside the system frequency range (47 Hz to 52 Hz). In generation systems with synchronous generators within the range of influence of such a faulty converter, these interactions can lead to increased fatigue or damage on components of the turbine-generator set [4, 7, 9, 10]. 20
The following considerations should provide insights into the different technical versions of the HVDC systems and the converters used, as well as enable a risk assessment by HVDC operators, transmission system operators and power plant operators in regard to the described interactions. 5.2 Definition of the basis for the classification of HVDC systems Various HVDC converter principles are known from the literature [12]. Currently, the following HVDC systems are in use or planned in Germany for the following purposes: HVDC systems for connections between different asynchronous transmission systems (interconnector) HVDC systems for connecting offshore wind farms to the three-phase network (offshore wind farm) HVDC systems connected to a direct current transmission line or to a direct current network within a transmission system (overlay link) Multi-terminal combinations of different connections to an HVDC system (interconnector & offshore wind farm; interconnector & overlay link) In chapter 2 (see also 7 Annex) a survey of existing and planned HVDC systems is provided. 5.2.1 Technical design The following converter technologies can be distinguished: Converters with LCC (line-commutated converter) technology The converters with LCC technology usually consist of 12-pulse thyristor-controlled bridge circuits which are connected in specific sequences (phase angle control) in order to perform either the rectifier or inverter function. These converters are line-commutated and hence depend on an existent voltage of the three-phase system. This technology using thyristors was introduced around 45 years ago and therefore has proven reliable for decades. Converters with VSC (voltage source converter) technology The converters with VSC technology make use of turn-off power semiconductors such as IGBTs. These self-commutating converters feature load-independent direct current and, with suitable control, can modulate AC voltage. They thus have black-start capability and offer, among other things, higher switching frequencies, considerably reducing the need for passive filters compared with the LCC technology. The VSC technology was introduced in 1997 (in use in Germany since 2010) so that long-term operating experience is not available. Current VSC converters for large HVDC systems have a modular design with MMC (modular multilevel converter) technology [13] (in use in Germany since 2015). 21
5.2.2 Control systems used in terms of their application and the control modes utilized Depending on the utilized technology, the possibilities for control differ; consequently, the potential technical solutions for avoiding unwanted interactions due to frequencies outside the system frequency range differ as well. According to VDE-AR-N 4131, when conducting the SSTI study the complete controls including all envisaged control modes of the HVDC system always must be taken into account. The influence of individual control modes on the reaction of the HVDC system in the relevant sub- synchronous frequency range is to be demonstrated. All control modes that (can) influence plant behaviour in regard to sub-synchronous interaction have to be included in the detailed study. The following characteristics can be assigned to the individual technologies [12, 14]: Converter station in LCC technology: Acquisition of the reference signal by means of phase-locked loops (PLL) Direct current in the intermediate circuit Current-driven control For active power reversal the output voltage on the direct current side is used (direction of current flow remains the same) Firing angle control, commutation through selective energization of the thyristors, and control through symmetric timing of the thyristors (EPC – equidistant pulse control) Converter station in VSC technology: Acquisition of the reference signal by means of phase-locked loops (PLL) DC voltage in the intermediate circuit Voltage-oriented current control Active power control and reactive power control possible Rapid power flow reversal possible through reversal of current flow Generation of AC voltage through controlled switching on and off of the valves Switching frequencies of up to 2 kHz possible Black-start capability possible 5.2.3 Specifications of the Europeans rules and regulations The applicable requirements were already stated in chapter 4.1. 22
5.2.4 Standards applied to the operation of turbomachinery and generators High demands are made on the operation of turbomachinery and generators in power plants and industrial installations. In this connection, the following documents were and are drawn up by VDMA (German Mechanical Engineering Industry Association) taking into account the Machinery Directive, harmonized standards IEC 62061, ISO 13849, and standards of the process industry IEC 61508 and IEC 61511: VDMA 4315 Turbomachinery and generators – Application of the principles of functional safety – Part 1: 4315-1 Methods for determination of the necessary risk reduction Part 2: 4315-2 Existing plants Part 5: 4315-5 Risk assessment steam turbines Part 8: 4315-8 Risk assessment hydrogen cooled generators Part 9: 4315-9 Risk assessment air cooled generators Summarising, SIL (safety integrity level) studies always are carried out to evaluate the risk, and suitably qualified technology is used for the protective devices. 5.2.5 Control and protection tasks in relation to the avoidance of torsional vibrations The HVDC converters on the transmission system side have the purpose of regulating the electric power and frequency in accordance with the constraints and requirements of the transmission system. The controls of LCC and VSC converter stations are continuously in operation. Control of converters that use LCC technology With LCC technology, interactions can lead to stronger torsional interaction in the event that faultily generated power oscillations in the sub-synchronous frequency range affect the natural torsional frequencies of a turbine-generator set within the area influenced by an HVDC system, and no damping control is implemented [4, 9, 10, 14, 15, 16]. A change in magnet wheel angle leads to corresponding voltage changes via the grid infeed. The controls of the line-commutated (LCC) converter seek to compensate the change. The following parameters can amplify or influence sub-synchronous interaction: operating mode or control mode, in particular current regulation rated point of the HVDC system higher firing angle firing angle control voltage stiffness at the grid connection point of the converter Protection from torsional vibrations if LCC technology is used For LCC converter stations, in the event of a problem with torsional vibrations an additional damping controller is designed. This damping controller has the purpose to generate a positive damping behaviour of the converter [13, 15]. 23
Furthermore, the HVDC system can be provided with a device that is able to detect a beginning torsional vibration based on the measured direct current. If a beginning torsional vibration, or one that does not attenuate quickly enough, is detected, if necessary the power can be reduced or the HVDC converter station can be switched off. Control of converters that use VSC technology The control of converters that utilize VSC technology is more complex than the control of LCC technology [15, 17]. Suitable control concepts and measures also are available in VSC technology and, if need be, are implemented to manufacturer specification so that the HVDC system is able to contribute to the electrical damping of torsional vibrations and meet the requirements of Section 10.1.21 VDE AR N 4131. The following parameters can amplify or influence sub-synchronous interaction: Operating mode dependent on selected control concept (individual approach required depending on manufacturer and system configuration). Concept and design of the control, plus the parameterization, have major influence on the stability and properties of the damping. The objective is therefore concepts in which the damping is inherently included in the normal control. This control behaviour can be achieved through the design of the control and the project- specific parameterization. The control is then designed so that the real part of the transfer function in the relevant frequency range is always positive. In this case the converter makes a contribution to the damping of torsional vibration. In normal and thus pre-specified operation, this characteristic always will result in improvement of the original damping. The property that the real part of the transfer function in the relevant frequency range and in all operating modes of the converter (rectifier, inverter) is greater than zero is achieved in a project-specific way. In the VSC technology the HVDC system can be provided, for example, with a device that is able to detect a beginning torsional vibration. However, for detection the VSC technology does not make use of the direct current, but instead the busbar voltage at the connection point of the converter. Torsional vibration monitoring systems independent of the controls A fundamental requirement for the safe and reliable operation of HVDC systems without negative repercussions on power plants is the correct design of the hardware and software of the control systems and their fault-free operation. A monitoring system completely independent of the HVDC control, where torsional vibrations are concerned, generally is not envisaged at the current time. 24
5.3 I&C design concepts for control 5.3.1 Concepts utilized for control The control system of HVDC systems is designed redundantly with 2 channels. Interruption-free, smooth switchover in the event of faulty regulation in one channel is possible. The cycle time is approximately 50 μs. Signal evaluation for channel switching is performed according to the specifications of the HVDC system operator. The control system design is manufacturer-specific and software-based. 5.3.2 Monitoring of control (e.g. self-monitoring for hardware faults) Self-monitoring of the control takes place on a continuous basis. Among other things, it covers the case of an interruption of the electric supply of a control channel. According to the specifications the HVDC system can continue operating without restrictions even if single IGBT modules (VSC) fail. Currently there are no provisions for specific monitoring of turbine-generator sets for natural frequencies and resonance frequencies within the area of interaction. 5.3.3 Assumed faults and conditions and constraints for the design of a robust control The faults assumed for the design of the control are to be agreed with the respective HVDC system contractor. The usual network failures always are considered. The study investigating sub- synchronous interaction is carried out for different rated points of the output diagram of the power plant generators in the area of interaction. In addition, the mechanical damping of the turbine- generator set in the simulation is conservatively set at D=0 or to very low values (no damping effect). The minimum short circuit capacity specified by the network operator has a major influence on the setting of the controller. 5.4 Measures intended to verify the robustness of the control 5.4.1 Necessary input criteria The power plant’s input data are needed to permit making a proper study and analysis of sub- synchronous resonances on turbine-generator sets. Along with the electrical data of the connection (generator output diagram, generator step-up transformer…) the models, data and settings of the voltage regulator and, if available, of the power system stabilizer (PSS) are required. In selecting the duty points, the real conditions and constraints of power plant operation are to be taken into account, e.g. auxiliary station supply losses, own consumption of reactive power. The mechanical parameters and a simplified shaft train model of the turbine-generator set also are needed for the SSTI study. 25
You can also read