OPERATION AND MAINTENANCE INSTRUCTIONS FOR COMPACT AIR & COMPACT HEAT - Applicable to program version 3.07 and newer versions

Page created by Joyce Hamilton
 
CONTINUE READING
GB.COMPACTAHSK.211115

OPERATION AND MAINTENANCE INSTRUCTIONS
FOR COMPACT AIR & COMPACT HEAT

Applicable to program version 3.07 and newer versions

                                                                                                 COMPACT Heat
                          COMPACT Air

                                                                                       The document was originally written in Swedish.

Registered design. The company reserves the right to make design changes without prior notice.                    www.swegon.com    1
GB.COMPACTAHSK.211115

Content
1 SAFETY PRECAUTIONS............... 3                                 9 FUNCTIONS............................... 18                      11 READINGS............................... 38
1.1 To Start/Stop the Air Handling Unit............3                  9.1 Temperature...........................................18
1.2 Risks ........................................................3     9.2.1.1 ERS Regulation...............................19
                                                                                                                                         12 MANUAL TEST........................ 38
                                                                        9.2.2 Airing Function..................................20        13 ALARM SETTINGS................... 39
2 GENERAL..................................... 4                        9.2.2.1 Automatic Airing............................20
2.1 Field of Application...................................4                                                                             13.1 Fire Alarms............................................39
                                                                        9.2.2.2 Manual Airing................................20          13.2 External Alarms.....................................39
2.2 Mechanical Design....................................4              9.2.3 Summer Night Cooling......................21
2.3 Control System.........................................4                                                                             13.3 Alarm Limits..........................................39
                                                                        9.2.4 Intermittent Night-time Heating                            13.4 Alarm Priority........................................39
2.4 Environmental Documentation..................4                      (applies to COMPACT Heat only).................22
2.5 The Components of the                                               9.2.5 Morning BOOST                                              14 CONTROL DISPLAY................. 40
Air Handling Units...........................................5          (applies to COMPACT Heat only).................23                14.1 Language..............................................40
  2.5.1 COMPACT Air.....................................5               9.2.6 Setpoint Temperature Displacement...23                     14.2 Air flow unit..........................................40
  2.5.2 COMPACT Heat...................................6                9.2.7 Heating                                                    14.3 Min/Max Adjustment............................40
3 COMMISSIONING....................... 7                                (applies to COMPACT Heat only).................24                14.4 Base Settings.........................................40
3.1 General.....................................................7       9.2.8 External Temperature Sensors............24
                                                                      9.3 Flow/Pressure..........................................25      15 COMMUNICATION.................. 41
4 CONTROL DISPLAY AND                                                   9.3.1 Fan Regulation..................................25         15.1 EIA-485................................................41
USING THE MENU.......................... 8                              9.3.1.1 Flow Regulation..............................25          15.2 Ethernet................................................41
4.1 Control display..........................................8          9.3.1.2 Demand Regulation (Control).........25                   16 SERVICE LEVEL........................ 41
  4.1.1 General:..............................................8         9.3.1.3 Slave Control..................................25
  4.1.2 The Buttons.........................................8           9.3.1.4 Clean Air Control............................26          17 MAINTENANCE....................... 42
  4.1.3 Display screen......................................8           9.3.2 Outdoor Temperature Compensation.27                        17.1 Filter Change........................................42
  4.1.4 Abbreviations Used..............................8               9.3.3 Downspeed Control of Fan Speed to                            17.1.1 To remove the Filters........................42
                                                                        Min. Set Point, Airflow...............................28           17.1.2 To fit new filters...............................42
5 MAIN MENU 1............................. 9                          9.4 To Activate the Filter                                         17.2 Cleaning and Inspection........................42
5.1 The Menu Tree..........................................9          Monitoring Function.....................................28           17.2.1 General...........................................42
5.2 General...................................................10      9.5 Operation...............................................29       17.2.2 Filter Space......................................42
5.3 Selection of Language.............................10                9.5.1 Switch clock......................................29         17.2.3 Heat exchangers..............................42
5.4 Normal Operation...................................10               9.5.2 Extended Operation...........................29              172.4 Fans and Fan Space..........................42
5.5 Extended operation.................................10               9.5.3 Summer time/Winter time.................29                 17.3 Performance Checks.............................42
5.6 Airing.....................................................10     9.6 Heating...................................................30   17.4 Damper Actuator for
5.7 Heating                                                             9.6.1 Heat exchanger.................................30          the Change-over Damper..............................42
(applies to COMPACT Heat only)...................10                     9.6.1.1 Defrosting the
5.8 Heating + Recirculation                                             rotary heat exchanger.................................30         18 ALARMS AND
(applies to COMPACT Heat only)...................10                     9.6.1.2 Heating BOOST                                            FAULT TRACING........................... 43
5.9 Main Menu 2..........................................10             (applies to COMPACT Heat only).................31                18.1 General.................................................43
                                                                      9.7 Cooling (Applies to an air cooler                                18.1.1 A and B Alarms................................43
6 MAIN MENU 2........................... 11                           installed in the outdoor air duct only)............32                18.1.2 To reset the alarm............................43
6.1 Menu tree...............................................11          9.7.1 Operation..........................................32        18.1.3 To Change the Alarm Settings..........43
6.2 Changing Operating Mode.....................12                      9.7.2 Temperature Regulation (Control)......32                   18.2 Alarm Descriptions with
6.3 Settings..................................................12        9.7.3 Periodic Operation.............................33          Factory Settings............................................44
7 USER LEVEL............................... 13                          9.7.4 Regulation Speed..............................33
                                                                        9.7.5 Outdoor Temperature Limit................33                19 INFORMATIVE MESSAGES ..... 48
7.1 Temperature...........................................13
  7.1.1 Readings...........................................13           9.7.6 Restart Time......................................33       20 TECHNICAL DATA................... 49
  7.1.2 Settings.............................................13         9.7.7 Cooling Min Air Flow.........................33
                                                                                                                                         20.1 Dimensions, COMPACT Air...................49
7.2 Air flow/Pressure.....................................14            9.7.8 Neutral Zone.....................................33
                                                                                                                                         20.2 Dimensions, COMPACT Heat.................49
  7.2.1 Readings...........................................14           9.7.9 Cooling BOOST.................................33
                                                                                                                                         20.3 Electrical Equipment Cubicle.................50
  7.2.2 Settings.............................................14       9.8 Input/output connections........................34
                                                                                                                                          20.3.1 Internal Connections,
7.3 Switch clock............................................15        9.9 IQnomic Plus...........................................35
                                                                                                                                          COMPACT Air............................................51
7.4 Filters......................................................15   9.10 All Year Comfort...................................36
                                                                                                                                          20.3.2 Internal Connections,
  7.4.1 Readings...........................................15         10 AUTOMATIC FUNCTIONS....... 37                                    COMPACT Heat..........................................52
  7.4.2 To Calibrate the Filters.......................15             10.1 General.................................................37     20.3.3 Connection to Terminal Blocks.........53
  7.4.3 Calibration - Rotary Heat Exchanger...15                       10.1.1 Starting Sequence...........................37             20.4 Electrical Data.......................................54
7.5 Air Adjustment........................................16           10.1.2 Cooling Recovery.............................37             20.4.1 Air Handling Unit.............................54
7.6 Alarms....................................................16       10.1.3 Zero Point Calibration......................37              20.4.2 Fans................................................54
                                                                       10.1.4 Additional cooling –                                        20.4.3 Electrical equipment cubicle.............54
8 INSTALLATION LEVEL............... 17
                                                                       Electric Air Heater.......................................37       20.4.4 Heat Exchanger Motor.....................54
8.1 Menu Survey...........................................17                                                                              20.4.5 Control Inaccuracy...........................54
                                                                       10.1.5 Additional running -
                                                                       Heat Exchanger..........................................37        21 APPENDICES ........................... 55
                                                                       10.1.6 Density-corrected Airflow................37
                                                                                                                                         21.1 Commissioning Record..........................55
                                                                       10.1.7 BOOSTER-function
                                                                                                                                         21.2 Declaration of Conformity.....................63
                                                                       (Applies to COMPACT Heat only)................37
                                                                                                                                         21.3 Ecodesign data......................................63

2       www.swegon.com                                                  Registered design. The company reserves the right to make design changes without prior notice.
GB.COMPACTAHSK.211115

1         SAFETY PRECAUTIONS
All staff concerned must acquaint themselves with these
instructions before beginning any work on the unit. Any
damages to the unit or parts of it due to improper han-
dling or misuse by the purchaser or the fitter cannot be
considered subject to guarantee if these instructions have
not been followed correctly.
        Warning
        Only an authorised electrician or qualified service
        personnel trained by Swegon shall be permitted to
        carry out electrical installation on the air handling
        unit or wire external functions to it.

1.1 To Start/Stop the Air Handling Unit
The air handling unit should normally be started and
stopped via the control display. Note that the control
equipment of the air handling unit is still electrified after
the unit has been switched off via the control display.
Pull out the plug connector before servicing the unit if not
otherwise specified in the pertinent instructions or in the
event of an emergency.

1.2 Risks
     Warning
        Before carrying out any work, make sure that the
        power supply to the air handling unit has been
        isolated.
Risk areas with moving parts
Typical moving parts are fan impellers and drive pulleys of
the rotary heat exchanger. Safety guards are provided in
front of these components. If the ducts are not connected
to the fan outlet, these must be fitted with a safety guard
(wire mesh screen).
Only a qualified electrician or trained service technicians
shall be allowed to remove the safety guards.

Registered design. The company reserves the right to make design changes without prior notice.         www.swegon.com   3
GB.COMPACTAHSK.211115

2       GENERAL                                                   2.2 Mechanical Design
                                                                  The COMPACT is available in one physical size and for two
2.1 Field of Application                                          airflow ranges.
The COMPACT Air and COMPACT Heat units are complete               Its sheet steel exterior is painted . The decorative strips
air handling units that can be installed directly in the room     and cover plate around the control display are dark grey,
to be ventilated. The ducts for outdoor air and exhaust air       NCS S6010-R90B. The inner skin is predominantly made
should be connected to the top of the unit and should be          of aluminium-zinc plated sheet steel and Magnelis. The
arranged to lead out through the wall. Other than that,           casing has 30 mm thick intervening mineral wool insula-
you need only connect the unit to the mains electric sup-         tion; the inspection doors have 50 mm thick insulation.
ply.
                                                                  The COMPACT Air and the COMPACT Heat are equipped
The installation work can be carried out very quickly and         with pleated, Class ePM1 50% (F7) filters.
easily and if the task of cutting openings through the wall
is not complicated, the unit can be operational in just a         The type RECOnomic rotary heat exchanger is variable
few hours. It is also simple to relocate the air handling         speed controlled.
unit if the nature of the activities conducted in the room        The supply air and extract air fans are direct-driven plug
changes.                                                          fans. The fans are equipped with EC motors that provide
The ventilation is very effective thanks to the displacement      high efficiency across the entire operating range.
air distribution method used. The built-in control equip-
ment has several functions for economic operation.                2.3 Control System
The COMPACT Air and COMPACT Heat units are designed               The IQnomic control system is microprocessor-based and is
for comfort ventilation and can be used in classrooms, day        integrated into the unit. It controls and regulates the fans,
nurseries, conference halls, smaller offices, workrooms,          heat exchanger, temperatures, airflows, operating times
shops, restaurants and similar public premises.                   and a large number of internal and external functions as
                                                                  well as alarms.
The difference between the COMPACT Air and the COM-
PACT Heat units is that the COMPACT Heat units can also
be used for heating.                                              2.4 Environmental Documentation
It is important keep all the special characteristics of the       Environmental Documentation with the Dismantling
air handling units in mind when planning them into the            Instructions for recycling and the Environmental Declara-
project, installing, adjusting and operating them to fully        tion can be downloaded from our home page: wwww.
obtain all the benefits the COMPACT system has to offer.          swegon.com.

The unit must be installed indoors.                               The air handling unit is design in such a way that it can
                                                                  be dismantled into its natural parts for scrapping. When
The COMPACT units are designed and tested for ambient             the unit has ended its useful product life, the services of
temperatures from -25°C to +40°C, and air stream tem-             an accredited recycling company should be utilized for
peratures from -40°C to +40°C. However, for the rotary            disposal.
heat exchanger the temperature difference between the
outdoor air and extract air must not exceed 70°C.                 Approximately 94% of the parts in COMPACT air handling
                                                                  units is recyclable.
                                                                  Swegon AB is associated with the REPA Register, No.
      Important!                                                  5560778465.
      Always read the safety precautions in Section 1 that        Contact Swegon AB, Phone: +46 (0)512-322 00, if you
      explain the risks involved in running the unit and          have any questions regarding the dismantling instructions
      designate who shall be permitted to operate and             or the air handling unit’s impact on the environment.
      service the unit, and carefully follow the installation
      instructions provided in each paragraph.

The product identification plates are located inside the
room unit and on the unit’s rear side. See Sections 2.5.1
and 2.5.2 respectively. Refer to the particulars on the
product identification plate when you contact Swegon.

4   www.swegon.com                          Registered design. The company reserves the right to make design changes without prior notice.
GB.COMPACTAHSK.211115

2.5 The Components of the
Air Handling Units
2.5.1 COMPACT Air                                                          The arrangement of the components
The individual components each specified below in a sim-                   and their designations
plified and diagrammatical description.                                    1 Extract air fan with motor and built-in controller
                                                                           2    Control display (on the inspection door)
                                                                           3    Product identification plate
                                                                           4    Pressure sensor, extract air fan
                                                                           5    Electrical equipm. cubicle with control unit
                                                                           6    VOC sensor
                                                                           7    Sensor, extract air temperature
                       16                       1                          8    Extract air filter
                                                      2       3            9    Sensor, supply air temperature (inside the lower section)
                                                                           10   Supply air fan with motor and built-in controller
                        15                                                 11   Heat exchanger
              14                    4                                      12   Pressure sensor, supply air fan
                                                5                          13   Sensor, rotation monitor
                   13                                                      14   Drive motor, heat exchanger
                                                6                          15   Sensor, outdoor temperature
                11 12           8       7                                  16   Supply air filter

              10

                   9

Outdoor air        Supply air           Extract air       Exhaust air

Registered design. The company reserves the right to make design changes without prior notice.                         www.swegon.com       5
GB.COMPACTAHSK.211115

2.5.2 COMPACT Heat
The individual components each specified below in a sim-
plified and diagrammatical description.
                                                                                 The arrangement of the components
                                                                                 and their designations
                                                                                 1 Extract air fan with motor and built-in frequency inverter
                    19          20                                               2    Control display (on the inspection door)
                                                                                 3    Product identification plate
                                                                                 4    Pressure sensor, extract air fan
                    18                          1                                5    Electrical equipm. cubicle with control unit
                                                       2            3            6    VOC sensor
                                                                                 7    Sensor, extract air temperature
                    17                                                           8    Extract air filter
               16                    4                                           9    Electric air heater, (inside the lower section)
                                                 5                               10   Sensor, supply air temperature (inside the lower section)
                   15
                                                 6                               11   Change-over damper with actuator (inside the lower section)
                                                                                 12   Supply air fan with motor and built-in controller
               13 14            8        7                                       13   Heat exchanger
                                                                                 14   Pressure sensor, supply air fan
                                                                                 15   Sensor, rotation monitor
              12                                                                 16   Drive motor, heat exchanger
                                                                                 17   Sensor, outdoor temperature
                                                                                 18   Supply air filter
                   9                                                             19   Recirculation section with actuator
                                                                                 20   Louvre damper
                   10

                   11

Outdoor air        Supply air            Extract air           Exhaust air

6   www.swegon.com                                         Registered design. The company reserves the right to make design changes without prior notice.
GB.COMPACTAHSK.211115

3         COMMISSIONING
3.1 General
Commissioning sequence:
1. Check that there are no foreign objects inside the unit,
   duct system or functional sections.
    COMPACT Heat: air recirculation section, louvre
    damper and room temperature sensor shall be installed.
2. Connect the mains plug. Note that the air handling
   unit starts up immediately and operates in the normal
   mode.
3. Select the appropriate language, if you have not already
   done so. See Section 14.1.
4. The air handling unit has a factory setting that makes
   it ready to operate. See Section 21.1 Commissioning
   Record.
    However, in many cases, these settings need to be
    adjusted to suit the current installation.
    Program the timer (switch clock), operating mode,
    temperatures, airflows and functions according to the
    procedures in Sections 5-16.
    Select whether the airflow unit of measurement shall
    be l/s, m3/s or m3/h. (INSTALLATION LEVEL in the CON-
    TROL DISPLAY menu).
    Fill out the Commissioning Record and save it in the
    document pocket of the air handling unit.
5. Activate, if needed, manual or auto operation (MAIN
   MENU 2) or lock the speed of the fans (AIR ADJUST-
   MENT menu).
6. Finish off with a filter calibration as described in Section
   7.4.2.

Registered design. The company reserves the right to make design changes without prior notice.         www.swegon.com   7
GB.COMPACTAHSK.211115

4       CONTROL DISPLAY AND
        USING THE MENU
4.1 Control display
4.1.1 General:
The control display has an illuminated display, 6 pushbut-                              √ NORMAL OPERATION
tons and a red LED for indicating alarms.                                                 EXTENDED OPERATION
                                                                                          AIRING
                                                                                        		              >>
4.1.2 The Buttons
The buttons have the following functions:

      ENTER confirms your selection of the highlighted
      function and proceeds to next deeper menu level.
      ESCAPE changes the display back to the previous
      menu. For menus with REMAIN.TIME display, the
      image changes automatically back to the previous
      menu after approx. 10 seconds.

      ADVANCE UPWARD or to the LEFT.

      ADVANCE DOWNWARD or to the RIGHT.

      DECREASES the value of the highlighted setting.                           The control display is mounted on the
      Changes are registered immediately and need not                          inspection door of the air handling unit.
      be confirmed by pressing Enter.

      INCREASES the value of the highlighted setting.
      Changes are registered immediately and need not
      be confirmed by pressing Enter.

4.1.3 Display screen                                                      √ NORMAL OPERATION
                                                                            EXTENDED OPERATION
The display screen has 4 lines. Many of the menus how-                      AIRING
ever have more lines and these are shown line for line as                 		              >>
you press the ADVANCE DOWNWARD button. The posi-
tion indicator shows where you are in the menu.
                                                                          COMPACT-A TUE 14:40
                                                                                STOP                        Position indicator
                                                                           MANUAL OPERATION
4.1.4 Abbreviations Used                                                  STOP?
The following abbreviations are generally used in the                     MAN/AUTO.OP
menus:                                                                    SETTINGS
SA = Supply air (Ex: SA FAN = Supply air fan)
EA = Extract air
OUTD = Outdoor air
ROOM = Room
ANTI-FROST MON = Anti-frosting monitor
HEAT EXCH = Heat exchanger

8   www.swegon.com                          Registered design. The company reserves the right to make design changes without prior notice.
GB.COMPACTAHSK.211115

5         MAIN MENU 1
5.1 The Menu Tree

                                               √ NORMAL OPERATION
                                                 EXTENDED OPERATION
                                                 AIRING
                                                 HEATING
                                                HEATING + RECIRC.
                                                			               >>

                                                 NORMAL OPERATION
                                               √ EXTENDED OPERATION
                                                 AIRING
                                                 HEATING
                                                                                                 EXTENDED
                                                                                                 LOW SPEED
                                                                                                    		 REM.TIME

                                                 NORMAL OPERATION
                                                 EXTENDED OPERATION
                                               √ AIRING
                                                 HEATING
                                                                                                 AIRING

                                                                                             			 REM.TIME
                                                                                             VÄRMNING
                                              Applies to COMPACT Heat only
                                                 NORMAL OPERATION
                                                 EXTENDED OPERATION
                                                 AIRING
                                               √ HEATING
                                                                                                 HEATING

                                                                                             			 REM.TIME
                                                                                             VÄRMNING
                                              Applies to COMPACT Heat only
                                                 EXTENDED OPERATION
                                                 AIRING
                                                 HEATING
                                               √ HEATING + RECIRC.
                                                                                                 HEATING + RECIRC.

                                                                                            			 REM.TIME
                                                                                            VÄRMNING

                                               AIRING
                                               HEATING
                                               HEATING + RECIRC.
                                               			               >>
                                                                                                                       Code = 1110*
                                                                                                 CODE: 0000

                                                                                                  To Main Menu 2

                                                                                             * The code can be changed under Service Level.

Registered design. The company reserves the right to make design changes without prior notice.                       www.swegon.com      9
GB.COMPACTAHSK.211115

5.2 General                                                        5.7 Heating
The main menu is normally shown if no other menu has               (applies to COMPACT Heat only)
been selected.                                                     The COMPACT Heat can be used for heating the room.
The display automatically returns to the main menu after           When HEATING is activated, the electric air heater (7.5
30 minutes.                                                        kW) heats up the air. A change-over damper in the lower
The content in the menu changes depending on the                   section of the air handling unit is reset and the air is led to
operating mode selected, other functions that affect the           the air discharge outlets at the bottom of the unit. The air
present operating mode and possible tripped alarms.                is discharged at high velocity and follows the floor surface
                                                                   by means of the so-called coanda effect. This enables long
                                                                   throw lengths and quickly heats the entire premises.
5.3 Selection of Language
When the air handling unit is started up for the first time,       The function can also be manually selected under HEAT-
a language selection menu is displayed. Select the appro-          ING. The air handling unit then operates According to the
priate language.                                                   preset conditions and times, see Section 9.2.6.

If you want to change language at a later opportunity – or         The function can be cancelled by pressing the escape
if you’ve selected the wrong language – you can change             button on the control display and then selecting Normal
the language at INSTALLATION LEVEL under CONTROL                   Operation.
DISPLAY. See Section 14.1.
                                                                   5.8 Heating + Recirculation
5.4 Normal Operation                                               (applies to COMPACT Heat only)
NORMAL OPERATION is highlighted in the display when                The COMPACT Heat can be used for heating the room.
the air handling unit is operated in the selected operat-          When the HEATING + RECIRC. function is activated, the
ing mode under Main Menu 2. Alternatives to operation              extract air fan and the heat exchanger are switched off.
are: stop (appears alternately in the menu when selected),         The damper in the air recirculation section is reset and
auto operation, manual low speed or manual high speed              room air is circulated. The louvre damper for exhaust air
operation, see Section 6.2.                                        closes to prevent any cold down draught.
The type of operation selected can be checked under Main           The electric air heater (7.5 kW) heats up the air. A change-
Menu 2.                                                            over damper in the lower section of the air handling unit
Normal operation indicates that the air handling unit is not       is reset and the air is led to the air discharge outlets at the
being operated in any of the time-limited manually acti-           bottom of the unit. The air is discharged at high velocity
vated functions. See Sections 5.5, 5.6, 5.7 and 5.8.               and follows the floor surface by means of the so-called
                                                                   coanda effect. This enables long throw lengths and quickly
                                                                   heats the entire premises.
5.5 Extended operation
When EXTENDED OPERATION has been activated, the                    When HEATING + RECIRC. is activated the air handling
unit operates in the high speed airflow mode preset under          unit operates according to the preset conditions and
User Level, see Section 7.2.                                       times, see Section 9.2.6.

For particulars of the times for extended operation, see           The function can be cancelled by pressing the escape
Section 9.5.2.                                                     button on the control display and then selecting Normal
                                                                   Operation.
The function can be cancelled by pressing the escape
button on the control display and then selecting Normal
Operation.                                                         5.9 Main Menu 2
                                                                   You can access to Main Menu 2 by highlighting >> the
                                                                   line farthest down and acknowledge by pressing the Enter
5.6 Airing
                                                                   button.
When AIRING is activated, the unit operates in the max
speed airflow mode preset under User Level, see Section            Enter the code. (Factory-preset code: 1110) The code can
7.2.                                                               be changed under Service Level.

For particulars on how to set the appropriate supply air
temperature and period for airing, see Section 9.2.2.
The function can be cancelled by pressing the escape
button on the control display and then selecting Normal
Operation.

10    www.swegon.com                         Registered design. The company reserves the right to make design changes without prior notice.
GB.COMPACTAHSK.211115

6 MAIN                              COMPACT-A TUE 14:40
                                    STOP
                                                                                                  Important! The appearance of
                                                                                                  the menus varies depending on
MENU 2                              MANUAL OPERATION
                                    STOP?                                                         the type of air handling unit and
                                                                                                  functions selected.
6.1 Menu tree
                                    COMPACT-A TUE 14:40
                                    MANUAL OPERATION
                                    STOP?
                                    MAN/AUTO.OP
                                                                              AUTO OPERATION
                                                                              MANUAL LOW SPEED
                                                                              MANUAL HIGH SPEED
                                    COMPACT-A TUE 14:40
                                    STOP?
                                    MAN/AUTO.OP
                                    SETTINGS

USER LEVEL                                                                   TEMPERATURE
(Section 7)

                                                                                                              *TEMPERATURE*
                                                                                                              READINGS
                                                                                                              SETTINGS
                                                                             ALL YEAR COMFORT

                                                                                                              *ALL YEAR COMFORT*
                                                                                                              READINGS
                                                                                                              SETTINGS
                                                                             FLOW/PRESSURE

                                                                                                              *FLOW/PRESSURE*
                                                                                                              READINGS
                                                                                                              SETTINGS
                                                                             SWITCH CLOCK

                                                                                                              *SWITCH CLOCK*
                                                                                                              TIME/DATE
                                                                                                              TIME CHANNEL
                                                                                                              YEAR CHANNEL
                                                                             FILTERS

                                                                                                              *FILTERS*
                                                                                                              READINGS
                                                                                                              CALIBRATION
                                                                             AIR ADJUSTMENT

                                                                                                              *AIR ADJUSTMENT*
                                                                                                              LOCKS FAN SPEED
                                                                                                              TIME SETTING: 0 h
                                                                             ALARMS

                                                                                                              *ALARMS*
                                                                                                              ACTIVE ALARMS
                                                                                                              ALARM HISTORY

INSTALLATION LEVEL                                                           INSTALLATION
(Section 8-16)

Registered design. The company reserves the right to make design changes without prior notice.                 www.swegon.com         11
GB.COMPACTAHSK.211115

6.2 Changing Operating Mode                                            COMPACT-A TUE 14:40
                                                                             STOP
You can start and stop the air handling unit or                        MANUAL OPERATION
change over to manual or automatic operation                           STOP?
from the main menu.
                                                                       COMPACT-A TUE 14:40
       The air handling unit should normally be                        MANUAL OPERATION
                                                                       STOP?
       started and stopped from the hand-held                          MAN/AUTO.OP
       micro terminal; not by switching the safety
                                                                                                                AUTO OPERATION
       isolating switch on and off.                                                                             MANUAL LOW SPEED
                                                                                                                MANUAL HIGH SPEED
When the air handling unit is started up, menus                        COMPACT-A TUE 14:40
for the various delays that are part of the starting                   STOP?
sequence are shown.                                                    MAN/AUTO.OP
                                                                       SETTINGS
See also Section 10.1.1, Starting Sequence.

6.3 Settings
When selecting SETTINGS in the main menu, you                               USER LEVEL
will advance to User Level and Installation Level.
See Section 7.

                                                                       INSTALLATION LEVEL

12    www.swegon.com                         Registered design. The company reserves the right to make design changes without prior notice.
GB.COMPACTAHSK.211115

7         USER LEVEL                                                                 TEMPERATURE
                                                                                                                                                                                                 Important! The
                                                                                                                                                                                                 appearance of the menus
                                                                                                                                                                                                 varies depending on the
7.1 Temperature                                                                                                  *TEMPERATURE*                                                                   type of air handling unit
        The basic functions can be preset at INSTALLATION LEV-                                                   READINGS                                                                        and functions selected.
        EL and the values can be read and set at USER LEVEL.                                                     SETTINGS
        See also Section 9.2 in which the functions for
        temperature are described in detail.
IMPORTANT! If you intend to substantially alter the tempera-
ture settings, you should first stop the air handling unit before                    *TEMPERATURE*
doing so.                                                                            READINGS
7.1.1 Readings                                                                       SETTINGS
Used for checking the performance.                                                                                                                             ERS REGULATION 1
7.1.2 Settings                                                                                                                                                             ERS REGULATION 2

ERS REGULATION 1
The control unit regulates the relationship between the sup-
ply air and the extract air temperatures according to a factory
preset curve.
Settings (see the chart to the right as well):
Value                             Setting       Factory
                                  range         settings
Step                              1-3           1
EA/SA Differential                1-5 °C*       2 °C
Breakpoint (refers to             15-23 °C*     20 °C		                                                               ERS Regulation 1
                                                                            Supply air temperature setpoint °C

extract air temperature)
                                                                                                                 24
*) The setting range can be changed. See Section 14.3, Min./
                                                                                                                 23
Max. Setting.
                                                                                                                 22
ERS REGULATION 2                                                                                                 21
The control unit regulates the relationship between the supply                                                                                                                       3      p2       Step
                                                                                                                                                                                                            1
                                                                                                                 20                                                             ep       Ste
air and extract air temperatures according to a custom-plotted                                                                                                               St
                                                                                                                 19
curve. The curve has three adjustable breakpoints.
                                                                                                                 18
Settings (see the chart to the right as well):                                                                   17
Value                             Setting            Factory                                                     16
                                  range              settings                                                    15
Extract air temperature                                                                                          14
X1                                10-40 °C           15 °C                                                         15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
X2                                10-40 °C           20 °C
X3                                10-40 °C           22 °C                                                                                                              Extract air temperature °C
Supply air temperature
Y1                                10-40 °C           20 °C
Y2                                10-40 °C           18 °C
Y3                                10-40 °C           14 °C                                                            ERS Regulation 2
                                                                                                                                                               22
                                                                                                                      Y = Supply air temperature setpoint °C

                                                                                                                                                                                1
                                                                                                                                                               20

                                                                                                                                                                                                     2

                                                                                                                                                               15
                                                                                                                                                                                                                3

                                                                                                                                                               10
                                                                                                                                                               9
                                                                                                                                                                   12        15                     20              25   27
                                                                                                                                                                        X = Extract air temperature °C

Registered design. The company reserves the right to make design changes without prior notice.                                                                                                     www.swegon.com        13
GB.COMPACTAHSK.211115

7.2 Air flow/Pressure                                                    AIR FLOW/PRESSURE
          Basic functions are set at INSTALLATION LEVEL
                                                                               *FLOW/PRESSURE*
          and values are read and set at USER LEVEL.                           READINGS
          Therefore see also Section 9.3, in which the func-                   SETTINGS
          tions for flow/pressure are described in detail.

7.2.1 Readings
Used for performance checks.
7.2.2 Settings
The functions selected at INSTALLATION LEVEL and the
min. and max. airflows of each unit size (see the table
below) determine which values can be set.
Values for airflow (l/s, m3/s, m3/h), pressure (Pa) or input
signal strength (%) can be preset depending on the func-
tion selected.
                                                                         *FLOW/PRESSURE*
LOW SPEED                                                                READINGS
Must always be preset! The value for low fan speed can-                  SETTINGS
not be higher than the value for high speed.
                                                                                          LOW SPEED
Low speed can be set as 0, which means that the air han-
                                                                                                  HIGH SPEED
dling unit stops.
HIGH SPEED                                                                                               MAX. SPEED
Must always be preset! The value for high speed cannot
be lower than the value for low speed.
MAX SPEED
Is only appropriate for the airing function. The value for
max speed cannot be lower than the value for high speed.

Min/Max Airflows

     AIRFLOW        MIN FLOW            MAX FLOW
                 COMPACT AIR AND     COMPACT AIR AND
                  COMPACT HEAT        COMPACT HEAT
      SIZE        m3/h *    m3/s      m3/h       m3/s
     02            300       0.08      900        0.25
     03            300       0.08      1440       0.40

* When you adjust the value, round off the value to the nearest
adjustable step.

14        www.swegon.com                         Registered design. The company reserves the right to make design changes without prior notice.
GB.COMPACTAHSK.211115

7.3 Switch clock                                                            SWITCH CLOCK
        Basic functions for the switch clock can be preset
                                                                                  *SWITCH CLOCK*
        at INSTALLATION LEVEL under FUNCTIONS/OPERA-
                                                                                  TIME/DATE
        TION and the values can be read and set at USER                           TIME CHANNEL
        LEVEL.                                                                    YEAR CHANNEL
TIME/DATE
The current date and time can be set and adjusted whenever                 Settings:
required.                                                                  Value                  Setting                    Factory
The switch clock automatically takes leap years into considera-            		                     range                      setting
tion.                                                                      TIME/DATE
Automatic changeover between summer time/winter time to EU                 Day                    Mon-Sun                     Automatic
Standard has been preset.                                                  Time                   00:00-23:59                 Current
This changeover function can be blocked at INSTALLATION LEVEL              Date                   Day/Month/Year              Current
under FUNCTIONS/OPERATION.                                                 TIME CHANNEL 1-8
TIME CHANNEL                                                               Operation               Low speed/High speed* High speed
Times and days can be set when the unit is to run at high speed,           Time                    00:00-23:59           00:00-00:00
low speed or be stopped.                                                   Period                  Not active            Not active
Eight different time channels can be set. If the same in-operation         		                     Mon, Tues, Wed etc
times are to apply every day of the week (Mon-Sun), you need               		                     Mon-Fri
only program one time channel. Different operation times for               		                     Mon-Sun
each day of the week can be programmed by programming a                    		                     Sat-Sun
time channel for each day (Mon-Fri, Sat-Sun or Mon, Tues, Wed,             YEAR CHANNEL 1-8
etc)                                                                       Operation              Not active                  Not active
The time can be set as 00:00-00:00 if the deviating in-operation           		                     Stop/Low sp./High sp.
period is desirable for the entire 24 hours period.                        Time                   00:00-23:59                 00:00-00:00
                                                                           Period                 From Day/Month/Year         01/01/2005
YEAR CHANNEL
                                                                           		                     To Day/Month/Year           01/01/2005
The year channels make it possible to set deviating in-service
times for parts of the day during certain parts of the year. Eight         *) Shows Stop/Low speed/High speed if this function is selected
different year channels (yearly time schedules) can be set. The            at INSTALLATION LEVEL under FUNCTIONS/OPERATION.
year channels over-modulate the time channel during the hours
of the day and the days that the year channel is active. The year           FILTERS
channel dates indicate the dates between which the year chan-
nel shall apply and the year channel hours indicate the hours of                *FILTERS*
the day between which the year channel will steer the controller                READINGS
to operate the rotary heat exchanger at a specified speed. Other                CALIBRATION
times within the year channel still apply to that time channel.
The time can be set as 00:00-00:00 if the deviating in-operation
period is desirable for the entire 24 hours period.                                       *FILTERS*
Functions for summer night cooling, prolonged operation, etc.,                            READINGS
operate also when the year channel is active.                                             CALIBRATION
                                                                                                                 *FILTER CALIBRATION*
                                                                                                                 STD.FILTER
7.4 Filters                                                                                                      HEAT EXCHANGER
(and anti-frosting function of rotary heat exchanger)
There are two types of filter monitoring:
Calculated filter monitoring (preset at factory) monitors the fan’s        Calibration should be activated for both the supply air and the
speed increase conditional on the degree of fouling in the filter.         extract air if both filters are changed or for only for one airflow
The calibration involves taking airflow and fan speed readings.            direction if only one filter has been changed.
An alarm is initiated when the fan speed has increased by 10%              When filter calibration has been activated, the unit runs at high
above the preset alarm limit.                                              speed for about 3 minutes.
Filter monitoring with a pressure sensor (accessory) measures              After the filter has been calibrated, a speed increase of 10%, or
the pressure drop across the filter. The alarm limit is preset in Pa.      a pressure rise (= fouling of the filters) of 100 Pa is permissible,
                                                                           after which an alarm is initiated indicating a fouled filter.
7.4.1 Readings                                                             The alarm limit can be changed at INSTALLATION LEVEL under
When reading the filter status, the first value shows current value        ALARM SETTINGS.
and the second value shows current alarm limit.
                                                                           7.4.3 Calibration - Rotary Heat Exchanger
7.4.2 To Calibrate the Filters                                             If the anti-frosting function accessory for heat exchanger is in-
The filters must be calibrated for the first time during commis-           stalled (see 9.6.1.1) calibration can be selected from this menu.
sioning, when the duct system has been installed and adjusted.             When calibration R-HX is activated the fans are accelerated to
After that every time filters are replaced.                                high speed for about 3 minutes.

Registered design. The company reserves the right to make design changes without prior notice.                         www.swegon.com         15
GB.COMPACTAHSK.211115

7.5 Air Adjustment                                                    AIR ADJUSTMENT
The speed of the fans can be locked for up to 72 hours.
                                                                            *AIR ADJUSTMENT*
This is practical in conjunction with adjusting the airflow in
                                                                            LOCKS FAN SPEED.
the duct system.                                                            TIME SETTING: 0 h
The period desired is preset but can be interrupted earlier
by selecting STOP in the menu or by changing the time
setting to 0.

7.6 Alarms                                                            ALARMS
If an alarm is initiated, this is shown in the hand-held ter-
                                                                            *ALARMS*
minal both as clear text and by a blinking red diode.                       ACTIVE ALARMS
This menu enables you to read alarms quickly.                               ALARM HISTORY

ACTIVE ALARMS
Shows alarms that are active but have not initiated an
alarm signal in the display. This applies to alarms that have
a long delay, i.e. airflow or temperature alarms.
ALARM HISTORY
The 10 most recent tripped alarms are shown.

       Alarm settings can be entered at INSTALLATION
       LEVEL under ALARM SETTINGS.
       For complete description of alarms, see Section 18.

16    www.swegon.com                          Registered design. The company reserves the right to make design changes without prior notice.
GB.COMPACTAHSK.211115

8         INSTALLATION LEVEL                                                                         Important! The appearance of the
                                                                                                     menus varies depending on the
8.1 Menu Survey                                                                                      type of air handling unit and func-
                                                                                                     tions selected.
 INSTALLATION

 *INSTALLATION*                                 FUNCTIONS                                   *FUNCTIONS*
 CODE: 0000                                                                                 TEMPERATURE                 Section 9
                                                                                            AIR FLOW/PRESSURE
                                                                                            FILTER
Code = 1111                                     READINGS                                    OPERATION
                                                MANUAL TEST                                 HEATING
                                                ALARM SET                                   COOLING
                                                CONTROL DISPLAY                             IN/OUTPUTS
                                                COMMUNICATION                               IQnomic Plus
                                                SERVICE LEV.                                ALL YEAR COMFORT

                                                                                            *READINGS*                Section 11
                                                                                            TEMPERATURE
                                                                                            FANS
                                                                                            HEAT EXCHANGE
                                                                                            REGULATION SIGNALS
                                                                                            IN/OUTPUTS
                                                                                            IQnomic Plus
                                                                                            OPERATION TIME
                                                                                            PROGRAMVERSIONS
                         Section 10Automatic functions
                                                                                            *MANUAL TEST*              Section 12
                                                                                            TEMPERATURE
                                                                                            FANS
                                                                                            HEAT EXCHANGE
                                                                                            REHEAT
                                                                                            IN/OUTPUTS
                                                                                            IQnomic Plus
                                                                                            ALL YEAR COMFORT

                                                                                            *ALARM SETTINGS*
                                                                                                                       Section 13
                                                                                            FIRE ALARM
                                                                                            EXTERNAL ALARMS
                                                                                            ALARM LIMITS
                                                                                            ALARM PRIORITY

                                                                                            *CONTROL DISPLAY INST*     Section 14
                                                                                            LANGUAGE
                                                                                            AIR FLOW UNIT
                                                                                            MIN/MAX SETTING
                                                                                            BASE SETTINGS

                                                                                            *COMMUNICATION*            Section 15
                                                                                            EIA-485
                                                                                            ETHERNET

                                                                                            *SERVICE LEV.*             Section 16
                                                                                            CODE: 0000

Registered design. The company reserves the right to make design changes without prior notice.                    www.swegon.com     17
GB.COMPACTAHSK.211115

9 FUNCTIONS                                                            INSTALLATION

9.1 Temperature                                                            FUNCTIONS
       Basic functions can be set at INSTALLATION LEVEL                           *FUNCTIONS*
       and values are read and set at USER LEVEL.                                 TEMPERATURE
                                                                                  AIR FLOW/PRESSURE          * TEMPERATURE *
IMPORTANT! If you intend to substantially alter the tem-                                                     TEMPERATURE REG
                                                                                  FILTER
perature settings, you should first stop the air handling                                                    AIRING FUNCTION
unit before doing so.                                                             OPERATION
                                                                                                             SUMMER NIGHT COOL
                                                                                  HEATING
9.2 Temperature Regulation (Control)                                              COOLING                    INTERM. NIGHT HEAT                 *
                                                                                  IN/OUTPUTS                 MORNING BOOST                      *
Select ERS Regulation. Then select ERS Regulation 1 or 2.
                                                                                  IQnomic Plus               SETPOINT TEMP DISPL
Control sequence for ERS regulation:                                              ALL YEAR COMFORT                                              *
                                                                                                             HEATING
1. The temperature efficiency of the air handling unit’s                                                     EXT. SENSORS
   heat exchanger is modulated to provide max. heat
   recovery.                                                                                                * Applies to COMPACT Heat
2. After that the air heater, if installed, will begin to                                                   only
   generate heat.
                                                                                                            Important! The appearance
3. If a downstream heating coil is not installed, or if the                                                 of the menus varies
   its output is not adequate, the supply air fan will be                                                   depending on the type of air
   automatically and variably downspeed-regulated to                                                        handling unit and functions
   convey air at a lower flow rate.                                                                         selected.
A neutral zone can be preset, which allows a lower supply
air temperature setpoint before regulation to a lower flow
rate begins. See 9.3.3.
When the supply airflow is regulated to a lower rate, the
heat exchanger will have ”excess heat”, i.e. warm extract
air, giving it capacity to maintain the supply air tempera-
ture required.
As the supply airflow is regulated to a lower rate, the air
pressure in the premises will become negative and this will
instead cause outdoor air to be sucked in through leakage
spots such as doors and windows. This outdoor air will
then be heated by the usual heating system of the prem-
ises.
Downspeed regulation to lower the airflow rate occurs
from the current preset flow (high speed or low speed),
down to half of this flow rate. The degree of regulation
to a lower rate is also limited by the min flow setting of
the unit. When preset flow for low speed is near the min
flow rate, the effect of this regulation to a lower rate will
be small.

18    www.swegon.com                           Registered design. The company reserves the right to make design changes without prior notice.
GB.COMPACTAHSK.211115

9.2.1.1 ERS Regulation                                                         ERS regulation 1
ERS regulation means Extract air temperature-Related
Supply air temperature regulation. This means that the
temperature of the supply air is regulated in relation to the
temperature of the extract air. Under normal circumstanc-

                                                                                    Supply air temperature setpoint °C
                                                                                                                         24
es, the supply air temperature is regulated to be a few de-                                                              23
grees lower than the extract air temperature. In this way,                                                               22
the heat exchanger will provide optimal performance, and                                                                 21
this means excellent operating economy. ERS regulation is                                                                                              3      p2        Step
                                                                                                                                                                               1
                                                                                                                         20                       ep       Ste
                                                                                                                                               St
suitable for use when there is excess heat in the premises                                                               19
generated, for example, by machinery, lighting or people                                                                 18
and the supply air devices in the premises are suitable for                                                              17
diffusing air below room temperature.                                                                                    16
ERS REGULATION 1                                                                                                         15
The control unit regulates the relationship between the                                                                  14
                                                                                                                           15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
supply air and extract air temperatures according to a
factory-preset curve.                                                                                                                    Extract air temperature °C

See the chart to the right.                                                    Factory setting means:
The steps, breakpoint and EA/SA differential plotted in                        If the extract air temperature is below 20 °C (breakpoint),
the curve can be changed at USER LEVEL under TEMPERA-                          the supply air temperature setpoint will be automatically
TURE/SETTINGS.                                                                 regulated to be 2 °C (EA/SA differential) lower.
Settings:                                                                      If the extract air temperature is above 20 °C, the supply
Value                               Setting          Factory
    range                           setting
                                                                               air temperature setpoint will follow the curve according to
Step                                1–3              1                         Step 1.
Breakpoint                          15-23 °C         20 °C
(refers to extract air temp.)
EA/SA-Differential                  1-5 °C           2 °C
                                                                               ERS regulation 2
The setting range for the Break Point and EA/SA differ-
ence is limited by Min. and Max. settings at INSTALLATION                                                                     22
LEVEL under CONTROL DISPLAY.
                                                                          Y = Setpoint supply air temperature °C

                                                                                                                                         1
                                                                                                                              20
ERS REGULATION 2
This is used when special needs and conditions are such                                                                                                             2
that the factory preset ERS regulation 1 curve cannot pro-
vide the results required. Conditional on which settings are
made, it may be necessary to install a post-heating coil.
An individually adapted curve regulates the relationship                                                                      15
                                                                                                                                                                               3
between the supply air and extract air temperature.
See the chart to the right.
The following settings are possible at USER LEVEL under
TEMPERATURE/SETTINGS:
                                                                                                                              10
Value                               Setting          Factory
                                                                                                                              9
                                    range            setting
                                                                                                                                  12   15                          20              25    27
Extract air temperature
                                    X1 10-38 °C      15 °C                                                                                   X = Extract air temperature °C
                                    X2 11-39 °C      20 °C
                                    X3 12-40 °C      22 °C                     Breakpoints according to factory setting means:
Supply air temperature setpoint
                                    Y1 10-40 °C      20 °C                     If the extract air temperature is below 15 °C (X1) the set-
                                    Y2 10-40 °C      18 °C                     point for supply air temperature is constant 20 °C (Y1).
                                    Y3 10-40 °C      14 °C
                                                                               If the extract air temperature is 20 °C (X2) the supply air
                                                                               temperature set point will be 18 °C (Y2).
The setpoint displacement and summer night cooling
functions can also affect the preset temperatures.                             If the extract air temperature is above 22 °C (X3), the sup-
                                                                               ply air temperature setpoint will be constantly 14 °C (Y3).

Registered design. The company reserves the right to make design changes without prior notice.                                                                          www.swegon.com   19
GB.COMPACTAHSK.211115

9.2.2 Airing Function
                                                                   INSTALLATION
The airing function means that the air handling unit will
operate in the max. speed mode and temperature during                  FUNCTIONS
the preset period.                                                            *FUNCTIONS*
The function requires either a presence detector or has to                    TEMPERATURE
                                                                              AIR FLOW/PRESSURE          * TEMPERATURE *
be manually activated in Main Menu 1.                                                                    TEMPERATURE REG
                                                                              FILTER
                                                                                                         AIRING FUNCTION
9.2.2.1 Automatic Airing                                                      OPERATION                  SUMMER NIGHT COOL
The presence detector shall be connected to the external                      HEATING
                                                                              COOLING                    INTERM. NIGHT HEAT                 *
input, selected for external high speed.                                                                                                    *
                                                                              IN/OUTPUTS                 MORNING BOOST
Conditions that must be met for automatic airing to start:                    IQnomic Plus               SETPOINT TEMP DISPL
• Presence of occupant(s) has been indicated during at                        ALL YEAR COMFORT           HEATING                            *
  least 10 minutes.                                                                                      EXT. SENSORS
• Occupant(s) are no longer present and the preset time                                                 * Applies to COMPACT Heat
  period for high speed airflow has expired.                                                            only
Conditions that must be met for automatic airing to stop:
• Airing has taken place during the preset time period.
• The presence of occupant(s) is indicated via input for
  externally actuated high speed airflow.

9.2.2.2 Manual Airing
The Airing function can be started from Main Menu 1 and
will then operate during the preset time period.
The Airing function can be manually cancelled by setting
the air handling unit to Normal Operation in the control
display.
Settings:
Value                  Setting range Factory set-
ting

Function, Off/On       Inactive/Active Inactive
Supply air temperature 10 - 20 °C      10 °C
Time period            10-60 min.      15 min.

20    www.swegon.com                       Registered design. The company reserves the right to make design changes without prior notice.
GB.COMPACTAHSK.211115

9.2.3 Summer Night Cooling
                                                                            INSTALLATION
The lower temperature at night is utilized to cool down
the building structure. This reduces the cooling load dur-                      FUNCTIONS
ing the first hours of the day. If a cooling unit is installed,                        *FUNCTIONS*
its in-operation hours will be minimized, thus offering sav-                           TEMPERATURE
ings. If no cooling unit is installed, a certain cooling effect                        AIR FLOW/PRESSURE     * TEMPERATURE *
will still be realized.                                                                FILTER                TEMPERATURE REG
                                                                                                             AIRING FUNCTION
When summer night cooling function is activated, the unit                              OPERATION             SUMMER NIGHT COOL
fans operate at high speed, with a supply air setpoint of                              HEATING
                                                                                       COOLING               INTERM. NIGHT HEAT         *
10°C, from the preset time until the conditions necessary
                                                                                       IN/OUTPUTS            MORNING BOOST              *
for stop are satisfied.
                                                                                       IQnomic Plus          SETPOINT TEMP DISPL
Conditions to be met to start summer night cooling at the                              ALL YEAR COMFORT                                 *
                                                                                                             HEATING
preset time:
                                                                                                             EXT. SENSORS
• The extract air temperature should be higher than the
                                                                                                            * Applies to COMPACT Heat
preset value
                                                                                                            only
• The extract air should be at least 2°C warmer than the
outdoor air.
• The outdoor temperature should be above the preset
value.
• Heating has not been required between 12.00–23.00
hours.
• The unit must not operate in the high speed mode or
be stopped from an external source or manually from the
control display.
Conditions to be met to stop summer night cooling at the
preset time:
• The extract air temperature drops below the preset
value.
• The outdoor temperature drops below the preset value.
• Switch clock or external input calls for high speed.
• The extract air is less than 1 °C warmer than the outdoor
air.

The function starts once per set time period.
Settings:
Value                             Setting            Factory
                                  range              setting
Extract air temperature for start 17 - 27 °C         22 °C
Extract air temperature for stop 12 - 22 °C          16 °C
Outdoor temperature for stop       5 - 15 °C         10 °C
Supply air setpoint               10 - 20 °C         10 °C
Operating period                  00:00-00:00        23:00-06:00

Registered design. The company reserves the right to make design changes without prior notice.                   www.swegon.com    21
GB.COMPACTAHSK.211115

9.2.4 Intermittent Night-time Heating
                                                                          INSTALLATION
(applies to COMPACT Heat only)
The unit is utilized to heat the premises when it is normally                 FUNCTIONS
stopped by the switch clock.                                                         *FUNCTIONS*
The function requires connection of an external room                                 TEMPERATURE
                                                                                     AIR FLOW/PRESSURE          * TEMPERATURE *
sensor. Connect the TBLZ-1-24-2 Room sensor by means                                                            TEMPERATURE REG
of the modular cable supplied, to an optional connection                             FILTER
                                                                                                                AIRING FUNCTION
marked Internal BUS 1.                                                               OPERATION                  SUMMER NIGHT COOL
                                                                                     HEATING
When the function is activated, the air handling unit de-                            COOLING                    INTERM. NIGHT HEAT                 *
tects when the room temperature drops below the preset                               IN/OUTPUTS                 MORNING BOOST                      *
start temperature. The unit starts with preset flows and                             IQnomic Plus               SETPOINT TEMP DISPL
the supply air temperature setpoint.                                                 ALL YEAR COMFORT                                              *
                                                                                                                HEATING
If extract air fan operation is not desirable, the extract                                                      EXT. SENSORS
airflow can be set to 0.
                                                                                                               * Applies to COMPACT Heat
The damper output can be set to be Inactive. This means                                                        only
that the connected dampers (such as shut-off dampers
for outdoor air and extract air) will not be affected. These
dampers are normally closed when the air handling unit is
stopped and they also remain closed. The damper in the
air recirculation section opens at the same time.
Intermittent night-time heating does not affect a possible
extra temperature zone (Xzone) that regulates according
to its ordinary set point, if intermittent night-time heating
is in operation.
Conditions to be met for intermittent night-time heating
to start:
• The unit should operate in a time channel/switch clock
stop.
• The room temperature should be below set start tem-
perature.
Conditions to be met for intermittent night-time heating
to stop:
                                                                             ROOM AIR
• High speed or external/manual stop should be activated.
• Room temperature should be above the preset stop
temperature.
• Alarm with preset stop priority has tripped.
If the needed, the air handling unit fans will continue to
operate to cool the electric air heater although other con-
ditions for stop have been met.)
                                                                                                        SUPPLY AIR
Settings:
Value                           Setting            Factory
                                                                        Intermittent night-time heating with air recirculation sec-
                                range              setting
Room temperature for start      5 - 25 °C          16 °C                tion:
Room temperature for stop       5 - 25 °C          18 °C                If the extract airflow is set to 0 and the output to the
Supply air temperature setpoint 10 - 40 °C         28 °C                damper is inactive, the following will take place:
Supply airflow                  *) m3/s/Pa         **) m3/s/Pa
Extract airflow                 *) m3/s/Pa         0 m3/s/Pa            When conditions for start are met, outdoor air and ex-
Damper output                   Inactive/Active    Inactive             haust air shut-off dampers remain closed. The damper in
                                                                        the air recirculation section is opened. The extract air fan
*) The setting range is the same as the min/max settings of the         is idle.
air handling unit.
                                                                        The supply air fan operates according to the preset supply
**) According to the setting for low speed at USER LEVEL under
FLOW/PRESSURE.                                                          airflow and the heating coil downstream of the air han-
                                                                        dling unit operates according to the supply air tempera-
                                                                        ture setpoint, until the conditions for stop are met.

22      www.swegon.com                            Registered design. The company reserves the right to make design changes without prior notice.
GB.COMPACTAHSK.211115

9.2.5 Morning BOOST
                                                                                           INSTALLATION
(applies to COMPACT Heat only)
The unit is utilised to heat the premises during a preset                                                  FUNCTIONS
period prior to the switch-in time set on the switch clock.                                                      *FUNCTIONS*
The unit starts early and uses the separate settings for                                                         TEMPERATURE
                                                                                                                                       * TEMPERATURE *
operation and temperature regulation.                                                                            AIR FLOW/PRESSURE
                                                                                                                 FILTER                TEMPERATURE REG
The preset time is the time difference between the start of                                                                            AIRING FUNCTION
Morning BOOST to the start of ordinary operation.                                                                OPERATION             SUMMER NIGHT COOL
                                                                                                                 HEATING
Damper output can be set to be inactive. This means that                                                         COOLING               INTERM. NIGHT HEAT          *
connected dampers (e.g. outdoor air and exhaust air shut-                                                        IN/OUTPUTS            MORNING BOOST               *
off dampers) are not affected. Normally these dampers                                                            IQnomic Plus          SETPOINT TEMP DISPL
are closed when the unit is stopped and thus they remain                                                         ALL YEAR COMFORT      HEATING                     *
closed. The damper in the air recirculation section opens
                                                                                                                                       EXT. SENSORS
at the same time.
                                                                                                                                      * Applies to COMPACT Heat
The extract airflow can be set to Inactive if it is not desir-
                                                                                                                                      only
able for the extract air fan to operate.
Settings:
Value                             Setting    Factory
                                  range      setting
Time for start prior to regular
start time according to switch clock         hour, min.
00:00
Damper output                     Inactive   Inactive
Extract air fan                   Inactive   Inactive
                                                                                       INSTALLATION
EA/Room temp*                     10 - 30 °C 22 °C
SA-min*                           8 - 20 °C  15 °C
                                                                                                           FUNCTIONS
SA-max*                           16 - 50 °C 28 °C
                                                                                                                 *FUNCTIONS*
* If these values are changed, the corresponding values                                                          TEMPERATURE           * TEMPERATURE *
under Heating will also change.                                                                                  AIR FLOW/PRESSURE     TEMPERATURE REG
                                                                                                                 FILTER                AIRING FUNCTION
                                                                                                                 OPERATION             SUMMER NIGHT COOL
9.2.6 Setpoint Temperature Displacement                                                                          HEATING               INTERM. NIGHT HEAT          *
                                                                                                                 COOLING
Used for changing the supply air and extract air tempera-                                                                              MORNING BOOST               *
                                                                                                                 IN/OUTPUTS
ture setpoints by means of an external 0-10 VDC signal                                                           IQnomic Plus          SETPOINT TEMP DISPL
(control unit terminals 35 (-), 37 (+)). The temperature can                                                     ALL YEAR COMFORT      HEATING                     *
be increased or decreased at certain times of the day by                                                                               EXT. SENSORS
means of an external switch clock or potentiometer, for
                                                                                                                                      * Applies to COMPACT Heat
instance.
                                                                                                                                      only
The setpoint can be influenced ±5 °C.
If the unit is operating in the supply air regulation mode,                                                 +5
                                                                           Setpoint temp displacement °C

the supply air temperature is displaced and if the unit is                                                  +4
operating in the extract air regulation mode, the extract                                                   +3
air temperature is displaced.                                                                               +2
When the unit is operating in the ERS regulation 1 mode,                                                    +1
the difference between extract air and supply air is influ-                                                  0
enced. The difference cannot be less than 0 °C. The differ-                                                 -1
ence will decrease as the input signal increases.                                                           -2
If the unit is operating in the ERS regulation 2 mode, the                                                  -3
supply air setpoint will be offset.                                                                         -4
When the function is activated, the setpoint is offset as                                                   -5
                                                                                                                 0             5             10
illustrated in the chart to the right.
                                                                                                                     Control signal V DC
Settings:
                                                                               Setpoint temp displacement involves:
Value                               Setting         Factory                    Control signal 0 V DC: The setpoint is lowered by 5 °C.
                                    range           setting                    Control signal 5 V DC: Unchanged setpoint.
Setpoint temp displacement          Inactive/active Inactive                   Control signal 10 V DC: The setpoint is increased by 5 °C.

Registered design. The company reserves the right to make design changes without prior notice.                                             www.swegon.com     23
GB.COMPACTAHSK.211115

9.2.7 Heating
                                                                      INSTALLATION
(applies to COMPACT Heat only)
The air handling unit is utilised for heating the room dur-               FUNCTIONS
ing a preset time period. The function must be activated                         *FUNCTIONS*
manually.                                                                        TEMPERATURE
                                                                                 AIR FLOW/PRESSURE          * TEMPERATURE *
The air handling unit switches over to extract air/room
                                                                                 FILTER                     TEMPERATURE REG
regulation (control) of the temperature. The air heater, air
                                                                                                            AIRING FUNCTION
recirculation section and BOOSTER function are activated.                        OPERATION
                                                                                                            SUMMER NIGHT COOL
                                                                                 HEATING
Settings:                                                                        COOLING                    INTERM. NIGHT HEAT                 *
Value                   Setting range Factory set-                               IN/OUTPUTS                 MORNING BOOST                      *
ting                                                                             IQnomic Plus               SETPOINT TEMP DISPL
		                                                                               ALL YEAR COMFORT                                              *
Time for manual heating hour:min      00:45                                                                 HEATING
EA/Room Temp*           10 - 30 °C    22 °C                                                                 EXT. SENSORS
SA min*                 8 - 20 °C     15 °C		                                                              * Applies to COMPACT Heat
SA max*                 16 - 50 °C    28 °C                                                                only
* If these values are changed, the corresponding values
under Morning BOOST will also change.

9.2.8 External Temperature Sensors
                                                                      INSTALLATION
An external room sensor and external outdoor sensor can
be connected to the IQnomic control unit. The sensor can                  FUNCTIONS
be used when the internal sensor of the unit does not                            *FUNCTIONS*
provide representative values.                                                   TEMPERATURE
External Extract air/Room can measure the extract air                            AIR FLOW/PRESSURE          * TEMPERATURE *
temperature in a larger room instead of the temperature                          FILTER                     TEMPERATURE REG
                                                                                                            AIRING FUNCTION
inside the air handling unit.                                                    OPERATION
                                                                                                            SUMMER NIGHT COOL
External Outdoor measures the outdoor air temperature                            HEATING
                                                                                 COOLING                    INTERM. NIGHT HEAT                 *
outdoors, instead of the temperature inside the air han-
                                                                                 IN/OUTPUTS                 MORNING BOOST                      *
dling unit.
                                                                                 IQnomic Plus               SETPOINT TEMP DISPL
Connect the TBLZ-1-24-2 sensor by means of the modular                           ALL YEAR COMFORT                                              *
cable supplied, to an optional connection marked Internal                                                   HEATING
BUS 1.                                                                                                      EXT. SENSORS
Sensor TBLZ-1-24-2 can be used both as a room sensor                                                       * Applies to COMPACT Heat
and an outdoor sensor. They must therefore be addressed                                                    only
according to function using the function selector switch
on the sensor. The function selector switch must be in
Position 0 when the room sensor is used and in Position A
when an outdoor sensor is used.
If the TBLZ-1-24-2 sensor is installed outdoors, it must be
mounted inside an air-tight enclosure.
As an alternative, a temperature reading can be commu-
nicated to the air handling unit from a supervisory system,
for instance.
Settings:
Value                    Setting range      Factory setting
External Extract air/Room Inactive//IQnomic Inactive
                          Communication
External Outdoor          Inactive//IQnomic Inactive
                          Communication
Alarms                    0 - 9990 min.     5 min.

24      www.swegon.com                        Registered design. The company reserves the right to make design changes without prior notice.
GB.COMPACTAHSK.211115

9.3 Flow/Pressure
                                                                            INSTALLATION
        Basic functions are set at INSTALLATION LEVEL and
        the values are read and set at USER LEVEL.                              FUNCTIONS
                                                                                       *FUNCTIONS*
9.3.1 Fan Regulation
                                                                                       TEMPERATURE
The type of regulation used for the supply air fan and the                             AIR FLOW/PRESSURE
extract air fan respectively can be selected individually.                             FILTER            * AIRFLOW/PRESSURE *
                                                                                       OPERATION         SA FAN REGULATION
9.3.1.1 Flow Regulation                                                                HEATING           EA FAN REGULATION
Flow regulation involves operating the air handling unit                               COOLING           CLEAN AIR CONTROL
to keep the preset airflow constant. The speed of the fans                             IN/OUTPUTS           OUTDOOR TEMP COMP.
is automatically regulated to provide correct airflow even                             IQnomic Plus         SA DOWN REGULATION
if the filters begin to become clogged, air devices are                                ALL YEAR COMFORT
blocked, etc.
Constant airflow is advantageous, since the airflow always                                                  * AIRFLOW/PRESSURE *
is exactly as it was from the beginning.                                                                    SA FAN REGULATION
                                                                                                            EA FAN REGULATION
It should however be noted that everything that increases                                                   CLEAN AIR CONTROL
the pressure drop in the ventilation system, such as the
                                                                                                            OUTDOOR TEMP COMP.
blocking of air devices and dust accumulating in the fil-
                                                                                                            SA DOWN REGULATION
ters, causes the fans to run at a higher speed. This causes
higher power consumption and may also cause discomfort
in the form of noise.

9.3.1.2 Demand Regulation (Control)                                        Settings:
The flow demand is regulated via a 0-10 V input signal                     Value                          Setting
from an external sensor, such as a carbon dioxide sensor                   Fan regulation (SA/EA)         Flow regulation
that is wired to control unit terminals 35(-) and 37(+).                                                  Demand control
                                                                                                          Slave control
Required setpoint (separate for low speed and high speed)
is set as a percentage of the input signal.
The function can be limited so that the flow will not be
higher or lower than the preset max. and min. permissible
values respectively.

9.3.1.3 Slave Control
The flow is constantly regulated to be the same from
the one fan as from the other fan. If one fan is pressure-
controlled or demand-controlled, the other one can be
controlled as a slave to generate the same airflow.
The performance of the fan controlled as a slave can be
restricted if its maximum flow is set to a lower airflow rate.
Both fans cannot be controlled as slaves. If both are select-
ed by mistake, the extract air fan will be forced to operate
in the flow regulation mode.

Registered design. The company reserves the right to make design changes without prior notice.                   www.swegon.com    25
You can also read