ECI2000 Closed Loop Door Operator Technical manual
←
→
Page content transcription
If your browser does not render page correctly, please read the page content below
ECI2000TM05.doc ECI2000 Closed Loop Door Operator Technical manual (Revision 2.0, Sep. 01, 2004) (Revision 2.1, Oct. 17, 2004) (Revision 2.2, Nov. 16, 2004) (Revision 2.3, July 29, 2005) The complete manual consists of the following computer files: ECI2000TM02.doc fig_8_3_1.pdf fig_8_3_2.pdf fig_8_3_3.pdf fig_8_3_4.pdf fig_8_3_5.pdf fig_8_4_1.xls fig_8_4_2.xls fig_8_4_3.xls fig_8_4_4.xls fig_8_5_1.pdf fig_8_5_2.pdf 1
ECI2000TM05.doc Table of contents 1. Safety notice 2. ECI 2000 door operator 2.1 Introduction 2.2 Technical data 2.3 Functional description 3. Electrical installation and modes of operation 3.1 Electrical installation 3.2 Setup mode 3.3 Scan mode 3.4 Automatic mode 4. Recommendations and remarks 5. Using the hand-held unit 6. Laptop interface commands 7. Tables 7.1 Functions of the LEDs 7.2 Inputs 7.3 Outputs 7.4 Adjustable parameters and user interface commands 7.5 Error log and the list of reported errors 7.6 Laptop link and the list of the commands 7.7 RS 232 extension cable 8. Diagram list. 9. Spare part list. 10. Troubleshooting guide 11. Electrical installation and the quick setup procedure Appendix A DIP switch settings Appendix B1, B2 Door operator parameter lists Appendix C1 ECI-2000-1100 printed circuit board Appendix C2 ECI-2000-1101 printed circuit board Appendix C3 ECI-2000-1101 rev. 1.0 printed circuit board 2
ECI2000TM05.doc 1. Safety notice. Observe these precautions: 1. Do not touch any circuit board, power device, or electrical connections without ensuring that high voltage is not present. 2. This unit has to be grounded. Do not apply power before grounding the unit. 3. Motor circuits may have high voltage present even if the motor is not rotating. Do not disconnect the motor before power has been removed. 4. Do not connect or disconnect any wires and connectors while power is applied to the unit. 5. Do not attempt to remove any boards or relays when power is present. Remove power first at the main disconnect and wait at least 5 minutes until power capacitors fully discharge. 6. Handle boards with care. The boards are static sensitive. Apply proper electrostatic discharge (ESD) procedures. Before applying power: 1. Verify wires are properly connected. 2. Remove all debris from the enclosure. Check for loose wire clippings. 3. Verify that the unit is grounded. 4. Verify that the supply voltage is 120V AC (+/- 10%), 60 Hz. 5. Verify that jumpers X1 and X2 have been set on the microcontroller board for the 24V DC inputs. 3
ECI2000TM05.doc 2. ECI 2000 door operator 2.1 Introduction The ECI2000 is a closed loop microprocessor controlled door operator. An encoder feedback continuously monitors door position while digital controllers and the speed profile generator calculate optimal performance. 2.2 Technical data. - supply voltage: 120V, 60 Hz, 500VA. - opto-isolated input voltage: 120V AC/DC or 24V to 48V DC/AC - input voltage selection: jumper selectable - user inputs: 9 - close command - open command - door locking command - nudging command - stop command - photo-eye protection contact - heavy door # 1 - heavy door # 2 - PANA633 light barrier direct input - user outputs: 5 (1 SPDT relay contact) - door closed - door open - advanced door closed limit - operator ready (optional, relay socket not installed) - spare (ECI-2000_1101 board: optional relay, socket not installed) (ECI-2000-1101 rev. 1.0: optional PANA633 output relay, socket not installed) - relay contact data: resistive load: maximum current 3A at 250V AC 3A at 30V DC minimum current 10mA, 5V inductive load (P.F. 0.4, L/R = 7ms): maximum current 1.5 A at 250V 2A at 30V DC minimum current 10 mA, 5V -signal diodes (LEDs): 19 - user interface: RS-232 for a hand-held unit or a laptop serial port -option DIP switch: - position 1: door type (ON centre opening, OFF single slide or 2-speed) - position 2: single point scan, ON enabled, OFF disabled - position 3: direction reversal switch - position 4: (software version prior to 1.11 : ON photo-eye input selection, OFF PANA633 input selection) 4
ECI2000TM05.doc - position 4: (software version 1.11 and higher: DOL relay logic reversal for T-IV and TAC50 controllers: ON: DOL relay drops out within the door open zone, OFF: DOL relay picks up within the door open zone) - motor data: - 1/4 HP, 170V DC, 1100 rpm. - door maximum speed: 1m/s 2.3 Functional description The ECI 2000 door operator consists of the driving unit and the door transmission elements. The isolation transformer, the power stage and the microcontroller boards are enclosed in a steel box, which can be mounted on the top of the elevator cabin. The power switch has been installed inside the box. The microcontroller board provides access to user inputs and the power board provides user output signals (contacts). Refer to figures 8.3.1 trough 8.3.5 for connection details. The user inputs are opto-isolated. The outputs are in a form of normally open, and normally closed relay contacts (SPDT). The hand-held unit allows for easy parameter check and tuning. It receives power from the microcontroller board and uses a cable for connection with the board. A digital incremental encoder is mounted on the motor rear shaft. The motor is left hand or right hand side mounted allowing for the adaptation to the left or right hand side doors. A DIP-switch is used to set the motor direction of rotation with respect to the mechanical configuration. Neither motor nor encoder wires have to be reconnected when the mechanical arrangement has been changed. 5
ECI2000TM05.doc 3. Electrical installation and modes of operation 3.1 Electrical installation The input power at 120 V AC (+/- 10%) has to be connected as follows: live wire - to the power main switch (use a provided push-on connector) neutral wire - to terminal 2 of the J8 connector on the bottom board. ground wire - to the ground lug (AWG #14 is recommended). The equipment has to be grounded. The control input signals have to be connected to terminal blocks J1 and J4 on the top board. The control output signals have to be connected to terminal block J4 and if provided to terminal block J5 on the bottom board. The motor and the transformer are factory pre-wired. An optional RS-232 extension cable (part number ECI-2000-1390) may be connected to terminal block J5 on the top board. It allows setting up the door operator without opening of the box front cover. The “door closed” inductive sensor has to be plugged into the 3-pin header (JH1) on the bottom board. An optional PANA633 light curtain input can be used (part number ECI-2000-1380) with both the ECI-2000-1101 and ECI-2000-1101 rev.1.0 power boards. Refer to schematics 8.5.1 and 8.5.2. In the former case the PANA633 cable is plugged into the 2-pin header (JH2) on the power board and connected at the other side as follows: -red wire: from JH2 pin 1 to TRG in the PANA633 box -black wire: from JH2 pin 2 to 0V in the PANA633 box - DIP1 switch 4 has to be set to ON position. In the latter case follow 8.5.2 schematic because the JH2 header is not used anymore as the PANA633 input. It has been assigned to an optional door open limit sensor. Refer to schematic 8.3.2. 3.2 Setup mode This mode of operation may be chosen by the user or is forced by the power-up software initialization routine, when it detects the discrepancy between the stored setup data and the configuration of the option switches. Every door operator has to be setup after mechanical and electrical installation. The setup data are stored in a non-volatile memory and are later used in the scan mode after each power-up. Follow the setup procedure to set up the operator. 3.2.1 Setup procedure using the toggle switches 6
ECI2000TM05.doc This setup procedure has to be carried out after initial installation of the door operator. In this mode the commands are accepted only from the switches. The position of the INSP switch is disregarded. 3.2.1.1. Move the door manually from its closed position to the fully open position and then stop the door in the middle position before applying power. Make sure that the door moves smoothly. 3.2.1.2. Set the option switches according to the setup table. Refer to appendix A. Verify the position of the input voltage select jumpers. Jumpers have only to be placed on terminals X1 to X8 for 24V to 48V inputs. 3.2.1.3. Set the “door close” limit inductive sensor as shown in diagram 8.1.2. 3.2.1.4. Switch the inspection switch to the ON position, and the setup switch and the SW3 switch to the OFF position. 3.2.1.5. Apply power with the power switch. After a short delay, the door operator will become initialized. If the D17 red LED is flashing, the software passed the self-test and is running. If the D17 red LED is lit, but is not flashing, refer to chapter 7.1 for troubleshooting information. Two green LEDs (D8, “ready” and D6, “main relay”) and two orange LEDs (D36, D37) have to be on. The orange LEDs indicate that the power stage has been enabled and is operational. Switch the setup switch to the ON position. The orange LED (D16) will start flashing indicating that the door operator is in the setup mode. 3.2.1.6. Start the closing cycle (SW3 toggled to CL, “close”). If the door starts to move in the wrong direction, stop it, then switch the main power switch off and switch DIP1 switch 3 to its alternate position. Return to step 3.2.1.5. 3.2.1.7. Allow the door to stop and stall at its fully closed position. Wait until the “door close” limit LED is lit (D3) and then stop the door (SW3 to OFF). After completion of the closing cycle start the opening cycle. If no errors were encountered during the setup closing cycle, the program will permit the execution of the next setup step. 3.2.1.8. Start the opening cycle switching SW3 to OP (open). If the door does not move in response to SW3, an error was encountered during the closing cycle. If the hand-held unit is available, display the error log, then re-check the position of the door close limit. With power on, check if the sensor LED and D7 LED are on. With power off, re-check the mechanical setup of the sensor. If the door starts to move, wait until the door stops, and stalls at the fully open position, and D4 LED lights up. If the setup has been successful, the orange LED will stop flashing. Switch the setup switch and the SW3 switch to OFF. The orange LED will be switched off. If the setup has not been successful, the orange LED will continue to flash. During the setup, the software determines the width of the door and preloads parameters accordingly. These parameters are chosen based on the door type and width and usually do not have to be changed. Compare the mass of your doors to the mass displayed on the hand-held unit (parameter P5A) The displayed mass shows the maximum mass of the door for which, the door kinetic energy will not exceed 10 J (7.4 ft-lb.) at any position of the door if the door is moving at the closing speed (parameter P1A). If the mass of your doors is higher than the displayed mass, lower the door closing speed and check parameter P5A again. 7
ECI2000TM05.doc 3.2.1.9. With the inspection switch in the ON position, run the door through the scan close, and open cycles (refer to 3.3) and then through the automatic close and open cycles (refer to 3.4). 3.2.1.10. If changes to the standard setup parameters are required refer to section 5.2.6. 3.2.2 Setup procedure with the hand-held unit This setup procedure may be used as an alternate to the procedure described in the previous section. It is assumed that the power to the door operator is on. 3.2.2.1. Plug-in the hand-held unit cable. After a few seconds the display will show: ECI KEYPAD VERSION X.YZ followed by ECI-2000 VERSION A.BC X.YZ and A.BC represent software versions of the hand-held unit and the door operator. Press the “ENT” key once and the “RIGHT” key twice, then the “DOWN” key once to read the latest error for future reference. 3.2.2.2 . Press the “ESC” key once and the “RIGHT” key twice. The display will show: T0 TESTING 3.2.2.3. Press the “DOWN” key twice, and the “ENT” key once. The display will show: T2 SETUP < CLOSE OPEN > Use the “LEFT” and “RIGHT” keys to close and open the doors. Use the “DOWN” key to stop the doors. You may exit the setup, using the “ESC” key, at any time without changes to the previous setup. 3.2.2.4. The closing cycle is the only one initially allowed, so press the “LEFT” key. Allow the door to stop and stall at its fully closed position. After completion of the closing cycle begin the opening cycle. If no errors were encountered during the setup closing cycle, the program will permit the starting of the next setup step. If the door does not move in response to the “RIGHT” key, press the “ESC” key, and check the error log. Then check if the LED on the sensor and D7 LED on the board are on. With power off re-check the mechanical setup of the sensor. 3.2.2.5. To start the opening cycle press the “RIGHT” key. Wait until the door stops and stalls at the fully open position. 3.2.2.6. During the setup, the software determines the width of the door and preloads parameters accordingly. These parameters are chosen based on the door type and width and usually do not have to be changed. Compare the mass of your doors to the mass displayed on the hand-held unit (parameter P5A) The displayed mass shows the maximum mass of the door for which, the door kinetic energy will not exceed 10 J (7.4 8
ECI2000TM05.doc ft-lb.) at any position of the door if the door is moving at the closing speed (parameter P1A). If the mass of your doors is higher than the displayed mass, lower the door closing speed and check parameter P5A again. 3.3 Scan mode If the software does not choose the setup mode after power up initialization, the door operator will be working in the scan mode. In this mode, the commands are accepted from any available source (the elevator controller, the switches, or the hand-held unit). The highest command priority is assigned to the switches, followed by the hand-held unit and the elevator controller outputs. In the scan mode the door will be moving at the scan speed until the position counter is synchronized. The door will have to complete one close and one open cycle if DIP1 switch 2 is in the OFF position. However, if this switch is in the ON position, the position counter may be synchronized at the door fully closed position only. This operation is called a single point scan. Set the DIP1 switch 2 to ON position only if necessary on jobs where the elevator controller would prevent the door from reaching a fully open position (when the door is running at the scan speed) because of too short door dwell times. We also recommend that the so called “door watchdog timer” be set at least to 20 seconds for all single slide and two speed doors and at least to 15 seconds for centre opening doors. If the scan cycles have been completed, the software will compare the setup data to the scanned data and switch over to the automatic mode if the parameters are within tolerance. If the parameters are not within tolerance, the door operator will be shut down for 10 seconds and enabled again if the number of the shutdowns within an hour does not exceed 11. If the data do not match, even after a few trials, the door operator has to be setup again by a maintenance mechanic. The mismatch between parameters is very likely to happen after the board has been exchanged. It is highly recommended that the door operator be set up again when the microcontroller boards have been replaced. Refer to chapter 4 of this manual for further recommendations and remarks. 3.4 Automatic mode This is the basic operating mode for the door operator. The door is moved at the predetermined speed and all the control features of the software are active. The door operator responds to commands, which may come from any source, however, the command priority is taken into account. The highest priority is assigned to the command switches, followed by the hand-held unit, and the controller. The stop command, from the controller input or the hand-held unit overrides any direction commands. The lock command overrides the open command, but only in the automatic mode. The nudging command overrides all other door close speed references, switching over the closing speed to a level lower than: “heavy door 2/intermediate speed”, “heavy door 1”, and “close speed”. If the photo-eye input is connected or PANA633 light curtain input is wired to the ECI-2000- 1101 power board and enabled (switch DIP1 position 3 ON), a door moving in the close direction will slow down immediately if the mentioned inputs have been activated. The door will continue to move in the closing direction at a reduced torque level equal to the nudging torque. Under these conditions an elevator controller would reverse the door if the door is not running in the nudging mode. The above feature eliminates any need for an additional control input during the “fire recall” mode. 9
ECI2000TM05.doc 4. Recommendations and remarks A complex electronic system such as a door operator has to be maintained properly to ensure long and reliable operation. We recommend that the following rules be observed when servicing, installing, and replacing the door operator equipment. 4.1 Only qualified personal shall be allowed to service the door operator. 4.2 High voltage is present in this system. When replacing the boards disconnect power to the door operator at the main disconnect, and wait at least 5 minutes to allow for the capacitors to be discharged. 4.3 Mechanical adjustment on the belt gear should be carried out after the power has been switched off. Use the main disconnect to switch off the power. 4.4 No wires should be disconnected or unplugged when power is present. 4.5 Fasten all the incoming cables to prevent the plugs from being pulled out by gravity or vibration. 4.6 When using the hand-held unit, make sure, its cable will not be caught by any moving parts. 4.7 When replacement of the boards is required, it is recommend that the whole board assembly is removed and sent back to ECI. The assembly consist of the microcontroller board and the power board. 4.8 The “door closed” inductive sensor is used as a hardware backup for the “door closed” relay. The relay will pick up if both the software and the hardware confirm that the door is closed. 4.9 The hand-held unit is a recommended tool for the door operator setup. 4.10 Avoid touching any elements on the boards when the power is applied to the operator. 4.11 Some parts are static electricity sensitive. Handle the boards with proper care. 4.12. When adjusting or testing the operator, a barricade in front of the hall door is recommended as a safety provision. 10
ECI2000TM05.doc 5. Using the hand-held unit Unit characteristics: - hand-held, tactile push button keypad - two-line, 16 character, LCD display - a standard RS-232 straight-through cable - available functions: - tuning of regulators - parameter adjustment - monitoring various signals - error log reading - close and open cycle testing and simulation. The hand-held unit is a recommended tool for adjustment of the door operator. Its RS-232 cable may be plugged into the DB-9 connector placed on the board. The hand-held unit uses only 6 keys to navigate the command menu. Four keys are the direction keys (“UP”, “DOWN”, “LEFT”, “RIGHT”) and two keys are the execution keys (“ESC” - escape, “ENT” - enter). The “ESC” key will move the display back to the previous selection in the menu. The “ENT” key moves the display down into a submenu or forces execution of a command. If any key is not active at the current level, it is ignored by the software. The menu resembles an upside down tree. The staring point for the menu is M0 (MONITORING). After applying power to the hand-held unit, the unit starts to communicate with the microcontroller board. Initially a message is displayed showing the hand-held unit software version number. After a few seconds, if the link has been established, the second message is displayed. This message displays the microcontroller software version. In the next step, the user may enter into the menu by pressing the “ENT” key. It is recommended that the users always terminate the operation by pressing the “ESC” key a few times until the message reads “LINK TERMINATED”. The menu windows are described subsequently. Refer to diagrams 8.4.1 through 8.4.4 showing the layout of the menu tree. At the top level, the menu tree has five windows. Use the “RIGHT” or “LEFT” keys to scroll from one window to the other. To enter a window above or below the main window use the “UP” or “DOWN” keys. The names of the windows have been listed below. The first letter displayed in the upper row always corresponds to the first letter of the branch name. M0 MONITORING - entry into the monitoring branch P0 PROGRAMMING - entry into the programming branch E0 ERROR LOG -entry into the error log U0 UTILITIES - entry into the utilities branch T0 TESTING - entry into the testing branch While at the top level (level 0) pressing “ESC” brings the display to M0 window or terminates the link from the M0 window. 5.1 M0-MONITORING This branch displays some of the system parameters, which are updated at a rate from 0.2 to 2 seconds (depending on their rate of change). Most of them are self-explanatory: 11
ECI2000TM05.doc M1 DOOR SPEED M2 MOTOR CURRENT M3 CLOSE TIME M4 OPEN TIME M5 CLOSE CYCLES - the number of the close cycles performed by the door operator M6 OPEN CYCLES - the number of the open cycles performed by the door operator M7 POSITION - door position; number of the encoder pulses. There are 85758 pulses for 1 m of the door traveling distance M8 DOOR WIDTH - door width as measured during the setup. This value corresponds to the door traveling distance. M9 SYSTEM TIME - indicates for how long power was applied to the door operator. It is not a real time clock. M10 BUS VOLTAGE - displays the DC bus voltage. This voltage is “chopped" by the PWM circuit. M11 LEM VOLTS - current sensor voltage; 2.5V +/- 0.050V represents zero current M12 SOFTWARE - displays microcontroller software version M13 INPUTS - displays the status of the input signals connected to the J1 and J4 connectors (the input byte). A “1” represents an active input. bit 0 - DO7, door close command bit 1 - DO10, door open command bit 2 - DO18, door lock command bit 3 - DO4, door nudging command bit 4 -STOP, stop command bit 5 - PHDT, photo detector contact bit 6 - HD1, heavy door 1 contact bit 7 - HD2, heavy door 2 contact M14 INPUT PORT - displays the status of the input signals from the switches placed on the board. bit 0 - DIP switch 1, door type bit 1 - DIP switch 2, single point scan bit 2 - DIP switch 3, direction reversal switch bit 3 - DIP switch 4, refer to Appendix A. ( bits 0 -3 are active low and the display shows a “0” if the corresponding bit is active, and a “1” if it is not.) bit 4 - setup switch bit 5 - inspection switch bit 6 - close command switch bit 7 - open command switch (bits 4 -7 are active high) M15 LED PORT -this byte displays the status of the output port (the status of LEDs D10 - D17). Refer to table 7.1.1 and 7.1.3 for more information M16 OUTPUTS - this byte represents the output signals bit 0 - “spare” relay energized (valid for ECI-2000-1101 rev.0 boards) bit 1 - “door operator ready” relay energized bit 2 - “main” relay energized bit 3 - “advanced door closed” relay energized bit 4 - “door open” relay energized bit 5 - “door closed” relay energized bit 6 - “door closed” sensor active bit 7 - H-bridge driver supply enabled 12
ECI2000TM05.doc 5.2 P0-PROGRAMMING The programming branch has six submenus. To scroll through the submenus use the “UP” and “DOWN” keys. To enter one of the submenus use the “ENT” key. When the submenu is entered, the orange signal diode lights up (SUB MENU). To scroll in the submenu, use the “UP” and “DOWN” arrows. To change a parameter, press the “ENT” key. If access to programming has been enabled, the cursor will start to blink. Move the cursor around with the “LEFT” and “RIGHT” keys, change a value at the current location using the “UP” and “DOWN” keys. To enter a newly selected value press the “ENT’ key, to escape without changes, press the “ESC” key. If an entry exceeds the allowable range, a parameter will be overwritten after exiting from the data entry level. Some of the entries may also be slightly rounded by the software even if they are in the correct range. The changes are negligible (less than 1%). Pressing the “ESC” key allows returning to the previous level. All the parameters are always readable, but they may be changed only if access to programming has been enabled (refer to U3-PASSWORD). Programmable parameters are listed in sections 7.4 and 7.7. Speed reference profiles are shown in diagrams 8.1.1, 8.1.2 and 8.1.3. 5.2.1 P1-SPEEDS Eight speed parameters are included in the P1 sub-menu. The parameters are displayed in mm/s or ft/s. P1A CLOSE SPEED - maximum door closing speed during the closing cycle P1B HD1 SPEED - maximum door closing speed if the H_D1 input is active. This speed will be always lower than the P1A speed. P1C HD2 SPEED Software version prior to 1.11: maximum door closing speed if the H_D2 input is active. This speed will be always lower than the P1B speed. Software version 1.11 and later: maximum door closing speed if the H_D2 input is active equal to the intermediate speed (refer to diagram 8.1.2) P1D NUDGE SPEED - door nudging speed P1E CLOSE SLOW - slow closing speed during final approach to the terminal position P1F SCAN SPEED - closing and opening speed in the scan mode P1G OPEN SPEED - maximum door opening speed during the opening cycle P1H OPEN SLOW - slow opening speed during final approach to the terminal position P1J PL SPEED - slow pre-opening at the beginning of the open cycle 5.2.2 P2-PROFILE The units used are mm/s2, mm/s3 or ft/s2, ft/s3. P2A ACC. RATE - door acceleration rate; prior to ver. 1.14 P2A ACC. CLOSE – close cycle acceleration rate; ver. 1.14 and later P2B DEC. RATE - door deceleration rate; prior to ver. 1.14 P2B DEC. CLOSE – close cycle deceleration rate; ver. 1.14 and later P2C FAST RATE - fast deceleration rate during reversal or stop P2D JERK RATE - door jerk rate; prior to ver.1.11 P2D INT. RATE - intermediate deceleration rate; ver. 1.11 and later P2E ACC. OPEN - open cycle acceleration rate; ver. 1.14 and later P2F DEC. OPEN – open cycle deceleration rate; ver. 1.14 and later 13
ECI2000TM05.doc 5.2.3 P3-CURRENTS Eight current (torque) levels can be programmed in this submenu. Door closing, opening and dynamic forces are proportional to the respective motor currents. P3A OVERCURRENT - motor overcurrent level. If this level is exceeded the motor will be shut down. P3B ACC. CRNT - motor acceleration current. Applied current limit during acceleration. P3C DEC. CRNT - motor deceleration current. Applied current limit during deceleration. P3D OPEN CRNT - steady state current during the opening cycle. P3E CLOSE CRNT - steady state current during the closing cycle. This current determines the door closing force. P3F NUDGE CRNT - steady state current during the nudging cycle. This current determines the door closing force level in the nudging mode. P3G HLD OP CRNT - the level of this current determines the door holding force when the door is in its fully open position (hold open current). P3H STALL CRNT - this current determines the level above which the door is considered to be stalled, if its speed is equal to zero. The suggested setting is between 0.5A and 0.7A. 5.2.4 P4-DISTANCES Four parameters may be set in this submenu. Units used are mm or inches. P4A CL. SLOW - the final distance from the fully closed position when the door will be moving at the slow close speed (P1E). P4B OP. SLOW - the final distance from the fully open position when the door will be moving at the slow open speed (P1H). P4C ADV. DCL - the distance from the fully closed position when the “advanced door closed” limit signal is activated P4D PREOPEN - initial distance when the door is moving at the pre-open speed at the beginning of the opening cycle 5.2.5 DOOR DATA Units used are kg or lb. These parameters are readable parameters only. They are calculated based on the kinetic energy limit of 10J [Joules] and the door closing speed, heavy door 1 closing speed, and heavy door 2 closing speed. P5A DOOR MASS - the mass calculated from the kinetic energy equation Mass[kg] = (2 * 10 [Joules]) / (close speed [m/s]* close speed [m/s]) 14
ECI2000TM05.doc P5B HD1 MASS - as above, but (hd1 speed) is used to calculate the mass P5C HD2 MASS - as above, but (hd2/intermediate speed) is used to calculate the mass 5.2.6 P6-CONTROL All the parameters in this submenu allow setting of the dynamics of the digital controllers. The system uses three controllers to control motor current (torque), motor speed, and door position. Follow the recommendations below when adjusting the controller gains. The current controller is of PI type. Its gains have been determined at the factory and (generally) changes to the settings are not required. The IKP and IKI are the proportional and the integral gains of this controller. Typical values for IKP are from 500 to 1000. Typical values for IKI are from 30 to 80. It is recommended that these gains not be changed if they are within the recommended ranges. The speed controller is of PID type. The VKP, VKI and VKD are its proportional, integral, and derivative gains respectively. The values of these three parameters mainly determine the responsiveness of the door operator. The speed proportional gain parameter (VKP) may be increased or decreased to suit application. Increasing the parameter, results in faster response. Too high a gain may cause overshoot and ringing (oscillations). Decreasing the parameter results in slower response. The speed integral gain parameter (VKI) controls the stiffness of the controller. Increasing this parameter increases the low frequency stiffness but may cause overshooting and oscillations. The speed derivative gain parameter (VKD) controls the high frequency response of the controller providing dampening to eliminate oscillations and minimize overshoots and ringing. Dampening is given as a force, proportional to the rate of change of speed error. Increasing the parameter reduces overshoots and stabilizes response. Too high a setting may lead to oscillations. P6A IKP - current controller proportional gain P6B IKI - current controller integral gain P6C VKP -speed controller proportional gain P6D VKI -speed controller integral gain P6E VKD -speed controller derivative gain P6F PKP -position controller proportional gain P6G SCL -position error scaler (the lower the scaler the higher the overall system gain, however too low a scaler may cause system oscillations) P6H FER -position following error (the difference between the required and the current door position). If this difference has been exceeded the door control will reduce the door speed and closing force. 15
ECI2000TM05.doc 5.3 E0-ERROR LOG Windows E1 to E30 display the error name and time. If the error buffer is filled up, a new error will overwrite the oldest one. The error log can be cleared from any error window (E1 - E30). Press the “ENT” key and then either the “ESC” key to cancel the operation or the “ENT” key to clear the log. If the drive is not running, the “LOG CLEARED” message will be displayed. Otherwise, the “STOP DRIVE” message will show up in the window. One can stop the drive or wait until it stops automatically. The command has been latched and the error log will be cleared as soon as the drive stops. Use the “ESC” key to exit. 5.4 U0-UTILITIES U1-DISPLAY UNITS The hand-held unit may display either metric or imperial system units. To change the unit system press the “ENT” key. An asterisk shows up in the window and the red signal diode lights up (DATA). Using the “UP” or “DOWN” key select the unit system and press the “ENT” key if you accept the change or the “ESC” key to cancel your election. Press the “ESC” key again to exit. U2-D/A CHANNEL The digital to analog channels may be used for adjustment or troubleshooting. A digital oscilloscope with a roll mode feature is the most suitable for this purpose. This window allows selecting an analog output from test channel 1 (TP3). Test channel 2 (TP4) displays the motor speed only, and is not selectable. After power-up, channel 1 displays the speed reference and channel 2 the motor speed. To select a different output on channel 1, press the “ENT” key. The asterisk shows up in the window and the red signal diode (DATA) lights up. Using the “UP” or “DOWN” keys, select a required channel and press the “ENT” key to accept the selection or the “ESC” key to exit. Press the “ESC” key again, to return to the U0-UTILITIES window. U3-PASSWORD After power-up, access to programming is denied. All the parameters under the P0- PROGRAMMING branch are readable, but they cannot be changed. The default password is 0. If one wants to enable access to programming and the default password has never been changed, one has to press the “ENT” key followed by the “ESC” key. If the default password has been changed, one has to press the “ENT” key and then enter the right password using the direction keys, and complete the operation by pressing the “ENT” key. If the correct password has been entered, access will be enabled. The range of the password entries is from 1 to 9998. U4-NEW PASSWORD If the window displays “ACCESS DENIED”, to change the password one has to enter the password correctly in the U3 window, or enable the access if the default password is used. If the window displays “ACCESS ENABLED” press the “ENT” key and enter a new password. Then press the “ENT” key again. Press the “ESC” key to return to the U0 level. 16
ECI2000TM05.doc U5-CONTRAST If your hand-held unit has a small hole at the left bottom side of the box then the display contrast may be adjusted by a potentiometer located there. Use a narrow flat tip screwdriver to adjust the display contrast. If your hand-held unit does not have the hole, use the U5-CONTRAST utility to adjust the contrast. Press the “ENT” key and using the “UP” key, reduce the display contrast or using the “DOWN” key, increase the display contrast. To accept the changes, exit by pressing the "ENT" key. 5.5 T0-TESTING This branch allows control of the door close, open, and stop signals from the hand-held. This feature allows the hand-held unit to override the inputs at the J1 terminal block. However, the hand-held unit will itself be overridden by setting the INSP switch on the microcontroller board to the ON position. There are two options under the T1 branch: T1-AUTOMATIC and T2-SETUP. T1 allows selecting one of four submenus (T1A - T1D). T2 may be used to perform the setup. It is recommended that the initial setup after the first installation, be done with the switches located on the microcontroller board. 5.5.1 T1-AUTOMATIC To enter one of the submenus, press the “ENT” key and using the “UP” or “DOWN” keys, select the required closing speed reference level. Consecutive pressing of the “ENT” key brings the control into a submenu (DATA signal diode is lit) and enables four direction keys. The functions of the direction keys are as follows: “LEFT” - close command “RIGHT” - open command “DOWN - stop command “UP” - cancel the stop command (start command) The submenus allow choosing one of the closing speed reference inputs to test operation of the door operator in various modes. The submenu functions are self-explanatory. T1A NORMAL T1B NUDGE T1C H_DOOR1 T1D H_DOOR2 5.5.2 T2-SETUP One can use the T2 SETUP window to perform the setup of the door operator with the hand-held unit. The setup mode overrides all other modes, however it may be exited before its completion. To enter the setup mode press the “ENT” key and use the “LEFT” and “RIGHT” keys to close and open the door. The setup has to be started when the door is partially open. The close command has to be executed first. To quit the setup before it is fully completed press the “ESC” key. Uncompleted setup will not make any changes to the previous setup. 17
ECI2000TM05.doc 6. Laptop interface commands A laptop computer with any communications software may also be used to set up the door operator. For successful interface your computer must use an RS-232 serial link set to 4800 baud rate, 8 bits, no parity, one stop bit. The serial cable has to be plugged into the JPH1 DB-9 socket. A straight-through cable with a DB-9 plug at one end and a DB-9 socket at the other end must be used. Commands have to be typed as lower case letters. Each command consists of a “three character word” sometimes followed by an “ = “ sign and a number. If the number has an invalid format the door operator will respond with a FORMAT ERROR message. If an entered value is out range, the operator will respond with an OUT OF RANGE message. Proper format of the commands is shown in section 7.7 of this manual. Typing entered from the keyboard is echoed to the screen. If typed characters are echoed twice, disable the echoing option in your communications software. Initialization of the link starts with the “pcc” command. The door operator will answer with: PC_LINK, OK * MONITOR *. Each session has to be terminated with the “end” command. 18
ECI2000TM05.doc 7. Tables 7.1. Functions of the LEDs 7.1.1 Diodes D10 - D17 If D17 (red) is continuously lit or it is off, it indicates that the power-up self-test failed. The door operator has been disabled and the software will try to display the latest encountered error (when D16 is off) or the major failure source (when D16 is on). See table 7.1.1 and 7.1.2 for the failure lists. Table 7.1.1 (D17 ON, D16 ON, D15 OFF) D17, D16, D15 ON, ON, OFF D14 (if ON) Data stored in Eeprom not in range D13 (if ON) Eeprom failure, lower block D12 (if ON) Eeprom failure, upper block D11 (if ON) SRAM failure D10 (if ON) Register failure Table 7.1.2 (D17 ON, D16 OFF) Diodes D10 to D15 display a binary error code. If the self-test reports an error, write down the code of the error and repeat the power on reset. If the error persists, report it to Elevator Components Inc. and exchange the boards. Errors from 3 (000011) to 33 (100001), and from 40 (101000) to 48 (110000) are related to microcontroller hardware failures. Errors from 34 (1000010) to 38 (100110) are related to SRAM failures. Error 49 (110001) is related to eprom checksum failures. The error code displayed on the output port is linked to a hardware failure as listed in table 7.1.2. An "H" in the table on the next page denotes a lit LED. 19
ECI2000TM05.doc Table 7.1.2 D15 D14 D13 D12 D11 D10 Error Error H H #3 p3_register H #4 not used H H #5 p2_dir H H #6 p2_reg H H H #7 p2_mode H #8 not used H H #9 p5_dir H H #10 p5_reg H H H #11 p5_mode H H #12 wg_out H H H #13 wg_con H H H #14 wg_reload H H H H #15 wg_comp1 H #16 wg_comp2 H H #17 wg_comp3 H H #18 wg_protect H H H #19 portABdir H H #20 portABdata H H H #21 ad_time H H H #22 ad_test H H H H #23 t1control H H #24 comp2_con H H H #25 p1_dir H H H #26 p1_reg H H H H #27 p1_mode H H H #28 baud_rate H H H H #29 ptscount_ad H H H H #30 ptscount_comp2 H H H H H #31 ptscount_epa0 H #32 time_tick_50, time_tick_500, timer1_aux1-4 H H #33 pwm_period H H #34 cl_cycles, op_cycles H H H #35 error_buffer (SRAM) H H #6 hand-held unit buffer (SRAM) H H H #37 timers structure (SRAM) H H H #38 rdb, rdw, rdl command initialization H H H H #39 comm0 port ring buffer H H #40 a/d channel 3 H H H #41 a/d channel 4 H H H #42 a/d channel 2 H H H H #43 a/d channel 1 H H H #44 a/d channel 0 (higher than 2.5V + 0.050V) H H H H #45 a/d channel 0 (lower than 2.5V - 0.050V) H H H H #46 microcontroller ALU unit H H H H H #47 microcontroller ALU unit H H #48 microcontroller ALU unit H H H #49 eprom checksum H H H #50 not used H H H H #51 not used H H H #52 not used H H H H #53 not used 20
ECI2000TM05.doc Table 7.1.3 (D17 flashing) D17 (flashing) Software is executing (system heartbeat) D16 If ON - setup required or setup completed If flashing - setup in progress D15 ( if ON) Forced slowdown (emergency slowdown) D14 (if ON) Stop executed (stop command input activated) D13 (if ON) Reduced speed input(s) activated D12 (if ON) Stop requested (internal system command) D11 (if ON) Open command active D10 (if ON) Close command active 7.1.2 Diodes D3 - D9 These diodes are related to the output relays and the door close sensor Table 7.1.4 D7 “door closed” sensor activated (the door is within 1” of its fully closed position) D3 door closed” relay picked up D4 “door open” relay activated D5 “advanced door closed” relay picked up D6 “main” relay picked up (applies output voltage to the motor) D8 “door operator ready” relay picked up D9 “spare” relay output activated (only ECI-2000-1101 “no revision” board) 7.1.3 Diodes D36 - D39 These diodes signal the operation of the power bridge gating signals. Table 7.1.5 D36, D37 If flashing very quickly - power bridge controlled by the system If OFF -power bridge not working (shutdown) D38 Always off D39 Dynamic braking activated (DC bus discharge circuit activated) 7.2 User inputs User inputs are accessed through the 5-pin connectors J1 and J4 on the microcontroller board. Pin 5 of J1 (COM1) is a common wire for inputs: DO7, DO10, DO18 and DO4. Pin 5 of J4 (COM2) is a common wire for inputs: STOP, PHDT, H_D1 and H_D2. All the inputs are 120V AC/DC or 24V to 48V AC/DC (jumper selectable). All inputs are active HIGH. Refer to schematic 8.3.3 and 8.3.4. 21
ECI2000TM05.doc There is only one user input on the power board. This is an input exclusively used as an interface to the PANA633 light barrier. On the ECI-2000-1101 power boards the JH2 header is used as an input. On the ECI-2000-1101 rev. 1.0 power boards the J5 pin 7 is used as an input. Refer to schematics 8.5.1 and 8.5.2. 7.2.1 Functions of the inputs Table 7.2.1 (terminal block J1 on the microcontroller board) Connection Name Function of the input Pin 1 DO7 door close command Pin 2 DO10 door open command Pin3 DO18 door locking command Pin4 DO4 door nudging command Pin5 COM Common for pins 1 to 4 Table 7.2.2 (terminal block J4 on the microcontroller board) Connection Name Function of the input Pin 1 STOP door stop command Pin 2 PHDT photo-detector input (future use) Pin3 H_D1 heavy door 1 Pin4 H_D2 heavy door 2 Pin5 COM Common for pins 1 to 4 7.3 User outputs All the user outputs are in a form of a single pole double throw (SPDT) relay contact. The relays have been placed on the power board. The relay coils are opto-isolated from the microcontroller circuits. The contact ratings are listed below: Resistive load: maximum current 3A at 250V AC 3A at 30V DC minimum current 10ma, 5V Inductive load (P.F. 0.4, L/R = 7ms): maximum current 1.5 A at 250V 2A at 30V DC minimum current 10 mA, 5V These contacts can reliably operate with the opto-coupled controller inputs. 22
ECI2000TM05.doc Remarks: 1. Before replacing any relays, the power has to be switched off for at least 5 minutes to allow capacitors to discharge. 2. Relay coils are energized when the microcontroller signals are active high and the driver opto-coupler outputs are active low. 7.3.1 Functions of the outputs Table 7.3.1 (terminal block J4 on the power stage board) Pin Relay Name Diode Contact Function 1 K1 DCL D3 NO3 door closed limit, normally open contact 2 " " DO17 door closed limit, normally closed contact 3 " " COM3 common for the contacts 4 K2 DOL D4 NO4 door open limit, normally open contact 5 " " DO3 door open limit, normally closed contact 6 " " COM4 common for the contacts 7 K3 ADVCL D5 NO5 door closed advanced limit 8 " " NC5 door closed advanced limit 9 " " COM5 common for the contacts Table 7.3.2 (terminal block J5 on the power stage board) * Pin Relay Name Diode Contact Function 1 K5 READY D8 NO6 door operator ready, normally open contact 2 " " DC6 door operator ready, normally closed contact 3 " " COM6 common for the contacts 4 K6** AUX 9 NO7 aux. relay, normally open contact 5 " " NC7 aux. relay, normally closed contact 6 " " COM7 common for the contacts 7 PANA input input for PANA633, *** * terminal J5 and the relay sockets are not installed on the board during production. They may be optionally installed later. ** ECI-2000-1101 board: the auxiliary relay is energized when either the PANA633 or PHDT input has been activated. This function is controlled by the software. ECI-2000-1101 rev. 1.0: the auxiliary relay is controlled directly by the PANA633 input. It is not controlled by the door operator software or hardware. 23
ECI2000TM05.doc 7.4 Adjustable parameters and user interface command table 7.4.1 Hand-held unit and serial link commands * software version prior to version 1.11 ** software version 1.11 and later *** software version 1.14 and later PC Range ( * ) Range ( ** ) Menu Window text command (versions prior to 1.11) (versions. 1.11 & later) M0 MONITORING M1 DOOR SPEED dsp 0 - 1000 mm/s 0 - 1000 mm/s M2 MOTOR CURRENT mcu 0 - 4A 0 - 4A M3 CLOSE TIME clt 0 - 3276 seconds 0 - 3276 seconds M4 OPEN TIME opt 0 - 3276 sec 0 - 3276 sec M5 CLOSE CYCLES ccy 0 - (2^32 -1) 0 - (2^32 -1) M6 OPEN CYCLES ocy 0 - (2^32 -1) 0 - (2^32 -1) M7 POSITION pos (-4194304) - 4194303 (-4194304) - 4194303 M8 DOOR WIDTH wth 0 - 5000mm 0 - 5000mm M9 SYSTEM TIME ctm format h..hh:mm:ss format h..hh:mm:ss M10 BUS VOLTAGE bvl 0 - 300V 0 - 300V M11 LEM VOLTS cvl 0 - 5V 0 - 5V M12 SOFTWARE VERSION ver M13 INPUTS binary coded byte binary coded byte M14 INPUT PORT " " M15 LED PORT " " M16 OUTPUTS " " P0 PROGRAMMING P1 SPEEDS P1A CLOSE SPEED cls, cls= 0.2 - 0.8 m/s 0.2 - 0.8 m/s P1B HD1 SPEED hd1, hd1= 0.2 - 0.7 m/s 0.2 - 0.7 m/s P1C HD2 SPEED ( * ) hd2, hd2= 0.2 - 0.7 m/s 0.2 - 0.7 m/s P1C INT. SPEED ( ** ) hd2, hd2= P1D NUDGE SPEED ndg, ndg= 0.15 - 0.5 m/s 0.15 - 0.5 m/s P1E CLOSE SLOW css, css= 0.01 - 0.1 m/s 0.01 - 0.1 m/s P1F SCAN SPEED rsp, rsp= 0.01 - 0.14 m/s 0.01 - 0.14 m/s P1G OPEN SPEED ops, ops= 0.2 - 1.0 m/s 0.2 - 1.0 m/s P1H OPEN SLOW oss, oss= 0.01 - 0.1 m/s 0.01 - 0.1 m/s P1J PL SPEED pls, pls= 0.01 - 0.1 m/s 0.01 - 0.1 m/s P2 PROFILE P2A ACC. RATE acc, acc= 0.5 - 1.2 m/s2 0.5 - 1.2 m/s2 P2A ACC. CL. (***) acc, acc= P2B DEC. RATE dec, dec= 0.5 - 1.2 m/s2 0.5 - 1.2 m/s2 P2B DEC. CL. (***) dec, dec= 24
ECI2000TM05.doc P2C FAST RATE fdc, fdc= 0.5 - 2.5 m/s2 0.5 - 2.5 m/s2 P2D JERK ( * ) jrk, jrk= 1.0 - 8.0 m/s3 1.0 - 8.0 m/s3 P2D INT. RATE ( ** ) dei, dei= P2E ACC. OP. (***) aco, aco= P2F DEC. OP. (***) deo, deo= P3 CURRENTS P3A OVERCURRENT ovc, ovc= 2.5 - 4.0 A 2.5 - 4.0 A P3B ACC. CRNT acr, acr= 1.5 - 3.3 A 1.5 - 3.3 A P3C DEC. CRNT dcr, dcr= 1.5 - 3.3 A 1.5 - 3.3 A P3D OPEN CRNT ocr, ocr= 0.7 - 1.8 A 0.7 - 1.8 A P3E CLOSE CRNT ccr, ccr= 0.7 - 1.8 A 0.7 - 1.8 A P3F NUDGE CRNT ncr, ncr= 0.5 - 1.3 A 0.5 - 1.3 A P3G HLD OP CRNT hcr, hcr= 0.5 - 1.0 A 0.5 - 1.0 A P3H STALL CRNT scr, scr= 0.5 - 1.0 A 0.5 - 1.0 A P4 DISTANCES P4A CL. SLOW csc, csc= 0 - 100 mm 0 - 100 mm P4B OP. SLOW cso, cso= 0 - 100 mm 0 - 100 mm P4C ADV. DCL acl, acl= 25 - 254 mm 25 - 254 mm P4D PREOPEN pld, pld= 0 - 100 mm 0 - 100 mm P5 DOOR DATA P5A DOOR MASS mas 30 - 520 kg 30 - 520 kg 66 - 1155 lb 66 - 1155 lb P5B HD1 MASS h1m 40 - 520 kg 40 - 520 kg 88 - 1155 lb 88 - 1155 lb P5C HD2 MASS h2m 40 - 520 kg 40 - 520 kg 88 - 1155 lb 88 - 1155 lb P6 CONTROL P6A IKP ikp, ikp= 300 - 1000 300 - 1000 P6B IKI iki, iki= 10 - 100 10 - 100 P6C VKP vkp, vkp= 10 - 100 10 - 100 P6D VKI vki, vki= 5 - 30 5 - 30 P6E VKD vkd, vkd= 0 - 100 0 - 100 P6F PKP pkp, pkp= 0 - 100 0 - 100 P6G SCL psc,psc= 32 - 320 32 - 320 P6H FER fer, fer= 5 % - 30% 5 % - 30% E0 ERROR LOG E1 - E30 dpe read error E1 read error E1 dpp read next error read next error 25
ECI2000TM05.doc cll clear log clear log U0 UTILITIES U1 UNIT SYSTEM met, imp U2 D/A CHANNEL dta= U3 PASSWORD pas= U4 NEW PASSWORD pas= U5 CONTRAST T0 TESTING T1 AUTOMATIC T1A NORMAL T1B NUDGE T1C H_DOOR1 T1D H_DOOR2 T2 SETUP 7.4.2 Serial link commands (laptop serial link) The PC commands listed below do not have equivalence in the hand-held unit. They are used to manage the serial link. Each command has to be followed by the “ENT” key on the laptop keyboard. pcc start communications link with a laptop serial port end end communications link with a laptop serial port wrt permanently store all changed parameters (when some parameters have been changed with commands of a format xxx=data, they have not been stored permanently and the changes will be lost if the power is switched off. To store the changed data permanently always execute “wrt” command after you accept the changes). 7.5 Error log: list of reported errors and messages 7.5.1 Errors reported by all software versions. NO FAULTS - the log is empty, no faults present EXT. SOURCE - external shutdown by the power module protection SHUTDOWN - shutdown by the software protection routine (*) FORMAT ERROR - data format error TIMER2 ERR. - timer2 error, hardware failure EEPROM ERROR - eeprom memory write or read error PROG. FAIL. - programme failure A/D CH. ERR. - a/d channel error (*) TIMER1 ERROR - timer1 error (*) POLARITY -encoder or motor polarity incorrect PARAM. ERR. -parameter entry error; the entry error has been corrected 26
ECI2000TM05.doc COMP2 INTRPT - compare2 channel error (*) RX ERROR - receive channel error (*) TX ERROR - transmit channel error (*) INV. BRANCH - invalid software branch INV. ENTRY - invalid data entry, format error WG_CNTR ERR. - waveform generator counter error OUT OF RANGE - invalid data, out of range SETUP ERR. - setup mode error WG INTERRUPT - waveform generator interrupt error NO ACCESS - access to certain locations denied WRITE FAIL. - eeprom memory write failure STOP DRIVE - request to stop the drive; message only SELF RESET - self reset occurred just before the last power up LOGIC ERROR - logic error found in logic equations RUN TIMEOUT - motor run time exceeded STOP TIMEOUT - motor stop time-out CALCUL. ERR. - calculation error DCL MISSING - door close sensor missing (scan mode) DCL ERROR - door close sensor not found where expected (auto mode) CLOSE T-OUT - close cycle time-out OPEN TIMEOUT - open cycle time-out STOP MISSING - motor was moving when stalled conditions were expected DCL ZONE ERR - door close limit zone error OVERCURRENT - motor overcurrent DIST. ERROR - distance error in the scan mode SCAN ERROR - scan mode error NO_ACKN. - no acknowledge received while writing to eeprom (*) SENS. ERROR - erroneous door close sensor operation (reset mode) HYST. ERROR - door close limit hysteresis error; message UNDERVOLTAGE - DC bus undervoltage OVERVOLTAGE - DC bus overvoltage OVERSPEED - motor overspeed COUNT > DCL. - position counter greater than the door fully closed position count (automatic mode) COUNT < DOL. - position counter less than the door fully open position count (automatic mode) COUNT < DCL - position counter less than the position of the door closed sensor count when the sensor has been activated (automatic mode) PRG. ERR. 01 - error while executing the scan mode routine ENCODER LOSS - encoder failure or connection lost or abrupt door stop AD INTERRUPT - a/d channel interrupt error 7.5.2 Errors reported only by software versions prior to 1.11 7.5.3 Errors reported only by software version 1.11 and later 27
ECI2000TM05.doc 7.5.4 Errors reported only by software version 1.14 and later 7.6 Laptop link: list of the commands These commands are used to set the door parameters from the laptop. 7.6.1 Door speeds: Command Range: Description: cls - - read the closing speed cls= - 200 - 800 mm/s - change the closing speed - 0.65 - 2.63 ft/s css - - read the slow closing speed css= - 10 - 100 mm/s - change the slow closing speed - 0.03 - 0.33 ft/s hd1 - - read the heavy door 1 closing speed hd1= - 200 - 700 mm/s - change the heavy door 1 closing speed - 0.65 - 2.30 ft/s hd2 - - read the heavy door 2 closing speed hd2= - 200 - 700 mm/s - change the heavy door 2 closing speed - 0.65 - 2.30 ft/s - change the intermediate speed ndg - - read the nudging speed ndg= - 150 - 500 mm/s - change the nudging speed - 0.49 - 1.64 ft/s ops - - read the opening speed ops= - 200 - 1000 mm/s - change the opening speed - 0.65 - 3.28 ft/s oss - - read the slow opening speed oss= - 10 - 100 mm/s - change the slow opening speed - 0.03 - 0.30 ft/s pls - - read the pre-opening slow speed pls= - 10 - 100 mm/s - change the pre-opening slow speed - 0.03 - 0.30 ft/s rsp - - read the scan speed rsp= - 10 - 140 mm/s - change the scan speed - 0.03 - 0.46 ft/s 7.6.2 Profile shape: Command Range: Description acc - - read the acceleration rate (or close cycle acc. rate) acc= - 500 – 1200 mm/s2 – change the acceleration rate (or close cycle acc. rate) - 1.64 - 3.94 ft/s2 dec - - read the deceleration rate dec= - 500 - 1200 mm/s2 - change the deceleration rate 28
ECI2000TM05.doc - 1.64 - 3.94 ft/s2 fdc - - read the fast deceleration rate fdc= - 500 - 2500 mm/s2 - change the fast deceleration rate - 1.64 - 8.20 ft/s2 jrk - - read the jerk rate jrk= - 1000 - 8000 mm/s3 - change the jerk rate - 3.28 - 26.25 ft/s3 dei - - read the intermediate deceleration rate dei= - - change the intermediate deceleration rate aco - - read the open cycle acceleration rate aco= - - change the open cycle acceleration rate dco - - read the open cycle deceleration rate dco= - - change the open cycle deceleration rate 7.6.3 Motor currents: Command Range: Description acr - - read the acceleration current limit acr= - 1.5 - 3.3 A - change the acceleration current limit ccr - - read the closing current limit, door closing torque ccr= - 0.7 - 1.3 A - change the closing current limit dcr - - read the deceleration current limit dcr= - 1.5 - 3.3 A - change the deceleration current limit hcr - - read the hold open current limit hcr= - 0.5 - 1.0 A - change the hold open current limit ncr - - read the nudging current limit, nudging torque ncr= - 0.5 - 1.3 A - change the nudging current limit ocr - - read the opening current limit ocr= - 0.7 - 2.5 A - change the opening current limit ovc - - read the overcurrent tripping point ovc= - 2.5 - 4.0 A - change the overcurrent tripping point scr - - read the stall current triggering point scr= - 0.5 - 1.0 A - change the stall current triggering point 7.6.4 Distances: Command Range: Description acl - - read the advanced door closed limit setting acl= - 0 - 254 mm - change the advanced door closed limit setting - 0 - 10.0 inch csc - - read the slow closing distance csc= - 0 - 100 mm - change the slow closing distance - 0 - 3.94 inch cso - - read the slow opening distance cso= - 0 - 100 mm - change the slow opening distance - 0 - 3.94 inch pld - - read the pre-opening distance 29
ECI2000TM05.doc pld= - 0 - 100 mm - change the pre-opening distance - 0 - 3.94 inch 7.6.5 Door mass (weight): Command Range: Description h1m - 40 - 520 kg - read the heavy door 1 mass 88 - 1155 lb h2m - 40 - 520 kg - read the heavy door 2 mass 88 - 1155 lb mas - 30 - 520 kg - read the normal door mass 66 - 1155 lb 7.6.6 Digital controllers: Command Range: Description fer - - read the “following error” fer= - 5 - 30 % - change the “following error” iki - - read the current controller integral gain iki= - 10 - 100 - change the current controller intergral gain ikp - - read the current controller proportional gain ikp= - 300 - 1000 - change the current controller proportional gain pkp - - read the position controller proportional gain pkp= - 0 - 100 - change the position controller proportional gain psc - - read the position controller scaler psc= - 32 - 320 - change the position controller scaler vkd - - read the speed controller derivative gain vkd= - 0 - 100 - change the speed controller derivative gain vki - - read the speed controller integral gain vki= - 5 - 100 - change the speed controller integral gain vkp - - read the speed controller proportional gain vkp= - 10 - 100 - change the speed controller proportional gain 7.6.7 Monitoring (read only commands): Command Range: Description bvl - 0 - 300V - read the DC bus voltage ccy - 0 - (2^32 -1 ) - read the number of closing cycles clt - 0 - 3276 s - read the latest door closing time cvl - 0 - 5V - read the LEM sensor voltage 30
ECI2000TM05.doc ctm - 0 - (2^32 -1) s - read the system time dsp - 0 - 1000mm/s - read the door speed - 0 - 3.28 ft/s mcu - 0 - 5A - read the motor current ocy - 0 - (2^32 -1) - read the number of opening cycles opt - 0 - 3276 s - read the latest door opening time pos - (-4194304) - 4194303 - read the door position (encoder pulses) ver - - report software version wth - 0 - 5000 mm - read the door width 7.6.8 Error log: Command Range: Description cll - - clear error log dpe - - read the latest error log entry dpp - - read the next error log entry 7.6.9 Miscellaneous commands: Command Range: Description dta= - 0 - 9 - select D/A channel for TP3 analog output 0 - motor speed 1 - speed reference 2 - speed error 3 - motor current 4 - current reference 5 - current error 6 - position error 7 - speed correction by the position controller 8 - LEM sensor output voltage 9 - DC bus voltage end - - end communications link with a laptop serial port imp - - select the Imperial unit system met - - select the metric unit system pas= - 0 - 9998 - enter or change the password pcc - - start communications link with a laptop serial port wrt - - permanently store all changed parameters Remark: When some parameters have been changed with commands of the format “xxx=data“, they have not been stored permanently and the changes will be lost if the power is switched off. To store the changed data permanently execute “wrt” command after each command, which changes parameters. 7.6 RS232 extension cable. An optional extension cable may be used to allow adjustment of the door within elevator cab. The cable is terminated at the terminal block J5 on the microcontroller board. Place the DB-9 31
You can also read