MANUEL D’UTILISATION

                               EATON

 DIVERS ELECTRICITE
ONDUL 4P EL 1200 USB

Besoin d’un conseil ? Une question sur ce produit ?
RDV sur la communauté SAV Darty : https://sav.darty.com
Déjà 1/2 million de solutions grâce à l’avis des utilisateurs.
www.eaton.com

                      Ellipse ECO
                      500/650/800/
                      1200/1600

                      Installation and
                      user manual
                      English - Français
                      Deutsch - Italiano
                      Español - Nederlands
                      Português - Eλληνiκά
                      Polski - Česky
                      Solvenčina - Slovensko
                      Magyar - Türkçe
                      РУCCКИЙ
                      Svenka - Suomi

614-06803-00.indd 1                    10/12/2010 11:15:07
Packaging

                                                 1
                                                                                   2                     3
                                    IEC                     USB models
                                    models
                4
                                                                 5

  Caution!
  l Before installing the Ellipse,           l Antes da instalação do Ellipse,         l Az Ellipse telepítése előtt
  read the booklet 3 containing the          ler o caderno 3 onde constam              olvassa el a 3 -es könyvet, mely a
  safety instructions to be respected.       as instruções de segurança                betartandó biztonsági előirásokat
  Then follow the instructions given         a respeitar. Depois, seguir as            tartalmazza. Ezután kövesse a jelen,
  in this manual 2 .                         instruções do presente manual 2 .          2 -ös kezikönyv utasításait.
  l Avant l'installation de Ellipse,                                                   l Ellipse'in tesisatini yapmadan
                                             p
  lire le livret 3 qui présente les                                                    önce, uyulacakgüvenliktalimatlarini
                                                                 3
  consignes de sécurité à respecter.                                                   gösteren 3 sayili kitapçiği
  Suivre ensuite les instructions du                                                   okuyunuz. Dana sonra isbu 2
  présent manuel 2 .                                                                   sayili ei kitabindaki talimatlara
  l Vor Installation des Ellipse                                           2           uyunuz.
  die im Heft 3 genannten                    l Przed zainstalowaniem Ellipse,          p
  Sicherheitsvorschriften lesen.             należy przeczytać instrukcję 3 ,
  Anschließend die Anweisungen               która zawiera niezbędne zalecenia                                 3
  im vorliegenden Handbuch 2                 bezpieczeństwa.
  befolgen.                                  Następnie należy zapoznać się z
  l Prima dell’installazione del             zaleceniami zawartymi w niniejszej
  Ellipse, leggere attentamente le           instrukcji 2 .                                                    2
  istruzioni di sicurezza riportate sul      l Před instatací zdroje Ellipse
  libretto 3 .                               si prostudujte příručku 3 kde
                                             najdete bezpečnostní předpisy,             3
  In seguito, attenersi alle istruzioni
  riportate sul presente manuale 2 .         které je třeba dodržovat.
                                             Dále postupujte podle pokynů                     2
  l Antes de la instalación del Ellipse,
  leer el manual 3 que presenta las          uvedených v příručce 2 .                  l Innan installation av Ellipse,
  instrucciones de seguridad a cumplir.      l Pred inštaláciou výpustky si            läs instruktionsmanualen
  A continuación, seguir las                 prečítajte knižku 3 , v ktorej sú          3 innehållande
  instrucciones del presente manual          uvedené bezpečnostné príkazy,             säkerhetsinstruktionerna och
   2.                                        ktoré je potrebné dodržať. Potom          följ sedan dem. Följ sedan
  l Lees voordat u het Ellipse
                                             postupujte podľa pokynov tejto            instruktionerna som ges i denna
  gaat installeren eerst de                  príručky 2 .                              manual 2 .
                                             l Preden instalirate Ellipse,             l Lue nämä ohjeet ennen
  veiligheidsinstructies in boekje 3 .
                                             preberite knjižico 3 , v kateri so        Ellipse asennusta
  Volg daarna de instructies van deze
                                             varnostna navodila, ki jih je treba       turvallisuusohjeet 3 ja
  handleiding 2 .
                                             upoštevati. Nato sledite navodilom        käyttöohjeet 2 .
                                             tega priročnika 2 .

  2                                                                                                                614-06803-00

614-06803-00.indd 2                                                                                          10/12/2010 11:15:07
Quick start

   A FR / DIN                      IEC

   B
                 500 / 650 / 800                          1200 / 1600

   C                                     D   USB models

  614-06803-00                                                                       3

614-06803-00.indd 3                                                     10/12/2010 11:15:07
Quick start

      E                                                           F   USB models

                                                                  Register warranty at: powerquality.eaton.com

  Battery disposal and safety
  l Caution. Battery service life is reduced by 50 % for         l The battery must be disposed of in accordance
  every ten degrees above 25 °C.                                 with applicable regulations. To remove the battery
  l The battery elements must be replaced exclusively            elements, shut down the UPS (button 12 OFF), remove
  by qualified personnel (risk of electrocution), with           the power cord and proceed as indicated in page 4
  new elements approved by EATON to ensure correct               "Battery change".
  operation of the UPS.

  Battery change

      Ellipse 500 / 650 / 800

                                    b

                                    c                        d
              a
                                                                                                          e

      Ellipse 1200 / 1600

                                b

                                c
          a

                                                                                                           e

                                                              d

  lWarning: take care not to inverse the polarity + (red) and - (black) when connecting the batteries as this will
  destroy the device.

  4                                                                                                            614-06803-00

614-06803-00.indd 4                                                                                       10/12/2010 11:15:08
Technical characteristics

   Ellipse ECO                                 500              650              800           1200          1600
   lUPS power                                500 VA /        650 VA /         800 VA /       1200 VA /     1600 VA /
                                              300 W           400 W             500 W         750 W         1000 W
   l Nominal input voltage                                  184 V - 264 V, adjustable to 161 V - 284 V
   l Input frequency                                            50/60 Hz (46 - 70 Hz working range)
   l Voltage/frequency of battery backup                220 V / 230 V / 240 V +15 % -20 % (50/60 Hz ± 1 %)
   outlets 9 in battery mode
   l Total output current for all outlets                                     10 A max
   l Output current of battery backup       2.3 A max        3 A max          3.6 A max      5.5 A max       7.3 A max
   outlets 9
   l Leakage current                                                            0.4 mA
   l Input protection                                             10 A resettable circuit breaker
   l Transfer time                                                           5 ms typical
   l Telephone surge protection                                     Tel, ISDN, ADSL, Ethernet
   l Sealed lead-acid battery              12 V, 4.5 Ah     12 V, 7 Ah        12 V, 9 Ah    2x12V, 7 Ah     2x12V, 9 Ah
   l Automatic battery test                                                  Once a week
   l Average battery life                 4 years typical, depending on temperature and amount of discharge cycles
   l Operating temperature                                                    0 to 35 °C
   l Storage temperature                                                   -25 °C to +55 °C
   l Operating relative humidity                                              0 to 85 %
   l Operating elevation                                                     0 to 2000 m
   l Safety standards                                         IEC 60950-1, IEC 62040-1, CE certified
   l Electromagnetic compatibility                                        IEC 62040-2, C1*
   standards
   l Warranty                                                                   2 years
   l Dimensions (mm)                                      263 x 81 x 235                             305x81x312
   l Weigth (Kg)                                2.9                     3.6                      6.7             7.8

  (*) Warning: Output cables should not exceed 10m length.

  Performances tested according to IEC 61643-1 (class 3) standard for 8/20 µs surge wave
    AC input source protection,                500             650               800          1200            1600
    Ellipse ECO:
   l Uoc                                                    6 kV / 2 kV                           6 kV / 1.8 kV
   (common mode / differential mode)
   l Up                                                   1.8 kV / 0.7 kV                         1.5 kV / 1 kV
   (common mode / differential mode)
   l In                                                                          3 kA
   Dielectric isolation
   l AC Ground                                                              1500 Vac, 50 Hz
   l AC / TEL                                                               3000 Vac, 50 Hz
   l Tel / Ground                                                           1000 Vac, 50 Hz
   Temporary overvoltage (TOV)
   l   Uc                                                                      250 Vac
   l   Ut                                                                      430 Vac
   Energy dissipation                                                         461 Joules

  614-06803-00                                                                                                            5

614-06803-00.indd 5                                                                                       10/12/2010 11:15:08
Operating conditions                   automatically deactivated and the         autonomy after it has been charged
          l This product is an Uninterruptible   peripherals shut down.                    for 8 hours. It is recommended that
          Power Supply (UPS) for computers       This function (deactivated by             the UPS be permanently connected
          and their peripherals, television      default) is validated and configured      to the AC power supply to ensure
                                                 using the configuration tool              the best possible autonomy.
English

          sets, stereo systems and video
          recorders... It must not be used to    integrated in the software.               l Switching-on the UPS: press

          supply other electrical equipment      Note: When the function is                button 12 for about 1 second.
          (lighting, heating, household          activated, do not connect critical        l Filtered outlets 8 without

          appliances, etc.).                     applications to EcoControl                battery backup: Equipment
          l UPS can be installed in
                                                 outlets.                                  connected to these outlets is
          horizontal, vertical position, or                                                supplied as soon as the AC cord 4
                                                 Threshold setup                           is plugged in. They are not affected
          placed in Rack 2U (optional kit).
                                                 A default setup ensures the correct       by button 12 .
          UPS connections                        operation of the EcoControl               l Battery backup outlets 9 :
          l  Connect the UPS 1 to the            function. However, depending              Equipment connected to these
          AC-power system via a wall outlet      on the consumption of the main            outlets is supplied as soon as
          with an earth connector, using the     load, the trigger threshold of            button 12 turns green (see figure
          supplied cord 4 for a UPS with         the EcoControl function may               E). These outlets can be turned on
          FR/DIN sockets or with the supply      have to be modified using the             even if the UPS is not connected to
          cord of your computer for a UPS        configuration software supplied           AC power (button 12 flashes).
          with IEC sockets (see figure A).       with the UPS:                             l AC-power disturbance: If AC
                                                 l First, make sure that the function      power is disturbed or fails, the UPS
          l Plug critical equipment
          (computer, monitor, modem,             is activated in the "EcoControl           continues to operate on battery
          etc.) into the outlets 9 providing     Function" tab of the configuration        power. Button 12 flashes green.
          battery backup power and surge         tool.                                     In normal mode, the audio alarm
                                                 l If the peripherals connected            beeps every ten seconds, then
          protection (see figure B), taking
          care not to exceed the rated current   to the EcoControl outlets do not          every three seconds when the end
          indicated in amperes.                  switch off when the main load is          of battery backup time is near. In
          l Other devices (printer, scanner,
                                                 not in normal operation (ex: when         silent mode (see the section on
          fax, etc.) can be connect to the       in standby mode), the detection           settings), the audio alarm simply
          filtered outlets 8 that provide        threshold value must be set to            beeps once when the UPS transfers
          surge protection (see figure B). The   High.                                     to battery power.
                                                 l If the rated consumption level          l If the power outage lasts longer
          filtered outlets are not backed up
          by battery power in the event of a     of the main load is low and the           than the battery backup time, the
          power outage.                          EcoControl outlets shut down              UPS shuts down and automatically
          l Optional Internet modem /
                                                 when the main load is operating           restarts when power is restored.
          Network connection:                    normally, the detection threshold         Following a complete discharge, a
          A modem or Ethernet data line          value must be set to Low.                 few hours are required to recharge
          can be protected against surges by                                               the battery back to full backup time.
                                                 Operation
          connecting it via the UPS. Connect                                               l To save battery power, it is possible
          the existing device cable between       8 : Filtered outlets.                    to press button 12 to cut the supply
          the wall outlet and the UPS, and        9 : Battery backup outlets.              of power to the devices connected
          use a similar cable between the        10 : LED ON indicate that surge          to the battery backup outlets.
          UPS and the device, as indicated in                                              l Lightning protection: All outlets,
                                                       protection is active.
          figure C (cable not supplied).                                                   whether backed up or simply
                                                 11 : LED ON indicate a UPS fault.
          l Optional USB connection:                                                       filtered, include surge protection,
                                                 12 : ON/OFF button for the battery       whatever the position of button 12 .
          The UPS device can be connected
          to the computer using the USB                backup outlets.                     l Shutdown of the battery backup
          cable 5 supplied.                      13 : Protection circuit breaker.          outlets 9 : Press button 12 for
          The software is available on the                                                 more than two seconds.
                                                 l Battery charge: The UPS
          CD-ROM 5 or downloadable               charges the battery as soon as it is
          from powerquality.eaton.com            connected to the AC outlet, whether
          (see figures D and F).                 button 12 is pressed or not. When
          Register for the warranty on           used for the first time, the battery
          powerquality.eaton.com.                will only provide its maximum
          Master and EcoControl                                         Ellipse 500 / 650 / 800       Ellipse 1200 / 1600
          outlets operating
          procedure                                                                                                            8
          In order to limit energy
          consumption of peripherals
          (scanner, printer) in standby mode,                      12
          the Ellipse ECO is equipped
          with EcoControl outlets that are                         10
          dependent on the Master outlet.                          11                             9
                                                                                                                                9
          When the main application
          supplied by the Master outlet                                                           8
          (computer) is shut down,
          the EcoControl outlets are                                                          13                               13

          6                                                                                                                 614-06803-00

    614-06803-00.indd 6                                                                                               10/12/2010 11:15:08
Troubleshooting (For further information, visit the www.powerquality.eaton.com site or contact after-sales
  support.)
            Problem                                 Diagnostic                            Solution
   1

                                                                                                                                     English
            l The battery backup outlets 9 are l Button 12 is not lighted on.             l Press button 12 and check that it
            not supplied with power.                                                      turns green.
   2        l The connected devices are not     l The devices are not connected to        l Connect the devices to the battery
            supplied when AC power fails.       the battery backup outlets 9 .            backup outlets 9 .
   3        l AC power is available, but the    l Circuit breaker 13 , located under      l Disconnect excess equipment
            UPS operates on battery power.      the UPS, has been tripped by an           and reset the circuit breaker 13 by
                                                overload on the UPS output.               pressing the corresponding button.
   4        l The filtered outlets 8 are not    l The wall outlet is not supplied.        l Supply power to the wall outlet.
            supplied.                           l Circuit breaker 13 , located under      l Disconnect excess equipment
                                                the UPS, has been tripped by an           and reset the circuit breaker 13 by
                                                overload on the UPS output.               pressing the corresponding button.
   5        l Green button 12 flashes           l The UPS frequently operates             l Have the electrical installation

            frequently and audio alarm beeps. on battery power because the AC             checked by a professional or use
                                                power source is of poor quality.          another wall outlet.
   6        l Green button 12 flashes and audio l The UPS battery backup outlets          l Disconnect excess equipment
            alarm beeps continuously.            9 are overloaded.                        connected to the battery backup
                                                                                          outlets 9 .
   7        l Red LED 11 is on and the audio        l A fault has occurred on the UPS.    l Call after-sales support.

            alarm beeps every 30 seconds.           The battery backup outlets 9 are
                                                    no longer supplied.
   8        l  Green LED 10 is off and the          l Surge protection is no longer       l   Call after-sales support.
            filtered outlets 8 are supplied.        provided.
   9        l The telephone line is disturbed or    l Surge protection on the telephone l Disconnect the telephone line
            modem access is not possible.           line is no longer provided.         from the wall outlet.
                                                                                        l Call after-sales support.

   10       l   Red LED 11 flashes.                 l The battery has reached the end   l Have the battery replaced.
                                                    of its service life.
   11       l EcoControl outlets keep powered       l EcoControl function is not        l Activate or set properly
            when main application (Master           activated or not properly set.      EcoControl function using the
            outlet) is stopped.                                                         software provided with the product.

  Advanced customizing of your UPS
    Sensitivity to variations of the AC power supply                 Audio alarm

    l Only to be used if frequent switching to the UPS               l Possibility of deactivating the audio alarm when the
    battery due to large variations in the AC supply                 UPS is operating on the battery.
    voltage.                                                         l Accessing the programming mode: with the device
    l Accessing the programming mode: with the device                switched off, press button 12 for 11 s and release it
    switched off, press button 12 for 6 s and release it             when the audio alarm sounds.
    once LEDs 10 11 have come on.                                    l Display   of the 2 possible audio alarm modes:
    l Display of the 3 possible voltage ranges according to
    the status of LEDs 10 and 11 :
   Normal mode               Low range             Low and high     Normal mode (factory             Silent mode:
   (factory                  mode:                 range mode:      configuration):                  the UPS emits a single
   configuration):           AC supply             AC supply        the UPS emits a beep             beep when switching to
   AC supply                 between 161V          between 161V     every 10 s when operating        battery operation and
   between 184V              and 264V              and 284V         on its battery.                  then remains silent.
   and 264V
       11          12       11        12       11         12
                                                                          Normal mode                   Silent mode
                                                                          activated:                    activated:
                                                                          programming by                programming by a
            11 10 12             11 10 12          11 10 12               continuous beep.              beep every second.

      Change from one mode to another by successively                  Change from one mode to another by successively
      pressing button 12 .                                             pressing button 12 .
    l Memorizing the mode: 10 s after the last press of the          l Memorizing the mode: 5 s after the last press of the
    button.                                                          button.
  614-06803-00                                                                                                                   7

614-06803-00.indd 7                                                                                                 10/12/2010 11:15:08
Conditions d'utilisation                  La validation et le paramétrage             utilisation, la batterie ne donne
           l Cet appareil est une Alimentation       de cette fonction (désactivée par           sa pleine autonomie qu'après
           Sans Interruption (ASI) conçue            défaut) se font par l’intermédiaire         une recharge de 8 heures. Pour
           pour alimenter un ordinateur et ses       de l’outil de configuration intégré         conserver la meilleure autonomie,
FRANÇAIS

           périphériques, des appareils de TV,       au logiciel.                                il est conseillé de laisser l'ASI
           HI-FI, Vidéo, à l’exclusion de tout       Note : lorsque la fonction                  branchée en permanence sur le
           autre appareil électrique (éclairage,     est activée, ne pas connecter               réseau électrique.
           chauffage, électroménager...).            d’applications critiques sur les            l Mise en marche de l'ASI : appuyer
           l L'ASI peut être installée en
                                                     prises EcoControl.                          sur le bouton 12 environ 1 seconde.
           position horizontale, verticale, ou       Paramétrage des seuils                      l Prises filtrées 8 non secourues :
           en Rack 2U (kit optionnel).               Un paramétrage par défaut assure            les appareils raccordés sur ces
                                                     le bon fonctionnement de la                 prises sont alimentés dès que le
           Raccordement de l'ASI                                                                 câble d’entrée 4 est branché sur
                                                     fonction EcoControl.
           l  Raccorder l'ASI 1 au réseau                                                        une prise murale. Le bouton 12 ne
                                                     Cependant, selon le niveau
           électrique sur une prise murale                                                       les commande pas.
                                                     de consommation de la
           avec terre, à l'aide du cordon fourni                                                 l Prises secourues 9 : les
                                                     charge principale, il peut être
            4 pour une ASI avec prises FR/DIN        nécessaire de modifier le seuil             appareils raccordés sur ces prises
           ou avec le cordon d'alimentation                                                      sont alimentés dès que le bouton
                                                     de déclenchement de la fonction
           de votre ordinateur pour une ASI                                                      12 est allumé en vert (voir figure
                                                     EcoControl en utilisant le logiciel
           avec prises IEC (voir figure A).                                                      E). Ces prises peuvent être mises
                                                     de configuration livré avec
           l Connecter les prises des                                                            en marche même si l'ASI n'est pas
                                                     l’onduleur :
           appareils critiques (ordinateur,                                                      connectée au réseau électrique
                                                     l s’assurer tout d’abord que la
           écran, modem...) sur les prises                                                       (bouton 12 clignotant).
                                                     fonction soit bien activée dans le
           secourues par la batterie 9 et                                                        l Perturbation du réseau
                                                     volet "Fonction EcoControl" de
           protégées contre les surtensions                                                      électrique : si la tension de ce
                                                     l’outil de configuration.
           (voir figure B), en ne dépassant pas                                                  réseau est mauvaise ou absente,
                                                     l si les périphériques connectés sur
           le courant indiqué en Ampères.                                                        l'ASI continue à fonctionner sur
                                                     les prises EcoControl ne s’arrêtent
           l Les autres appareils (imprimante,                                                   batterie : le bouton 12 clignote en
                                                     pas quand la charge principale
           scanner, fax…) peuvent être                                                           vert. En mode normal, l’alarme
                                                     n’est pas en fonctionnement
           branchés sur les prises filtrées et                                                   sonore émet un signal toutes les
                                                     normal (ex : pendant une mise
           protégées contre les surtensions                                                      10 secondes, puis toutes les
                                                     en veille), il est nécessaire
            8 (voir figure B); les prises filtrées                                               3 secondes lorsque la fin
                                                     d’augmenter la valeur du seuil de
           ne sont pas secourues en cas de                                                       d'autonomie batterie approche. En
                                                     détection au niveau Haut.
           coupure de courant.                                                                   mode silence (voir § ajustements),
                                                     l si le niveau de consommation
           l Liaison Modem Internet / réseau                                                     l'alarme sonore émet un bip au
                                                     nominal de la charge principale
           facultative : la ligne modem ou                                                       passage sur batterie.
                                                     est faible et que les prises
           réseau Ethernet peut être protégée                                                    l Si la durée de la coupure du
                                                     EcoControl s’arrêtent alors que
           contre les surtensions en la                                                          réseau électrique dépasse
                                                     la charge principale fonctionne
           raccordant via l'ASI. Pour celà,                                                      l'autonomie batterie, l'ASI s'arrête
                                                     normalement, il est nécessaire
           relier d'une part la prise murale à                                                   puis redémarre automatiquement
                                                     d’abaisser la valeur du seuil de
           l'ASI avec le cordon de l'appareil                                                    au retour du réseau électrique.
                                                     détection au niveau Bas.
           à protéger, et d'autre part l'ASI à                                                   Après décharge complète, quelques
           cet appareil à l'aide d'un cordon         Utilisation                                 heures sont nécessaires pour
           identique, comme indiqué figure C          8 : prises filtrées.                       restaurer l'autonomie complète.
           (cordon non fourni).                                                                  l Par souci d'économie d'énergie,
                                                      9 : prises secourues par batterie.
           l Liaison USB facultative :                                                           le bouton 12 peut être utilisé pour
           l’appareil ASI peut être connecté         10 : V oyant allumé, protection anti-
                                                                                                 couper l’alimentation électrique
           à l’ordinateur via le câble USB 5              surtensions active.
                                                                                                 des appareils raccordés sur les
           fourni.                                   11 : Voyant allumé, défaut de l'ASI.        prises secourues.
           Le logiciel est disponible sur le         12 : Bouton de mise en service ou          l Parafoudre : toutes les prises,
           CD-ROM 5 ou peut être téléchargé                d'arrêt des prises secourues.         secourues ou non, en bénéficient
           à partir du site powerquality.eaton.      13 : Disjoncteur de protection.             quel que soit l’état du bouton 12 .
           com (voir les figures D et F).            l  Charge batterie : l'ASI charge sa        l Arrêt des prises secourues 9 :
           Enregistrement de la garantie sur         batterie dès qu’elle est connectée          appuyer plus de 2 secondes sur le
           le site powerquality.eaton.com.           au réseau électrique quel que soit          bouton 12 .
           Mode de fonctionnement des                l'état du bouton 12 . A la première
           prises Master et EcoControl                                        Ellipse 500 / 650 / 800       Ellipse 1200 / 1600
           Afin de limiter la consommation
           d’énergie des périphériques                                                                                              8
           (scanner, imprimante) en mode
           veille, Ellipse ECO est muni de
           prises EcoControl dépendantes                                 12
           de la prise Master (voir figure B).
                                                                         10
           Quand l’application principale
                                                                         11                             9
           alimentée par la prise Master                                                                                             9
           (ordinateur) est arrêtée, les prises
           EcoControl sont automatiquement                                                              8
           désactivées et les périphériques
                                                                                                    13                              13
           s’arrêtent.
           8                                                                                                                      614-06803-00

     614-06803-00.indd 8                                                                                                     10/12/2010 11:15:08
Dépannage (Pour toute information, consulter le site www.powerquality.eaton.com ou notre Service Après-Vente)
            Symptôme                                  Diagnostic                               Remède
   1

                                                                                                                                           FRANÇAIS
            l Les prises secourues 9 ne sont          l   Le bouton 12 n’est pas allumé.       l Appuyer sur le bouton 12 et
            pas alimentées.                                                                    vérifier qu’il s'est allumé en vert.
   2        l Les appareils raccordés ne sont         l Les appareils ne sont pas              l Raccorder ces appareils sur les
            plus alimentés lors d'une coupure         raccordés sur les prises secourues       prises secourues 9 .
            du réseau électrique.                      9.
   3        l Le réseau électrique est présent        l Le disjoncteur 13 , placé sous l'ASI   l Débrancher l’appareil en cause en
            mais l'ASI fonctionne sur sa              s’est ouvert pour cause de surcharge     sortie et réarmer le disjoncteur 13
            batterie.                                 excessive en sortie de l'ASI.            en appuyant sur son bouton.
   4        l Lesprises filtrées 8 ne sont pas        l La prise murale n'est pas              l Rétablir l'alimentation de la prise
            alimentées.                               alimentée.                               murale.
                                                      l Le disjoncteur 13 , placé sous l'ASI   l Débrancher l’appareil en cause en
                                                      s’est ouvert pour cause de surcharge     sortie et réarmer le disjoncteur 13
                                                      excessive en sortie de l'ASI.            en appuyant sur son bouton.
   5        l Le bouton vert 12 clignote              l L'ASI fonctionne fréquemment sur       l Faire vérifier l’installation

            fréquemment et l’alarme sonore            batterie car le courant fourni par la    électrique par un professionnel ou
            fonctionne.                               prise murale est de mauvaise qualité.    changer de prise.
   6        l Le bouton vert 12 clignote              l L'ASI subit une surcharge sur les      l Débrancher l’appareil en cause

            fréquement et l'alarme sonore             prises secourues 9 .                     des prises secourues 9 .
            émet un signal continu.
   7        l Le voyant rouge 11 est allumé           l L'ASI a subit un défaut. Les           l   Faire appel au service après vente.
            et l’alarme sonore émet un signal         prises secourues 9 ne sont plus
            toutes les 30 secondes.                   alimentées.
   8    Le voyant vert 10 est éteint et les l La protection contre les
            l                                                                      l Faire appel au service après vente.

      prises 8 sont alimentées.             surtensions n'est plus assurée.
   9 l La ligne téléphonique est            l La protection contre les             l Débrancher la ligne téléphonique
      perturbée ou l'accès du modem est surtensions de la ligne téléphonique de la prise murale.
      impossible.                           n'est plus assurée.                    l Faire appel au service après vente.

   10 l Le voyant rouge 11 clignote.        l La batterie a atteint sa fin de vie. l Faire remplacer la batterie.

   11       l Les prises ECoControl restent        l La fonction EcoControl n'est pas          l Activer ou paramétrer
            alimentées alors que l'application     activée ou est mal paramétrée.              correctement la fonction EcoControl
            principale (prise Master) est arrêtée.                                             en utilisant le logiciel fourni avec le
                                                                                               produit.

  Personnalisation avancée de votre ASI
    Sensibilité aux variations du réseau électrique d’entrée             Alarme sonore

    l A utiliser uniquement en cas de fréquents passages                 l Possibilité de désactiver l’alarme sonore lorsque
    sur batterie de l’ASI du fait de variations importantes              l’ASI fonctionne sur batterie.
    de la tension du réseau électrique d’entrée.
    l Accès au mode de programmation : appareil à l’arrêt,               l Accès au mode de programmation : appareil à l’arrêt,
    maintenir le bouton 12 appuyé pendant 6 s et le                      maintenir le bouton 12 appuyé pendant 11 s et le
    relâcher après l’allumage des voyants 11 12 .                        relâcher au fonctionnement de l’alarme sonore.
    l Affichage des 3 plages possibles de tension suivant                l Obtention des 2 modes possibles de l’alarme
    l’état des voyants 11 et 12 :                                        sonore :
    Mode normal             Mode étendu           Mode étendu            Mode normal                      Mode silence :
    (configuration          bas :                 bas et haut :          (configuration usine) :          l’ASI émet un seul bip au
    usine) :                réseau d’entrée       réseau d’entrée        l’ASI émet un bip                passage sur batterie puis
    réseau d’entrée         compris entre         compris entre          toutes les 10 s en               reste silencieuse.
    compris entre           161 V et 264 V        161 V et 284 V         fonctionnement sur
    184 V et 264 V                                                       batterie.
       11           12     11       12           11           12                                             Mode silence activé :
                                                                             Mode normal activé :
                                                                                                             programmation par
                                                                             programmation par
                                                                                                             un bip toutes les
                                                                             un bip continu.
                                                                                                             secondes.
            11 10 12            11 10 12          11 10 12

       Changement de mode par appuis successifs                              Changement de mode par appuis successifs
       sur le bouton 12 .                                                    sur le bouton 12 .
    l Mémorisation du mode après 10 s sans appui.                        l Mémorisation du mode après 5 s sans appui.