TEKAPO SPIGOT PS1 - Boundaryline

Page created by Dan Cortez
 
CONTINUE READING
TEKAPO SPIGOT PS1 - Boundaryline
TITAN PS1

PRODUCER STATEMENT - PS1

                                                                    Issue Date: 22 Jun 2020
                                                                           Revision No. 1.01

                                        TEKAPO
                                        SPIGOT
                                                       PS1

STRUCTURAL DESIGN REPORT, JOB J001856

Boundaryline - Very high wind zone, various location

                                                             0800 003 006 / boundaryline.co.nz   1
TEKAPO SPIGOT PS1 - Boundaryline
GD C                Consultants Ltd

                                   Chartered Professional Engineers & Mediators

                                         Structural Design Report
This report has been prepared for Boundaryline by GDC Consultants Ltd (GDC). No
liability is accepted by this company or any employee or sub-consultant of this
company with respect to its use by any other parties.

This disclaimer shall apply notwithstanding that the report may be made available to
other persons for an application for permission or approval to fulfil a legal requirement

                           Cantilever glass balustrade and pool fence
                 Structural Design, very high wind zone, various location
                      Status                               For consent
                     Revision                                   0

                                      Quality Assurance Statement
                Task                           Res onsibilit                      Si nature & Date
                                                Alin Poanta
          Prepared by:                      MEngNZ No. 1027581

          Reviewed by                          Mike Osborne
                                            CMEng NZ No.212452

     Peer - Reviewed by                        Matt Bishop
                                             CPEng No. 243276

                                              Clement Fernando
  Approved for Issue by:
                                              CPEng. No. 202146

Job No: J001856
Date: June 2020
HBI House, 6C Taradale Road, Napier, 41101
Offices in: Hamilton! Thames! Whitiangal Rotorual Auckland! Napier! Asia
Website: www.gdcgroup.co.nz
Specialising in Civil, Structural, Environmental & Training

Structural Design Report, Job J001856
 Boundaryline - very high wind zone, various location
June 2020
TEKAPO SPIGOT PS1 - Boundaryline
Section 1 – PS1

Structural Design Report, Job J001856
Boundaryline – very high wind zone, various location
June 2020
TEKAPO SPIGOT PS1 - Boundaryline
B1 , F2
                                                                                                     Building Code Clause(s)………………………..

                           PRODUCER STATEMENT – PS2 – DESIGN REVIEW
                               (Guidance on use of Producer Statements (formerly page 2) is available at www.engineeringnz.org)

ISSUED BY: ……..………………………………………………………………………………………………………………….……
           BVT Consulting Ltd
                                                                       (Design Review Firm)
    Boundaryline
TO:………………………………………………………..…………………………………………………………………………..……
                                                                        (Owner/Developer)

TO BE SUPPLIED TO:…………………………………………………………………………………………………….……….……
                  Various Councils
                                                                 (Building Consent Authority)
              Design Review of Cantilever Glass Balustrade - Spigot 5 as per GDC Consultants Engineers PS1 J001856
IN RESPECT OF:…………………………………………………………………………………………….……………………….….
                                                                (Description of Building Work)

AT:………………………………………………………………………………………………………………………….………….…..
   Various Locations
                                                                            (Address)

Town/City:……………..………………………...…..… LOT…………….....…………… DP………………… SO…………………
                                    (Address)
   BVT Consulting Ltd                               Boundaryline
We …………..………..…………………………..…..… have been engaged by …………..………….……………….......……….
                        (Design Review Firm)
                                                                                             B1, F2
to review the design documents for this project in respect of the requirements of Clause(s) ……………………….………….
of the Building Code.
The Review is for        All                                                 GDC Consultants Ltd
                               or ■ Part only of the design work prepared by …………………………………………………….…
                                                                                                                        (Design Firm)

                                 Cantilever Glass Balustrade & Pool Fence - Spigot 5
as described in drawings titled ..…………………..…………………………………………………………………………………

and numbered …………………………………………….……………….
                J001856-03                                            together with the specification, and other documents set
out in the schedule attached to this statement according to which the building is proposed to be constructed.

                            spigot and anchor design
The Review is in respect of ………………………….………………………………………………..… or per attached schedule.
                                                                        (aspects of design)

The Review confirms that these aspects of the design are in accordance with:
                                                                                  B1/VM1
■ Compliance Documents issued by the Ministry of Business, Innovation & Employment………………..……………...….or
                                                                                                             (verification method/acceptable solution)

   Alternative solution as per the attached schedule…………………….……………………………………………………..……

On behalf of the firm undertaking this review, on the basis of the review undertaken, and subject to:

(i) Site verification of the following design assumptions …………See attached report……………………..……………..…
(ii) All proprietary products meeting their performance specification requirements;
I believe on reasonable grounds that a) the building, if constructed in accordance with the drawings, specifications, and other
documents provided or listed in the attached schedule, will comply with the relevant provisions of the Building Code and that b),
the persons who have undertaken the review have the necessary competency to do so.
   Matt Bishop
I, …………..………..………………………………….....…..……….             243276
                                        am: ■ CPEng ……….….. #                                                           Reg Arch …….…….. #
                        (Name of Design Review Professional)

I am a member of: ■ Engineering New Zealand                                                     BE(Hons)
                                                   NZIA and hold the following qualifications:…………………………….
The Design Review Firm issuing this statement holds a current policy of Professional Indemnity Insurance no less than
$200,000*.
The Design Review Firm is a member of ACENZ: ■
         Matt Bishop
SIGNED BY……………………….…………………………………………………..(Signature)……….…………..……………...…
                                          (Name of Design Review Professional)

ON BEHALF OF BVT                                          22 June 2020
             ……..……………………………………………………………………………………………..Date……..…….…
                 Consulting Ltd
                                                (Design Review Firm)

Note: This statement shall only be relied upon by the Building Consent Authority named above. Liability under this statement accrues to the
Design Review Firm only. The total maximum amount of damages payable arising from this statement and all other statements provided to the
Building Consent Authority in relation to this building work, whether in contract, tort or otherwise (including negligence), is limited to the sum of
$200,000*.
This form is to accompany Form 2 of the Building (Forms) Regulations 2004 for the application of a Building Consent.
                       THIS FORM AND ITS CONDITIONS ARE COPYRIGHT TO ACENZ, ENGINEERING NEW ZEALAND AND NZIA

PRODUCER STATEMENT PS2                                                                                                                    October 2013 (PDF)
TEKAPO SPIGOT PS1 - Boundaryline
Peer Review Summary

        Overview

        BVT has conducted a peer review of GDC Consultants PS1 on glass balustrade spigots and
        anchors to be installed at various locations in New Zealand. BVT has reviewed the component of
        the PS1 covering Clause B1 (Structure) of the NZ Building Code.

        Items raised by BVT and the responses from GDC Consulants are outlined in the RFI summary
        sheet in Appendix B.

        Key Outcomes

        The spigots and anchors specified in the PS1 design are reasonable for use with 1.2x1.4 m
        toughened glass panels. Calculations verify that the spigots are suitable for fastening 12 mm
        toughened glass panels at wind speeds up to 50 m/s, classified as Very High Wind Zones in NZS
        3604-2011. ​We believe that the designs of the spigots are in compliance with AS/NZS 1170.2
        and the Department of Building and Housing’s Guidance on Barrier Design. A PS2 can therefore
        be issued based on this review.

Project Contacts
Review Engineer:            Daniel Bulbring

Chartered Engineer:         Matt Bishop                 CPEng CMEngNZ

All information, details or designs portrayed in this document remain the copyright of BVT Consulting
Limited (unless BVT has expressly agreed otherwise with the Client). Any reproduction without the
express permission of BVT Consulting Ltd is prohibited.

This report has been prepared by BVT on the specific instructions of our Client. It is solely for our Client’s
use for the purpose for which it is intended in accordance with the agreed scope of work. Any use or
reliance by any person contrary to the above, to which BVT has not given its prior written consent, is at
that person’s risk.

BVT                                                                                                  Revision A
                                                                                                     19061267
TEKAPO SPIGOT PS1 - Boundaryline
Section 2 – B2 Compliance

Structural Design Report, Job J001856
Boundaryline – very high wind zone, various location
June 2020
TEKAPO SPIGOT PS1 - Boundaryline
H B I House, 6C Taradale Road
                                                                                        PO Box 44, Napier
                                                                                            +64 6 281 2270
                                                                                    napier@gdcgroup.co.nz
                                                                                    W: www.gdcgroup.co.nz

June 2020                                                                          Ref.: Job J001856

To Various Councils
Attention: Building officer

Dear Building consent officer,

Re: B2 Compliance
Cantilever Glass Balustrade – Spigot design as per GDC Consultants J001856

You have requested a Producer Statement for Design – PS1 for clause B2 of the Building Code – Structural
Durability.

We are not able to provide this because there is no effective verification method for B2 contained within
the Building Code.

However we can confirm that for the structural element shown in our documentation:

       Steel

       Steel protection has been specified in accordance with AS/NZS 2312.1:2014 “Guide to the protection
       of structural steel against atmospheric corrosion by the use of protective coatings Part1: Paint
       coatings”. We note that this is on a time first maintenance basis
       The spigots are made of Duplex 2205 Stainless Steel. Mechanical properties of 2205 grade stainless
       steels are in accordance with ASTM A276 / A276M - 17 Standard Specification for Stainless Steel Bars
       and Shapes.
       The spigots are manufactured according to ISO 16468:2015 which specifies technical requirements
       for castings produced by the investment-casting process. The International Standards specifying
       metallurgical material requirements for grade 2205 steel.

We trust that this provides the information that you are seeking.

Should you have further queries, please contact the undersigned.

Yours faithfully

Alin Poanta
Structural Engineer
For GDC Consultants Ltd

          OFFICES : HAMILTON – THAMES – ROTORUA - WHITIANGA – NAPIER – AUCKLAND - WELLINGTON - ASIA
TEKAPO SPIGOT PS1 - Boundaryline
Section 3 – F2 Compliance

Structural Design Report, Job J001856
Boundaryline – very high wind zone, various location
June 2020
TEKAPO SPIGOT PS1 - Boundaryline
SAFETY GLASS CERTIFICATION

SAFETY GLASS CERTIFICATION
F2: COMPLIANCE
 STATEMENT OF COMPLIANCE

To satisfy the New Zealand Building Code Acceptable Solution F2/AS1, glass likely to come into contact with people
must comply with NZS 4223: Part 3:2016 Code of practice for glazing in buildings – Human impact safety
requirements.

NZS 4223: Part 3:2016 requires Grade A safety glass to be used in shower doors, shower screens and bath enclosures
and Glass Pool Fencing.

Boundaryline confirms glass used in our Glass Pool Fencing and Balustrade has been produced to one or more of
the following standards as outlined in Appendix 3.B of NZS 4223:Part 3:2016:

AS/NZS 2208 Grade A
BS 6206 Grade A

ANSI Z97.1

Peter Carney GENERAL MANAGER
M: 0800 235 2473 I sales@belairefencing.co.nz

2 Waitane Place | Onekawa, Napier | New Zealand 3116

Tel: +64 6 8785 752 | Mob: +64 21 220 1403 | Fax: +64 6 8785 758

                                                                                                     June 2020
TEKAPO SPIGOT PS1 - Boundaryline
MATERIALS & TESTING
                                 LABORATORIES                 LIMITED
                                  Destructive & Non-destructive Test House

                                            CERTIFICATE OF TEST
                                                                                                                    Report No. 42653/2
                                                                                                                      Page 1 of 3 pages

      Reference:                   BELAIRE DESIGNER FENCING
                                   Order No.: PETER
                                   Attention: Mr Peter Carney

                                   Load Testing on 1400mm Long x 1200mm High Uniglass Infill Panel

      Test Standard/ Method: Method as discussed with client

      Test Equipment:              Riken P-4 Pump, Serial No. 22968 with AEP Digital Force Gauge, Serial No. 109626
                                   SPX 5 Ton, Model B No. C55C Single Ram
                                   (all verified against Shimadzu Universal Grade 1 Testing Machine, Model No. REH 50, Serial No. 72666.
                                   Calibration due June 2016).
                                   Kristeel LAD 1 0-600mm

      RESULTS:

      1 x Uniglass infill panel 1400mm long x 1200mm high, mounted to 2 x stainless steel spigots. 3 x Separate load tests performed:
      Maximumlload vs Deflection at maximum load and Permanent Set recorded.

      Test 1:    240kg Distributed Through a 960 x 960mm Timber Load Board

                       Applied Force            Deflection at Maximum Load
                            (kg)                            (mm)
                             0                                0
                             30                               8
                             60                              23
                             90                              44
                            120                              57
                            150                              71
                             180                             82
                            210                              93
                            240                              105

                   Permanent Set= 12mm - No failure observed.

       Certificate of Test 20 15 dotx                                                        . Document Date 1 I /02/15 Rev 0
P.O. BOX 14-042, PANMURE 1741, 172g MARUA RD, MT WELLINGTON, AUCKLAND, N.Z. TEL: 579 0262 FAX: 579 0260 Email: admin@mtlabs.co.nz
Section 4 – Drawings

Structural Design Report, Job J001856
Boundaryline – very high wind zone, various location
June 2020
BOUNDARYLINE

                                                   CANTILEVER GLASS BALUSTRADE
                                                  & POOL FENCE SPIGOTS (SPIGOT 5)

                                                              NEW ZEALAND

                                                              DRAWING REGISTER

                    1.                     GENERAL NOTES              J001856 - 01   REVISION 0
                    2.                     NOTES & PS4                J001856 - 02   REVISION 0
                    3.                     LAYOUT & DETAILS           J001856 - 03   REVISION 0

GDC
Consultants Ltd
CharteredProfessionalEngineers&Mediators
                                                                                                      FOR CONSENT

                                                                                                  JOB NO: J001856
NOTES

GENERAL
G1   STRUCTURAL DRAWINGS SHALL BE READ IN CONJUNCTION                 INSPECTIONS
     WITH THE SPECIFICATION, ARCHITECTURAL, CIVIL AND
     ENGINEERING SERVICES DOCUMENTS.
G2   NO DIMENSIONS ARE TO BE OBTAINED FROM
     SCALING DRAWINGS U.N.O.
                                                                      I1. CHECK THE BUILDING CONSENT CONDITIONS FOR ANY INSPECTIONS
                                                                          THAT ARE REQUIRED BY THE BUILDING CONSENT AUTHORITY (BCA).
G3   UNLESS OTHERWISE NOTED ALL LEVELS ARE IN METRES
     AND ALL DIMENSIONS ARE IN MILLIMETRES.
G4   THE BUILDER SHALL BE RESPONSIBLE FOR MAINTAINING
     THE STABILITY OF THE STRUCTURE UNTIL ITS COMPLETION
                                                                      I2. IT IS INCREASINGLY COMMON FOR BUILDING CONSENT AUTHORITIES
     AND SHALL ENSURE THAT NO PART OF THE STRUCTURE IS                    TO REQUIRE A "PS4" FOR SPECIFICALLY DESIGNED STRUCTURES.
     OVERSTRESSED BY EXCESSIVE LOADING.

G5   ALL MATERIALS AND WORKMANSHIP SHALL BE IN ACCORDANCE
                                                                          CONFIRM WITH BCA AND GDC CONSULTANTS THE SCOPE AND TYPE
     WITH THE CURRENT CODES OF PRACTICE EXCEPT WHERE VARIED
     BY THE SPECIFICATION AND/OR DRAWINGS.
                                                                          OR REQUIRED INSPECTIONS FOR GDC CONSULTANTS LTD. TO ISSUE
     ISO 16468 - INVESTMENT CASTINGS                                      THIS AS WE NEED TO CARRY OUT INSPECTIONS AS PER THE BUILDING
G6   LEGEND USED FOR GENERAL ABBREVIATIONS                                CONSENT REQUIREMENTS. RING GDC CONSULTANTS LTD. LOCAL
     TYP   TYPICAL
     NTS   NOT TO SCALE                                                   OFFICE TO ARRANGE BOOKING.
     SFL
     FFL
           STRUCTURAL FLOOR LEVEL.
           FINISHED FLOOR LEVEL
                                                                          (NO INSPECTION EQUALS NO PS4 ISSUED)
     SOP   SET OUT POINT
     UNO   UNLESS NOTED OTHERWISE
     FL    FOUNDING LEVEL (IE UNDERSIDE OF FOOTING)                   I3. GDC MUST SEE STAMPED BUILDING CONSENT DRAWINGS BEFORE AN
G7   WHERE PROPRIETARY PRODUCTS ARE SPECIFIED IN THE DOCUMENTS THE        INSPECTION CAN BE CARRIED OUT.
     CONTRACTOR MAY NOT SUBMIT AN ALTERNATIVE PRODUCT FOR APPROVAL.

                                                                      I4. CONTRACTOR TO SUPPLY PS3 OR LICENCED BUILDING PRACTITIONER
                                                                          (LBP) WITH SIGNED GDC DRAWINGS AFTER CONSTRUCTION.

                                                                      I5. REQUIRED INSPECTIONS SCHEDULE MUST BE UNDERTAKEN BY THE ENGINEER
                                                                      - BALLUSTRADE SPIGOT MANUFACTURE

                                                                      I6. IT IS THE BUILDING CONSENT APPLICANT'S( OR AUTHORIZED AGENT)               REV               REVISION DETAILS                       APPD DATE
                                                                          RESPONSIBILITY TO ENSURE THAT GDC CONSULTANTS LTD. IS NOTIFIED IN           A person using GDC drawings and other data accepts the risk of:

                                                                          ADVANCE OF THE REQUIRED INSPECTION. WE CANNOT ISSUE PS4 FOR ITEMS WE     1. Using the drawings and other data in electronic form without requesting
                                                                                                                                                      and checking them for accuracy against the original hard copy versions;
                                                                                                                                                   2. Using the drawings or other data for any purpose not agreed to in writing by GDC
                                                                          DID NOT INSPECT. BOOKING SHOULD BE MADE 48 HOURS PRIOR TO DESIRED TIME
                                                                          OF INSPECTION.
                                                                                                                                                                                               489 Anglesea Street
                                                                                                                                                                                               PO Box 9403
                                                                      I7. DURABILITY. IF COUNCIL REQUIRES B2-DURABILITY SIGN OFF ON THE PS4, THE                                               Hamilton 3204
                                                                          CONTRACTOR NEEDS TO PROVIDE QUALITY CERTIFICATES SUCH AS TIMBER
                                                                                                                                                         Consultants Ltd                      Ph. (07) 838 0090
                                                                          GRADE, STEEL GRADE, CONCRETE STRENGTH, PILE DRIVING RESULTS AND ANY            Chartered Professional
                                                                                                                                                         Engineers & mediators
                                                                          OTHER RECORDS TO DEMONSTRATE THAT THE BUILDING WAS CONSTRUCTED IN
                                                                                                                                                    Also at : Thames Whitianga Rotorua Napier Wellington Auckland
                                                                          ACCORDANCE WITH THE SPECIFIED DESIGN REQUIREMENTS AND SPECIFICATION.      Web: www.gdcgroup.co.nz Email: hamilton@gdcgroup.co.nz
                                                                          THIS INFORMATION TO BE PROVIDED TOGETHER WITH THE PS3 CERTIFICATE TO
                                                                          THE ENGINEER SO THAT HE/SHE IS ABLE TO ISSUE A PS4 CERTIFICATE FOR THE     Client:
                                                                          PROJECT.                                                                   BOUNDARYLINE

                                                                      I8. IF EQUIVALENT PRODUCTS ARE TO BE USED IN PLACE OF THE SPECIFIED            NEW ZEALAND WIDE
                                                                          PRODUCT ON DRAWINGS, THE ENGINEER MUST BE INFORMED AND AGREE TO
                                                                          THE SUBSTITUTION IN WRITING.

                                                                                                                                                     Project:

                                                                                                                                                     CANTILEVER GLASS
                                                                                                                                                     BALUSTRADE & POOL FENCE
                                                                                                                                                     SPIGOT 5

                                                                                                                                                     Drawing Title:

                                                                                                                                                     GENERAL NOTES

                                                                                                                                                     JOB No. J001856                     DESIGNED A.P
                                                                                                                                                     CAD No. J001856                     DRAWN             J.F
                                                                                                                                                     DATE          FEB 2020              CHECKED A.P
                                                                                                                                                     DATE          FEB 2020              APPROVED C.F

                                                                                                                                                     ORIGINAL SCALES
                                                                                                                                                     AS SHOWN @ A3

                                                                                                                                                     DRAWING No.                                       SHEET            REV.
                                                                                                                                                                                                       1                0
                                                                                                                                                    J001856-01                                         OF 2
NOTES

                                             1400
                                                                                                                                                                                                                           -   SPIGOTS TO BE MANUFACTURE
                                                                                                                                                                                                                               ACCORDING TO ISO 16468 : 2015

                                                                                                                                                                                                                       -       FOR TIMBER MEMBERS BEING LESS
                                                                                                                                                                                                                               THAN 90mm WIDE USE A DIFFERENT
                                                                                                                                                                                                                               TYPE OF SPIGOT

                                                                                                                                                                                                                       -       MINIMUM TIMBER MEMBER DEPTH
                                                                                                                                                                                                                               FOR FIXING THE SCREWS INTO IS
                                                                                                                                                                                                                               150mm
                                  12mm TOUGHENED SAFETY GLASS
                                                                                                                                                                                                                       -       COACH SCREW PENETRATION TO
                                                                                                                                                                                                                               BE MINIMUM 140mm
1200

                                                                                                                                                                                                                                         FOR CONSENT

                           1                                                    1                                                                  SPIGOT TYPE 5                                                    REV               REVISION DETAILS                       APPD DATE
                           -                                                    -                                                                                                                                    A person using GDC drawings and other data accepts the risk of:
                                                                                                                                                   SCALE 1:5                                                      1. Using the drawings and other data in electronic form without requesting
                                                                                                                                                                                                                     and checking them for accuracy against the original hard copy versions;
                                                                                                                                                                                                                  2. Using the drawings or other data for any purpose not agreed to in writing by GDC

                                                                                                                                                            45             45
                                                                                                                                                                                                                                                              489 Anglesea Street
                                                                                                                                                                                                                                                              PO Box 9403
                          SPIGOT                            SPIGOT                                                                                   45              45                                                                                       Hamilton 3204
                                                                                                                                                                                                                        Consultants Ltd                      Ph. (07) 838 0090
                                                                                                                                                                                                                        Chartered Professional
                                                                                                                                                                                                                        Engineers & mediators
                                                                                                                                                                                EDGE OF TIMBER
                                                                                                                                                                                                                   Also at : Thames Whitianga Rotorua Napier Wellington Auckland
                                                                                                                                                                                                                   Web: www.gdcgroup.co.nz Email: hamilton@gdcgroup.co.nz
          300                                 800                               300                                                TIMBER BLOCKING
                                                                                                                                                                                                                    Client:

                                                                                                                                                                                                                    BOUNDARYLINE
                                                                                                                                                                                                                    NEW ZEALAND WIDE
                                                                                                                     TIMBER MEMBERS BY OTHERS
       GLASS FENCE SUPPORTED BY STAINLESS STEEL SPIGOTS                                                                                                   MINIMUM 90mm WIDE
       SCALE 1:10

                                                                                                                                                                                                                    Project:

                                                                                                                                      PLAN VIEW ON TIMBER CONNECTION                                                CANTILEVER GLASS
                                                                                                                                      SCALE 1:10
                                                                                                                                                                                                                    BALUSTRADE & POOL FENCE
                                                SS SPIGOT                                                    SS SPIGOT                                                                                              SPIGOT 5
                    12mm TOUGHENED                                          12mm TOUGHENED                                                                                SS SPIGOT
                                                                                                               25 MINIMUM
                       SAFTEY GLASS                 4/M10 STAINLESS STEEL      SAFTEY GLASS                                           12mm TOUGHENED
                                                                                                                  EDGE DISTANCE                                                                                     Drawing Title:
                                                    CHEMSET BOLTS                                                                        SAFTEY GLASS                       4/M10 BOLTS OR 4/M10 COACHSCREWS
                                                                                                               4/M10 S/S BOLTS                                              CENTRALLY PLACED TO TIMBER MEMBERS.     SPIGOT FIXING
                 CONCRETE SLAB                      EPCON C6 EPOXY
                                                    100mm EMBEDMENT                                            SPIGOT BASE PLATE                                            NO FIXINGS TO THE
                25MPa STRENGTH
                                                                                                                                                                            TIMBER ENDS

                                                                                                   115         8mm STEEL PLATE
                                                                                                               6mm FWAR TO                                                                                          JOB No. J001856                     DESIGNED A.P
                                              100    MINIMUM CONCRETE                                          STEEL                                                                                                CAD No. J001856                     DRAWN             J.F
                                                     EDGE DISTANCE                                                                                                                                                  DATE          FEB 2020              CHECKED A.P
                                                                                                                                                                                                                    DATE          FEB 2020              APPROVED K.W
                                       1
                     SECTION               TO CONCRETE                                SECTION            1
                                                                                                              TO STEEL                     SECTION               1
                                                                                                                                                                          TO TIMBER
                     SCALE 1:10        -                                              SCALE 1:10         -                                 SCALE 1:10            -                                                  ORIGINAL SCALES
                                                                                                                                                                                                                    AS SHOWN @ A3

                                                                                                                                                                                                                    DRAWING No.                                       SHEET            REV.
                                                                                                                                                                                                                                                                      2                0
                                                                                                                                                                                                                   J001856-02                                         OF 2
Section 5 – Self Closing Gates
                                                       Compliant With F9

Structural Design Report, Job J001856
Boundaryline – very high wind zone, various location
June 2020
Frameless Glass Pool Fencing Glass Gate Hardware Compliance
                            Glass Gate Self Closing Hinges

                                                      All Glass And Hardware Has Been tested to AS1926.1 -
                                                            2012, A full report is available on Request.

                                                      - Gate Material: 10mm Toughened Glass
                                                      - Gate Size:        1200mm high x 900mm wide
                                                      - Lock Description:Magnalatch
                                                      - Hinge Descption: Self Closing Spring hinge gate
                                                      - Lock On Inside of Barrier:           Yes
                                                      - Self Closing from all angles:        Yes
                                                      - Self Closing from 150mm of open: Yes
                                                      - Overall Gate Height:                 1250mm

                              20

                                                                                                          18
102.2

                                                6.3
                             48
                       80

                                                                            10
                                                                       21

                                                                                                          4
                                                                                 20                  20
        4

                                                                                      50        50

                                        106.3
Frameless Glass Pool Fencing Glass Gate Hardware Compliance

                                                                         Glass Gate Self Locking Gate Latch
self closing hinge

                                                                    Self Locking Latch

self closing hinge

                                   self closing spring hinge
                                                                                         Below Is a photo of the Testing Setup to comply with AS1926.1 - 2012

                                                                                  18
           10
      21

                                                                                  4

                             20                                     20

                                    50                         50

                                  self closing gate latch

                                                   10mm gate
                12mm panel

                                         15mm