SERVICE MANUAL QBD HYDROCARBON COOLERS

Page created by Kathryn Chapman
 
CONTINUE READING
SERVICE MANUAL QBD HYDROCARBON COOLERS
QBD HYDROCARBON COOLERS
      SERVICE MANUAL

       Logo should read as Natural Refrigerant
SERVICE MANUAL QBD HYDROCARBON COOLERS
Content
Description                                Page
• Why R-290                                  3
• Overview of R-290                          4
• Introducing Cooling Deck 3.0               5
• Labeling for R-290                         6
• HC Coolers- Electrical Parts               7
• Recommended Tools                          10
• Replace vs Repair                          12
• Recommended Service Procedures             14
• Do’s and Don’ts                            18
• FAQs                                       19

                QBD Cooling Systems Inc.          2
SERVICE MANUAL QBD HYDROCARBON COOLERS
Why R-290
Hydrocarbon (HC) refrigerants are non-synthetic substances, have
ZERO Ozone Depletion Potential and are environmental friendly
substances.
                                             #1: Regulatory Forces
                                             In line with the Montreal Protocol’s calls for
                                             reduction/elimination of CFC & HCFC production, the
                                             EPA has mandated a ban on HFC Refrigerants R-
                                             134a and R-404A by 2020.
                                             In North America, the Significant New Alternatives
                                             Program (SNAP), accepted hydrocarbon R-290 as an
                                             alternative for small charge refrigeration applications.
                                             Department of Energy (DOE) has mandated approx.
                                             40-70% reduction in energy consumption by 2017

                                             #2: Improved Efficiency
                                             R-290’s specific cooling capacity is approximately 90%
                                             greater than that of R134a resulting into lesser amount
                                             (45-60% reduction) of refrigerant charge while
                                             maintaining the same cooling performance. This means
                                             approximate 30% reduction in size of the compressor,
                                             resulting into better energy efficiency of the system.
                                             Hydrocarbon Coolers are approximately 30% more
                                             energy efficient compared to previous generation HFC
                                             coolers.

                                             #3: Sustainability
                                             R-290 is a natural, non-toxic refrigerant with zero ozone
                                             depletion potential and very low global warming
                                             potential (GWP). Compared to R134a, which has GWP
                                             of 1430, R-290’s GWP index is just 3. It is one of the
                                             most climate-friendly and energy efficient refrigerants
                                             available.

 (https://www.epa.gov/snap/unacceptable-substitute-refrigerants)
 (https://www.epa.gov/snap)
 (https://www.epa.gov/ozone-layer-protection/recent-international-developments-under-montreal-protocol)   3
 (https://www.epa.gov/snap/acceptable-substitutes-industrial-process-refrigeration ).
SERVICE MANUAL QBD HYDROCARBON COOLERS
Overview of R-290
•    R-290 is Propane with 99.5% purity with minimum levels of
     critical impurities.

•    R-290 is Odorless / Inflammable / Non-Toxic

•    The use of R-290 has been increased due to its low
     environmental impacts and greater economic gains

•    Has excellent thermodynamic performance, leading to higher
     energy efficiency and operating cost reduction

•    R-290 is classified as extremely inflammable. Therefore the
     handling and use of R-290 requires adequate safety
     measures.

•    Only a maximum 150 grams (5.3 oz.) of R-290 charge is
     required in each refrigeration system. (Ref: UL#471).

•    EPA has approved the venting of Hydrocarbon refrigerant into
     the atmosphere

It is recommended to ensure all employees have access to MSDS
of R-290 to fully understand the hazard and pre-cautions

Use of NON OEM parts is strictly prohibited. Use of non OEM parts will not only void the warranty, but may
also lead to a major fire or explosion causing property damage, severe personal injury or even death.

                                  QBD Cooling Systems Inc.                                           4
SERVICE MANUAL QBD HYDROCARBON COOLERS
Introducing Cooling Deck 3.0
                                              UL Required Labeling &
Gasket is UL V0                              RED identification sleeves
    Rated                                       on Service Lines*

 Green Base                                          R290 specific
                                                        labels

                         Green Lift Rods
* Technicians are responsible to ensure these RED SLEEVES are
always present on access points as per UL#471 requirements.

                       QBD Cooling Systems Inc.                     5
SERVICE MANUAL QBD HYDROCARBON COOLERS
Labeling for R-290

                     6
SERVICE MANUAL QBD HYDROCARBON COOLERS
HC Cooler- Electrical Parts

                         CONTROLLER
                         Approved for Hydrocarbon
                         applications / Electronic /
                         Built in Defrost Timer

                         ECM MOTORS
                         UL Approved / Very High
                         Efficiency / Brushless /
                         Wider operating range

                         ELECTRICAL
                         CONNECTORS
                         Approved for Hydrocarbon
                         applications

          QBD Cooling Systems Inc.                  7
SERVICE MANUAL QBD HYDROCARBON COOLERS
HC Cooler- Electrical Parts
NEVER use a 3in1 Starting Kit on R-290 Refrigeration System

                                      COMPRESSOR
                                      RELAY
                                      Approved for
                                      Hydrocarbon
                                      applications

                                      COMPRESSOR
                                      CAPACITOR
                                      Approved for
                                      Hydrocarbon
                                      applications

                                      COMPRESSOR
                                      OVERLOAD
                                      Approved for
                                      Hydrocarbon
                                      applications

                    QBD Cooling Systems Inc.          8
SERVICE MANUAL QBD HYDROCARBON COOLERS
HC Cooler- Electrical Parts

                           LED POWER
                           SUPPLY
                           Approved for
                           Hydrocarbon / Class 2
                           Type Power supply: 12V
                           DC / High Energy
                           Efficiency

                           LED+ Lighting
                           Approved for
                           Hydrocarbon cooler
                           application/
                            up-to 50% more product
                           illumination & efficiency

         QBD Cooling Systems Inc.                  9
SERVICE MANUAL QBD HYDROCARBON COOLERS
Recommended Tools

Tube Cutter       R-290 Gas Detector      Vacuum Pump

  Scale              Crimping Tool        Manifold Gauge

                                     Optional

Piercing Valves           Torch           Recovery Tank

                       Safety Mandated
                                                      10
Ignition Sources
R290 is highly inflammable. Please be aware of all ignition sources before
servicing any HC cooler. Below is a list of some common ignition sources to
watch out for:

•   Temperature greater than 460*C (860*F)
•   Flame from a match, pilot, burner etc.
•   Torch including Halide Leak detectors
•   Hot wire refrigerant leak detector
•   Open spark
•   Static electricity
•   Light and socket switches
•   Unsealed relays and overloads
•   On Off switches
•   Contactors
•   Pressure switches
•   Defrost timers
•   Thermostats
•   Vacuum pump switches
•   Electronic leak detectors
•   Open motors
•   Cellular Phones and other electronic devices
Replace vs Repair
•   Replace (swap) the cooling deck under the following circumstances:

     –   Compressor failure
     –   Refrigerant leak
     –   Damaged/broken base (platform)

•   Repair the cooling deck under the following conditions:

     –   Controller failure
     –   Motor (condenser/evaporator) malfunction
     –   Damaged fan blade(s)

    NOTE: Use only OEM parts for replacement.

•   Please contact QBD Technical Assistance at 1-(800) 663-3005 or (905)
    459-0709

                          QBD Cooling Systems Inc.                       12
Replacing the Cooling
            Deck
1                                        2

          Loosen Front Grill Screws                 Remove Locking Screws

3                                        4

                                                    Unplug the Power Cord
           Slide Up Lift Bar Holder

5                                       6

         Rotate Lift Bars Inward to               Slide CD Out By Pulling Lift
       Release CD from Lock Position                   Bars Towards You

    Watch Youtube video of QBD cooling deck replacement
    https://www.youtube.com/watch?v=yLMDcNMOEos

    Check more troubleshooting guidelines at
    http://www.qbd.com/sales_service.php

                             QBD Cooling Systems Inc.                            13
Recommended Service
 Procedures for HC cooler
All inflammable refrigerants when mixed with air form highly inflammable
mixtures. The effects of ignition on this mixture can be severe. It is
extremely important that all appropriate safety requirements are observed at
all times when working with inflammable substances.

HC refrigerant systems must always be serviced and repaired by a qualified
refrigeration technician and must follow the applicable safety precautions.
Before entering any service area, a HC refrigerant monitor or detector must
be switched ‘on’ and it should remain in operation until the service is
completed.

All service procedures for HC coolers must be done in a well ventilated area
and away from any ignition source.

Electrical Safety
•   Check the area using a certified gas detector prior to carrying out
    servicing of a HC cooler.
•   Disconnect power supply to the cooler.
•   Ensure all the electrical components are de-energised
•   Authorised service personnel should use certified spark-proof tools only

If diagnosis indicate failure of any sealed system component (e.g.-
compressor, evaporator or condenser leak, partial blockage, full/partial loss
of refrigerant, etc.), follow recommended repair procedures.

                          QBD Cooling Systems Inc.                        14
Servicing HC Coolers
Venting or Recovery
R-290 refrigerant recovery is not required under SNAP but may still be
called for under other authorities, controls or practices. Always follow local
laws and regulations for recovery or venting of hydrocarbon refrigerant. If
the HC refrigerant is to be vented to the atmosphere, either the unit should
be moved to a well ventilated area before the venting procedure begins or
use hoses long enough to discharge it safely to outside environment.

•   Attach gauges to both the high and low sides of the system using an
    approved method.
•   To avoid accidental release of refrigerant and lubricant, ensure that they
    are recovered/ vented safely from the system before removing the failed
    component of the sealed system.
•   Always recover the refrigerant from both high and low sides of the
    system to assure that no refrigerant is trapped in the system.
•   Purge the system with Oxygen Free Dry Nitrogen (OFDN) several times
    to ensure complete removal of refrigerant from refrigeration system.
•   Achieve a 500 micron vacuum in the refrigeration system using a
    certified vacuum pump before replacing failed sealed system
    component(s).
•   Use a tube cutter rather than a torch to remove the failed component as
    shown below. Using a torch may cause a fire hazard, especially if the
    refrigerant has not been completely discharged/recovered. If you must
    use a torch to remove the failed component of sealed system, do so
    while running dry nitrogen continuously through the system.
•   Always use OEM parts only. Use of non-OEM parts will not only void
    the warranty but may also lead to a major fire or explosion.

                                                                            15
Servicing HC Coolers

Pressure testing and Evacuation
•   Pressurise the serviced refrigeration system with oxygen free dry
    nitrogen (OFDN) up to 150 psig.
•   Hold the pressure and check for possible leak.
•   Purge OFDN before starting the evacuation process.
•   Never use a compressor to evacuate a system. Instead, use a certified
    vacuum pump specifically designed for this purpose.
•   Connect a certified vacuum pump to the repaired system using manifold
    gauges as before starting evacuation.
•   The discharge of the vacuum pump must be vented to an open-air area.
•   Ensure the refrigeration system holds a vacuum pressure of at least
    100 micron before charging.
•   Never attempt to start the compressor while the system is under
    vacuum.
•   Always break a vacuum with refrigerant charge before starting the
    compressor.

Charging refrigerant

•   Do not overcharge a refrigeration system (maximum 150 grams or
    5.3 oz.). Overcharging can result in an explosion.
•   Use only recommended type and amount of refrigerant as indicated on
    the serial label
•   Always use proper charging techniques e.g.- using only certified and
    calibrated weighing scales

                         QBD Cooling Systems Inc.                      16
Servicing HC Coolers
Leak test
Leaks inside or outside of a cooler may result in a inflammable mixture.
Leak detection must be done using electronic or ultrasonic leak detectors
calibrated for hydrocarbon refrigerants.

Sealing the process tubes
Seal the process tube using an approved method or by pinching the tubing
with the recommended equipment and then sealing it with brazing material
or silver solder. Improper sealing of the process tube may lead to leaks or a
sudden release of inflammable refrigerant.

Note: Always use OEM parts. Use of non-OEM
parts will not only void the warranty but may also
lead to a major fire or explosion.

                           QBD Cooling Systems Inc.                         17
Do’s and Don’ts
 Do's
 • Area must be well ventilated & free from any source of
   ignition
 • Use only OEM parts
 • Purge the system with Oxygen Free Dry Nitrogen
   (OFDN) several times
 • R-290 Cooling Decks must be installed in Hydrocarbon
   certified cabinets only
 • Leak Detector – must be designed specifically for HC
   refrigerants. Ensure HC approved leak detector is
   operational at all times.
 • Only “Refrigerant Grade Propane” should be used. Do
   not use any other grade of propane.

 Don'ts

 • Do not use non-OEM parts.
 • Do not use spark producing tools to repair the unit
 • Do not retrofit cooling system
 • Do not reposition electrical components or temperature
   probe
 • Do not use extension cords, power bars and/or wiring
   devise adapters.
 • Do not ‘modify’ the system

        QBD Cooling Systems Inc.                       18
FAQs
How do I know if a cooler is working on R-290?
A number of visual differences have been made in coolers running on R-290.You can
check for R-290 indication on Cooling Deck and the serial plate of the cooler.

Do you need any specialized training to service R-290?
Although it is not mandatory, we recommend you to attend specialised training for this.
You can check more details at Refrigeration Service Engineers Society www.rses.org.

Can I retrofit any cabinet to HC/R-290 refrigerant?
NO, the EPA has ruled that the retrofitting of any existing equipment is prohibited. All
potential spark producing parts in the system, including those in cabinet have to be UL
certified. Any negligence may lead to a major fire or explosion.

Can I use/add light switches in R-290 cabinet?
NO. All electrical fittings must comply with UL # 471 and must be explosion proof. It is
therefore recommended not to add any electrical switch in the cabinet. LEDs provided
with the cooler are compliant to UL#471 and must be replaced with OEM parts only.

 Can the same tools be used to service a hydrocarbon cooler that are used on a R-
134a/R-404A cooler?
Since refrigerant R-290 is highly inflammable, no spark producing tool can be used with
HC cooling system. More details of recommended tools in provided in this manual.
Please check with QBD technical support team if you have any question.

Can the same parts be used in a hydrocarbon cooler that are used on a R-134a/R-
404A cooler?
NO

Is there a maximum charge amount for R-290 refrigeration systems?
YES. You can only have a maximum charge amount of 150 grams (5.3 ounces) in HC
refrigeration system.

Do I need to recover the R-290 refrigerant?
NO, it is not mandatory. Always follow local laws and regulations for recovery or venting
of hydrocarbon refrigerant.

Where can I get R-290 refrigerant?
You can source this refrigerant from an HVAC supply house or a company that sells
gases and welding supplies. Always make sure you are purchasing “refrigerant grade
propane R-290”.
                                                                                           19
MSDS of R290

It is mandatory for users to go through MSDS of R290 and be aware of hazards and precautions.

•    http://www.linde-
     gas.com/en/products_and_supply/refrigerants/natural_refrigerants/r290_propane/index.html

•    http://www.boconline.co.uk/internet.lg.lg.gbr/en/images/care40410_55784.pdf?v=1.0

Service Checklist for HC Coolers
It is recommended to use attached check-sheet before servicing any HC cooler.

                                    QBD Cooling Systems Inc.                                    20
Service Checklist for HC Coolers
S No Points to consider before servicing an HC refrigerant cooler                                     Compliance (Y/N)
     Check for the presence of Refrigerant
     Do not plug or unplug before checking the area for flammable environment around the cooler
  1 Monitor the area prior to and during work.
     Use a Combustible Gas Detector/ Monitor. Clear the area of any potential refrigerant leak.
     Make sure the leak detection equipment used is suitable for use with HCs.
     No ignition Sources
     No smoking, including displaying ‘No Smoking’ signs
  2 Survey the area around the equipment prior to servcing to establish any flammable hazards or
     ignition risks. Remove all sources of ignition. Be aware that a cell phone or similar electronic
     devices could be source of ignition.
     Labels
     Both cabinet and chassis labels must indicate for R290 refrigerant use. If the labels do not
     match assume the system has been retrofitted and is non-compliant.
  3 STOP work on this system immediately
     Inform owner (operator*) of system violation
     Offer to replace system with approved systems
     Refuse to service
     General Work Area
     Instruct anyone in the immediate area as to the nature of the work
  4 Avoid confined spaces
     If possible, section off the workspace
     Be aware of any flammable material in the area
     Minimum Room Volume
     Consideration to ensure that equipment is not installed in a room where the release of the HC
  5
     could cause an explosion hazard. Always follow local laws and regulations for installation,
     operation and servicing an HC cooler.
     Personal Protective Equipment
  6 Technicians should wear appropriate PPE, e.g.- including chemical goggles, protective gloves,
     grounding probe, anti-static band
     Free Air Movement
     Ensure that free air movement can be achieved around all refrigerant containing parts of the
  7 systems. Depending on the size of the room, especially in a confined space, mechanical
     ventilation may need to be considered.
     The ventilation should displace any released refrigerant and preferably expel it externally.
     Floor Voids
  8 HC refrigerants are heavier than air. Precautions should be made against refrigerant collecting
     in drains and low points of a flooring structure.
     Electrical Devices
     An initial safety check of components to see a fault exists that could compromise safety.
     Capacitors should be discharged with a bleed resistors (minimum 2 Watt / 10,000 Ω ) or
  9
     meter.
     Do not work on ‘live’ electrical components.
     Maintain a good ground – equipment and user
     Rated Equipment
     This includes, but not limited to
     - Gas Leak Detectors and Monitors
 10
     - Electrical Test meters (CAT III minimum)
     - Portable Lighting
     - non-sparking tools
     Work Space Guidelines
     -Good ventilation
 11
     - Purge refrigerant outdoors
     - Dry powder fire extinguishers
     Awareness
     Familiar with the information provided by other sources, such as the manufacturers of the
     system equipment, component manufacturers, refrigerant suppliers, and Material Safety
     Datasheets (MSDSs).
 12
     Occupants should be aware of manufacture operating instructions, procedures, guidelines and
     safety issues regarding the equipment.
     Be made aware to evacuate the space immediately following the accidental release of a
     flammable refrigerant.
Contact Us
31 Bramsteele Rd., Brampton, Ontario, Canada L6W 3K6
Telephone: (905) 459-0709
Toll Free: (800) 663-3005
Fax: (905) 459-1478

info@qbd.com
www.qbd.com

                                             22
You can also read