QUEEN CHARLOTTE PHARMACY UPGRADE - PROJECT ADDRESS: 3209 OCEANVIEW DRIVE, QUEEN CHARLOTTE, BC, CANADA
←
→
Page content transcription
If your browser does not render page correctly, please read the page content below
QUEEN CHARLOTTE PHARMACY UPGRADE PROJECT ADDRESS: 3209 OCEANVIEW DRIVE, QUEEN CHARLOTTE, BC, CANADA PROJECT TEAM OWNER: ARCHITECT: NORTHERN HEALTH AUTHORITY STANTEC Architecture Ltd. 300-299 Victoria Street 1100-111 Dunsmuir Street Prince George, BC V2L 5B8 Vancouver, BC, V6B 6A3 Contact: Contact: Jay Dupras Eleonore Leclerc tel: (250) 617-3805 tel: (604) 369-6753 email: Jay.Dupras@northernhealth.ca email: Eleonore.Leclerc@stantec.com MECHANICAL/PLUMBING ENGINEER: ELECTRICAL ENGINEER: STANTEC Consulting Ltd. STANTEC Consulting Ltd. 1100-111 Dunsmuir Street 1100-111 Dunsmuir Street Vancouver, BC, V6B 6A3 Vancouver, BC, V6B 6A3 Contact: Contact: John Maccarrone Thys Fourie APPROXIMATE LOCATION OF tel: (778) 772-6936 tel: (778) 838-0194 PHARMACY RENOVATION email: john.maccarrone@stantec.com email: thys.fourie@stantec.com DRAWING LIST: MAIN ARCHITECTURAL MECHANICAL ENTRANCE A001 - COVER SHEET M001 - DRAWING LIST, LEGEND, LEGEND, SCHEDULES, SCHEDULES AND HVACHVACCONTROLS CONTROLS A002 - GENERAL NOTES, SYMBOLS M101 - STORES LEVEL 1 -ROOM UPGRADE - LEVEL 1 - MECHANICAL MECHANICAL A101 - FLOOR PLAN - DEMOLITION/PROPOSED M102 - STORES LEVEL 2/3ROOM UPGRADE--NEW - MECHANICAL LEVEL 1 - MECHANICAL WORK A102 - RCP - DEMOLITION/PROPOSED M201 - NAPRA M200 UPGRADE - LEVEL HVAC SCHEDULES 1 - MECHANICAL AND DETAILS M202 - NAPRA UPGRADE - LEVEL 2/3 - MECHANICAL - NEW WORK ELECTRICAL M203 - NAPRA UPGRADE - HVAC SCHEDULES AND DETAILS E000 - COVER PAGE E100 - ELECTRICAL RENOVATION OCEANVIEW DRIVE E200 - ELECTRICAL SPECIFICATIONS 115602082 SITE PLAN - NTS ISSUED FOR TENDER - MAY 3RD 2021
G F E D C B A SYMBOLS LEGEND ABBREVIATIONS DETAIL NUMBER AFF ABOVE FINISHED FLOOR OSCI OWNER SUPPLIED CONTRACTOR INSTALLED 100A DOOR OPENING NUMBER CLR CLEAR OSOI OWNER SUPPLIED OWNER INSTALLED 1 SIM 0 1 2 3 4 5 6 CIF CONFIRM IN FIELD OSVI OWNER SUPPLIED, VENDER INSTALLED A802 CLF CLEAR GLASS +FILM PB PANIC BUTTON Stantec Architecture Ltd. 1 GENERAL SHEET NOTE CPT CARPET PE PATCH EXISTING 1100-111 Dunsmuir Street SHEET ON WHICH Vancouver, V6B 6A3 DETAIL IS SHOWN CMU CONCRETE MASONRY UNIT PT PAINT Tel: (604) 696-8000 / Fax: (604) 696-8100 1 DEMOLITION SHEET NOTE CONC CONCRETE PL (PLAM) PLASTIC LAMINATE 5 A A1 ELEVATION NUMBER CSCI CONTRACTOR SUPPLIED CONTRACTOR INSTALLED PREFIN PREFINISHED www.stantec.com A101 SHEET ON WHICH C/W COMPLETE WITH PS PRESSED STEEL Copyright Reserved 1 DRAWING REVISION ELEVATION IS SHOWN CT CERAMIC TILE PTR PRESSURE TREATED The Contractor shall verify and be responsible for all dimensions. 1 DBL DOUBLE PLY PLYWOOD DO NOT scale the drawing - any errors or omissions shall be ELEVATION NUMBER FLOOR FINISH B DP DEEP RB RUBBER BASE reported to Stantec without delay. The Copyrights to all designs and drawings are the property of 4 A600 2 FSV-# DTL DETAIL RCP REFLECTED CEILING PLAN Stantec. Reproduction or use for any purpose other than that LOCATION OF authorized by Stantec is forbidden. PHARMACY SHEET ON WHICH BSV-# DS DOWN SPOUT RF RESILIENT FLOORING RENOVATIONS 3 ELEVATION IS SHOWN BASE FINISH EXIST (EX) EXISTING RRM RAISED RUBBER MAT C SIM SIM SECTION NUMBER PHOTO TAG EXP FF EXPOSED FACTORY FINISH RWL SCW RAIN WATER LEADER SOLID CORE WOOD 1 1 A909 A909 BUILDING SECTIONS # Axxx PHOTO NUMBER FG FIBERGLASS SC SEALED CONCRETE SHEET NUMBER FOS FACE OF SILL SDT SMOKE DETECTOR SHEET ON WHICH D FOC FACE OF CONCRETE SIM SIMILAR SECTION IS SHOWN ROOM TAG ROOM NAME G GLASS SS STAINLESS STEEL ROOM NAME 101 GWB GYPSUM WALL BOARD TFF TOP OF FINISHED FLOOR ROOM NUMBER 150M2 HL HOLLOW METAL T/O TOP OF ROOM AREA E SECTION NUMBER HS HANDICAP SHOWER TYP TYPICAL SIM 1 HSS HOLLOW STEEL SECTION UNF UNFINISHED A909 WALL SECTIONS EWD-10F-1 WINDOW TAG LPO LAST PERSON OUT U.N.O. UNLESS NOTED OTHERWISE LT LIGHT U/S UNDERSIDE SHEET ON WHICH WALL TAG SECTION IS SHOWN MT METAL V.I.F VERIFY IN FIELD # WALL TYPE NIC NOT IN CONTRACT VSVI VENDER SUPPLIED VENDER INSTALLED x WALL TERMINATION OC ON CENTRE VSCI VENDER SUPPLIED CONTRACTOR INSTALLED 4 FLOOR FLOOR OR ROOF LEVEL NAME O.I.C OPTICAL IMAGING CAMERA WD WOOD 0'-0" VERTICAL ELEVATION - WALL FINISH TAG OSF OUTSIDE FACE OF WP WATERPROOFING PHARMACY RENOVATION CEILING TYPE BL-# INTERIOR WINDOW COVERING TAG ACT1 3000 LOCATION PLAN - LEVEL 1 CC-# CUBICLE CURTAIN TAG CEILING HEIGHT SC-# SHOWER CURTAIN TAG Clear Dim. Panel Widths & Types Frame Opening Door Rm. No. of Room Schedule Room Name Panel Panel Fire No. No. Width Height Panels Material Finish Thickness Hardware Type Material Finish Note Area Name Number Width Type Label Level 01 7.26 m² ANTE ROOM 1-926 New door, frame and hardware. Stantec Architecture Inc D926 ANTEROOM 1‐926 915 2150 1 915 D1 ED DP 45 Set 1.0 F1 PS PTD N/A 6.59 m² HAZARDOUS COMPOUNDING ROOM 1-927 Interlocked with door D927 23.16 m² STORE 1-925 50 VARIES 50 SEE SCHEDULE SEE SCHDL 150 150 GENERAL DEMOLITION NOTES 50 200 3 1. AS REQUIRED BY ALL RENOVATION WORK, REMOVE AND DISPOSE OF PORTIONS OF EXISTING MASONRY, GYMSPUN BOARD WALLS AND CEILINGS INCLUDING ALL WALL MOUNTED ITEMS, WALL MOUNTED EQUIPMENT AND ACCESSORIES ETC. THE CONTRACTOR SHALL BE FULLY RESPONSIBLE TO CHECK AND ENSURE THE STRUCTURAL INTEGRITY AND STABILITY OF THE RETAINED PORTIONS OF THE EXISTING WALLS AND STRUCTURAL ELEMENTS INCLUDING COLUMNS AND FLOOR ASSEMBLY, AND SHALL NOT DEMOLISH ANY STRUCTURAL ELEMENTS IF FOUND EMBEDDED IN THE EXISTING WALLS OR FLOORS. LAMINATED VARIES SEE SCHEDULE VARIES SEE SCHEDULE GLAZING 2. REMOVE AND DISPOSE OF EXISTING WALL/PARTITION AS REQUIRED TO CREATE AN OPENING FOR NEW MECHANICAL OPENINGS 50 16 3. AS INDICATED ON FLOOR PLAN REMOVE AND DISPOSE OF EXISTING FLOOR FINISH TO EXISTING CONCRETE SLAB. SCARIFY OR SHOT BLAST AS REQUIRED TO PREPARE FLOOR FOR UNDERLAYMENT AND/OR FINISH PER MANUFACTURERS. 4. DISPOSAL OF ITEMS SHALL BE IN COORDINATION WITH FACILITIES MANAGEMENT DEPARTMENT / EMPLOYER'S REPRESENTATIVE AND CAN 13 INCLUDE SALVAGING CERTAIN MATERIALS AND DEPOSITING THEM ON CAMPUS OR OFF-SITE. CONTRACTOR TO PREPARE A LIST OF ITEMS TO BE SALVAGED IN AGREEMENT PRIOR TO START OF DEMOLITION WORK. 50 5. REFER ALSO TO THE MECHANICAL AND ELECTRICAL DRAWINGS PRIOR TO DEMOLITION. THE SCOPE OF WORK HAS GENERALLY BEEN INDICATED ON 1 ISSUED FOR TENDER RLB EL 2021-05-03 1000 THE DRAWINGS FOR THE CONTRACTORS INFORMATION. THE CONTRACTOR SHALL BE RESPONSIBLE TO DETERMINE THE FULL SCOPE, EXTENT, NATURE AND MANNER OF DEMOLITION REQUIRED TO COMPLETE THE WORK UNDER THIS PACKAGE. Revision By Appd YYYY.MM.DD 50 6. ONLY WORKMEN SKILLED AND KNOWLEDGEABLE IN THEIR RESPECTIVE TRADES SHALL BE EMPLOYED IN THE DEMOLITION. 7. FACILITY TO REMAIN OPEN AND ACCESSIBLE TO STAFF DURING THE COURSE OF DEMOLITION AND CONSTRUCTION. PROVIDE TEMPORARY 13 LOCATION OF HOARDING/TARPS, FULLY TAPED AND SEALED TO CONTAIN DUST AND DEBRIS. COORDINATE WITH OWNER/FACILITIES MANAGEMENT. PHARMACY A RENOVATIONS F1 D1 8. ALL EXISTING FIRE EXIT DOORS ARE TO REMAIN FUNCTIONAL AND ACCESSIBLE FOR EMERGENCY EGRESS. PROVIDE AND MAINTAIN DUST SEALS AROUND DOORWAYS TO PREVENT DUST FROM ENTERING STAIRS OR OTHER OCCUPIED SPACES. 9. EXISTING AREAS, SURFACES, AND FINISHES NOT AFFECTED BY THE WORK INTHIS CONTRACT SHALL BE PROTECTED PRIOR TO COMMENCEMENT FRAME TYPE DOOR TYPE FRAME PROFILE AND UNTIL COMPLETION OF THE WORK. ISSUED FOR 90% CLIENT REVIEW HB EL 2021.01.15 1 : 25 1 : 25 1:5 10. CONTRACTOR TO TAKE CARE TO DEMOLISH ONLY EXISTING CONSTRUCTION WHICH IS REQUIRED TO BE DEMOLISHED AND NOT DISTURB EXISTING CONSTRUCTION TO REMAIN. IN THE COURSE OF DEMOLITION, IF THE CONTRACTOR DISTURBS EXISTING CONSTRUCTION TO REMAIN, REPAIRS OR Issued By Appd YYYY.MM.DD B REPLACEMENT SHALL BE COMPLETED AT THE CONTRACTOR'S EXPENSE. 2 11. WHERE DEMOLITION OF EXISTING CONSTRUCTION AND/OR EQUIPMENT OCCURS, PATCH AND REPAIR FLOOR, WALL, AND CEILING CONSTRUCTION AND/OR FINISHES TO MATCH ADJACENT EXISTING CONSTRUCTION. MINIMUM DIMENSION FROM EDGE SEE ARCH, MECH, OR ELECTRICAL 12. IF UNFORSEEN CONDITIONS OR EXISTING UNDOCUMENTED UTILITIES OR STRUCTURAL ELEMENTS ARE DISCOVERED, WORK IN THE IMMEDIATE OF EQUIPMENT TO EDGE OF HOUSEKEEPING PAD FOR VIBRATION DRAWINGS FOR SIZE AND LOCATION AREA IS TO BE STOPPED UNTIL THE STATUS OF THE EXISTING UTILITIES / STRUCTURAL ELEMENTS ARE ESTABLISHED BY THE OWNER OR ENGINEER. OBTAIN APPROVAL TO PROCEED FROM THE OWNER. PRELIMINARY ISOLATION REQUIREMENT 15M @ 400 E.W. 13. CONTRACTOR MUST NOTIFY THE OWNER THREE DAYS PRIOR TO STARTING A DEMOLITION PHASE SO THE OWNER MAY REMOVE ITEMS, IF NEEDED. NOT FOR CONSTRUCTION 14. REMOVE AND DISPOSE OF ITEMS OR DEBRIS THAT IS NOT TO BE TURNED OVER TO THE OWNER. COORDINATE WITH THE FACILITIES 15M@400 (1' - 4") H1E DRILL AND DOWEL MANAGEMENT DEPARTMENT TO ESTABLISH A LOCATION FOR STORAGE OF SALVAGED ITEMS OR EQUIPMENT TO BE TURNED OVER TO THE OWNER. Not for permits, pricing or other official purposes. MAIN 25mm (1") CHAMFER 30 TO SLAB WITH HILTI HY200 This document has not been completed or checked and ENTRANCE TYP. 100 (4") MIN EMBED / EXIT is for general information or comment only. GENERAL CONSTRUCTION NOTES 150 (6") MAX. 1. GENERAL CONTRACTOR TO CO-ORDINATE ALL SECTIONS OF WORK, PAY ALL FEES AND OBTAIN ALL PERMITS AS REQUIRED. 2. ANY WORK REQUIRED BY THE DRAWINGS OR REASONABLY NECESSARY TO COMPLETE THE WORKSHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. Queen Charlotte Pharmacy 3. ALL WORK COMPLETED BY THE CONTRACTOR TO BE IN ACCORDANCE WITH THE DRAWINGS. ALTERNATIVES CAN BE PROPOSED BY PARTIAL FIRE SEPARATIONS PLAN LEVEL 1 - NTS THE CONTRACTOR FOR NORTHERN AUTHORITY REPRESENTATIVES/ DESIGNER APPROVAL PROVIDED THE APPROVED PROJECT SCHEDULE IS NOT DELAYED AS A RESULT OF SUBSTITUTION AND THE QUALITY IS NOT TO A LESSER STANDARD. QUEEN CHARLOTTE PHARMACY UPGRADE ANCHOR BOLTS AS REQUIRED 2-ADDITIONAL 15M DOWELS @200 (8") SLAB-ON-GRADE OR SUSPENDED SLAB BY EQUIPMENT SUPPLIER IF B>2000 (6' - 7"). EMBEDDED 125 (5") 4. ALL WORK TO BE PERFORMED IN ACCORDANCE WITH LATEST APPLICABLE BUILDING CODES AND FIRE REGULATIONS AND ANY LOCAL BUILDING REQUIREMENTS. EMBEDDED 125 (5") IN EXISTING SLAB IN EXISTING SLAB Title 5. VERIFY AND CONFIRM ALL DIMENSIONS ON SITE AND REPORT ANY DISCREPANCIES TO THE ARCHITECT BEFORE PROCEEDING WITH WORK. GENERAL NOTES 1 NOTES: 6. THESE DRAWINGS TO BE READ IN CONJUNCTION WITH ALL OTHER DRAWINGS, SCHEDULES, SPECIFICATIONS, DETAILS AND 1. PAD SIZE SHALL BE MINIMUM INDICATED OR AS SHOWN ON THE PLANS OR AS DETERMINED BY THE EQUIPMENT MANUFACTURER AND APPROVED BY THE ENGINEER. ENGINEERING DRAWINGS AND SPECIFICATIONS FOR COORDINATION WHERE APPLICABLE. 2. THE SIZE, NUMBER, TYPE, LOCATION, AND THREAD PROJECTION OF THE ANCHOR BOLTS SHALL BE DETERMINED BY THE EQUIPMENT MANUFACTURER, AND SHALL BE AS APPROVED BY THE ENGINEER. ANCHOR BOLTS SHALL BE HELD IN POSITION WITH A TEMPLATE WHILE PAD IS BEING PLACED. Project No. 3. EQUIPMENT BASES SHALL BE INSTALLED LEVEL UNLESS SPECIFIED OTHERWISE. Scale 4. WEDGES OR SHIMS SHALL BE USED TO SUPPORT THE BASE WHILE THE NON-SHRINK GROUT IS PLACED. TEMPORARY LEVELING NUTS SHALL BE BACKED OFF. IF LEFT IN, 115602082 As indicated HE WEDGES OR SHIMS SHALL NOT BE EXPOSED TO VIEW. 5. USE HILTI HIT HY 200 SYSTEM FOR ALL REBAR AND ANCHOR BOLTS FASTENING TO EXISTING CONCRETE SLAB Revision Drawing No. 1 3/5/2021 7:25:55 PM TYPICAL HOUSEKEEPING PAD 1 : 10 A-002 ORIGINAL SHEET - ARCH D (24"x36")
G F E D C B A 2 3 8800 REMOVE REFRIGERATOR Stantec Architecture Ltd. EXISTING COUNTERS AND SET ASIDE FOR 1100-111 Dunsmuir Street TO REMAIN IN PLACE RELOCATION Vancouver, V6B 6A3 Tel: (604) 696-8000 / Fax: (604) 696-8100 www.stantec.com 5 TS EXIST. GLOVE BOX TO REMAIN Copyright Reserved EXIST. TALL The Contractor shall verify and be responsible for all dimensions. SHELVES EXISTING PASS-THROUGH DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay. TO REMAIN IN PLACE The Copyrights to all designs and drawings are the property of Stantec. Reproduction or use for any purpose other than that authorized by Stantec is forbidden. 4 3 A-101 A-101 EXIST. STRIP OF FLOORING TO RESILIENT BE REMOVED (3" W) FLOORING REMOVE DOOR, FRAME STORE 2965 AND HARDWARE 1-925 REMOVE STRIP OF EXIST. SHEET VINYL TO SUIT NEW DEMARCATION LINE TS AS SHOWN BELOW HAZARDOUS COMPOUNDING ANTE ROOM ROOM 1-926 EXISTING BSC 1-927 TS TS EXIST. EXIST. SINK EXIST. EYEWASH HOOKS 4 PHARMACY 2450 RENOVATION 1 FLOOR PLAN - DEMOLITION A-101 1 : 25 EXISTING PASS THROUGH Stantec Architecture Inc TS EXIST. GLOVE BOX RAISE EXIST. SS COUNTER TO EXIST. TALL SUIT RELOCATED FRIDGE EXIST COUNTER SHELVES RELOCATE EXISTING UNDER COUNTER REFRIGERATOR DIRTY ZONE 3 EXIST. 4 PATCH AND REPAIR EXIST. WALL 3 DOOR A-101 PROTECTION AFFECTED BY A-101 DOOR HARDWARE REMOVAL. NEW CONTRASTING COLOUR STORE STRIP OF FLOORING TO BE EXIST. DOOR, FRAME AND 1-925 HOT WELDED TO EXISTING HARDWARE RELOCATED. VINYL FLOOR D926 REFER TO EXIST. MOUNTING HEIGHTS. TS CLEAN ZONE HAZARDOUS COMPOUNDING ANTE ROOM EXISTING BSC ROOM TS TS 1-926 1 ISSUED FOR TENDER RLB EL 2021-05-03 1-927 Revision By Appd YYYY.MM.DD EXIST. EXIST. SINK EXIST. EYEWASH HOOKS ISSUED FOR 90% CLIENT REVIEW HB EL 2021.01.15 Issued By Appd YYYY.MM.DD 2 FLOOR PLAN - PROPOSED 2 A-101 1 : 25 1536 914 PRELIMINARY NOT FOR CONSTRUCTION Not for permits, pricing or other official purposes. 515 This document has not been completed or checked and is for general information or comment only. 350 EXISTING EXISTING GLOVE BOX TALL SHELVES RAISE EXISTING COUNTER TO SUIT RELOCATED FRIDGE. DIMS TO BE CONFIRNED. Queen Charlotte Pharmacy 530 RELOCATE EXISTING FRIDGE 2185 QUEEN CHARLOTTE PHARMACY UPGRADE Title 1100 FLOOR PLANS - DEMO AND PROPOSED TBD 900 900 EXISTING EXISTING 1 WALL BASE WALL BASE FINISHED FLOOR FINISHED FLOOR Project No. Scale 115602082 1 : 25 2220 Revision Drawing No. 1 3/5/2021 7:25:57 PM 3 A-101 LEVEL 1 - RM 1-927 CHEMO - NORTH 1 : 25 4 A-101 LEVEL 1 - RM 1-926 ANTE ROOM - NORTH 1 : 25 A-101 ORIGINAL SHEET - ARCH D (24"x36")
G F E D C B A 1 2 3 Stantec Architecture Ltd. 3683 8800 1100-111 Dunsmuir Street Vancouver, V6B 6A3 Tel: (604) 696-8000 / Fax: (604) 696-8100 PAINT ENTIRETY OF CEILING www.stantec.com 5 IN ROOMS 1-926 & 1-927 Copyright Reserved The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay. The Copyrights to all designs and drawings are the property of Stantec. Reproduction or use for any purpose other than that HAZARDOUS COMPOUNDING authorized by Stantec is forbidden. ANTE ROOM ROOM 1-926 1-927 EXISTING CEILING TO REMAIN EXISTING CEILING TO REMAIN 1213 661 RETAIN EXISTING LUMINAIRE NEW RETAIN EXISTING LUMINAIRE DIFFUSER. SEE MECH. 603 EXISTING CEILING TO REMAIN IN PLACE CUT EXISTING OPENING TO EXISTING CEILING TO REMAIN IN PLACE SUIT NEW DIFFUSER. REFER TO MECH. 1213 RETAIN EXISTING LUMINAIRE RETAIN EXISTING LUMINAIRE 4 1139 PHARMACY GWB 2700 GWB 2700 RENOVATION 603 93 505 Stantec Architecture Inc REFRAME EXISTING OPENING WITH 92mm GALV STEEL STUD FRAMING AS REQUIRED. REMOVE ADJACENT GWB AND FRAMING AS REQUIRED FOR NEW DIFFUSER INSTALLATION, AND PATCH AND REPAIR WITH MATCHING STEEL STUD FRAMING AND GWB. TAPE, FEATHER INTO ADJACENT SURFACE, SAND, AND PAINT. 3 1 LEVEL 1 - RCP A-102 1 : 25 1 ISSUED FOR TENDER RLB EL 2021-05-03 Revision By Appd YYYY.MM.DD ISSUED FOR 90% CLIENT REVIEW HB EL 2021.01.15 Issued By Appd YYYY.MM.DD 2 PRELIMINARY NOT FOR CONSTRUCTION Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only. Queen Charlotte Pharmacy QUEEN CHARLOTTE PHARMACY UPGRADE Title CEILING PLAN - 1 DEMOLITION/PROPOSED Project No. Scale 115602082 1 : 25 Revision Drawing No. 1 3/5/2021 7:25:57 PM A-102 ORIGINAL SHEET - ARCH D (24"x36")
G F E D C B A MECHANICAL SHEET LIST AIR FLOW MEASURING STATION (REFER TO CONTROLS LEGEND) ## SHEET NAME PIPING SYSTEMS (HVAC) VENTILATION (HVAC) QUANTITY M001 DRAWING LIST, LEGEND, SCHEDULES, AND HVAC - - TYPE CONTROLS PROJECT 2 1/2" PIPE SIZE AIR FLOW ARROW - SIZE (IN.) AIR OUTLET OR INLET TAG (REFER TO SCHEDULE) M101 STORES ROOM UPGRADE - LEVEL 1 MECHANICAL NORTH Stantec Consulting Ltd. CHWR CHILLED WATER RETURN - VOLUME (CFM) M102 STORES ROOM UPGRADE - LEVEL 1 - MECHANICAL 18"x12" 18"x12" RECTANGULAR DUCT AND SIZE* 1100-111 Dunsmuir Street M201 NAPRA UPGRADE - LEVEL 1 - MECHANICAL Vancouver, V6B 6A3 NORTH ARROW CHWR(G) CHILLED WATER RETURN - GLYCOL 18"ø 18"ø ROUND DUCT AND SIZE* Tel: (604) 696-8000 / Fax: (604) 696-8100 M202 NAPRA UPGRADE - LEVEL 2/3 - MECHANICAL - NEW WORK SECTION NUMBER RECTANGULAR DIFFUSER, SUPPLY. OPTIONAL ARROWS SHOW THE 5 CHWR(P) CHILLED WATER RETURN - PROCESS 18"x12"ø 18"x12"ø FLAT OVAL DUCT AND SIZE* FLOW DIRECTION. www.stantec.com M203 NAPRA UPGRADE - HVAC SCHEDULES AND DETAILS SIM RECTANGULAR REGISTER OR GRILLE, RETURN 1 CHWS CHILLED WATER SUPPLY 18"x12" EXTERIOR DUCT TREATMENT* Copyright Reserved _______ WALL SECTIONS A909 The Contractor shall verify and be responsible for all dimensions. 1 DRAWING REVISION CHWS(G) CHILLED WATER SUPPLY - GLYCOL RECTANGULAR REGISTER OR GRILLE, EXHAUST 18"x12" 18"x12" RECTANGULAR DUCT WITH ACOUSTIC LINING* DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay. SHEET ON WHICH CHWS(P) DUCT SECTION, SUPPLY AIR. SIZE* IS HORIZONTAL DIM. x VERTICAL DIM. ROUND DIFFUSER, SUPPLY CHILLED WATER SUPPLY - PROCESS 30"x12" The Copyrights to all designs and drawings are the property of SECTION IS SHOWN APPLIES TO RECT., ROUND AND OVAL Stantec. Reproduction or use for any purpose other than that MATCH LINE CWR CONDENSER WATER RETURN LINEAR DIFFUSER authorized by Stantec is forbidden. DUCT SECTION, OUTSIDE AIR. APPLIES TO RECT., ROUND AND OVAL CWR(CT) CONDENSER WATER RETURN (COOLING TOWER) SIDEWALL REGISTER OR GRILLE, SUPPLY DETAIL NUMBER SECTION NUMBER DUCT SECTION, RETURN AIR. APPLIES TO RECT., ROUND AND OVAL CWS CONDENSER WATER SUPPLY SIDEWALL GRILLE, RETURN OR EXHAUST SIM SIM DUCT SECTION, EXHAUST AIR. APPLIES TO RECT., ROUND AND OVAL 1 SIM 1 1 DETAIL CALLOUTS _______ _______ BUILDING SECTIONS CWS(CT) CONDENSER WATER SUPPLY (COOLING TOWER) UC UNDERCUT DOOR A802 A909 A909 FLEXIBLE DUCT DTR DUAL TEMPERATURE RETURN (HOT OR CHILLED) DOOR GRILLE OR LOUVER ELBOW TURN, SUPPLY DOWN. APPLIES TO RECT., ROUND AND OVAL SHEET ON WHICH SHEET ON WHICH DETAIL IS SHOWN SECTION IS SHOWN DTS DUAL TEMPERATURE SUPPLY (HOT OR CHILLED) TRANSFER GRILLE OR LOUVER ELBOW TURN, OUTSIDE AIR DOWN. APPLIES TO RECT., ROUND AND OVAL HWR HEATING WATER RETURN COIL (REFER TO CONTROLS LEGEND) ELBOW TURN, RETURN DOWN. APPLIES TO RECT., ROUND AND OVAL HWR(G) HEATING WATER RETURN - GLYCOL ELBOW TURN, EXHAUST DOWN. APPLIES TO RECT., ROUND AND OVAL ID-# EQUIPMENT TAG GENERAL NOTES HWS HEATING WATER SUPPLY UP CHANGE IN DUCT ELEVATION RISING IN DIRECTION INDICATED QUANTITY INTENT OF THE DRAWINGS AND SPECIFICATIONS ARE TO PROVIDE COMPLETE PLUMBING, FIRE PROTECTION, HEATING, CONTROL, VENTILATION AND AIR CONDITIONING SYSTEMS FOR THE PROPOSED PROJECT. THE - - TYPE HWS(G) HEATING WATER SUPPLY - GLYCOL SYSTEMS PROVIDED SHALL CONFORM TO THE DETAILS STATED IN THE SPECIFICATIONS AND SHOWN ON THE DRAWINGS. ITEMS OR WORK NOT SHOWN OR SPECIFIED, BUT REQUIRED FOR A COMPLETE HEATING, DN CHANGE IN DUCT ELEVATION DROPPING IN DIRECTION INDICATED RADIATION HEATING TAG (REFER TO SCHEDULE) - LENGTH (FT) VENTILATION AND AIR CONDITIONING SYSTEM, SHALL BE PROVIDED AND SHALL CONFORM WITH ACCEPTED TRADE PRACTICES, LOCAL CODES, AND GOVERNING AUTHORITIES. PIPE INSULATION - CAPACITY (MBH) THE DRAWINGS AND SPECIFICATIONS ARE PRESENTED TO DEFINE SPECIFIC SYSTEM REQUIREMENTS AND SERVE TO EXPAND ON THE PRIMARY CONTRACT REQUIREMENTS OF PROVIDING COMPLETE SYSTEMS. THE END CAP 4 DRAWINGS ARE DIAGRAMMATIC AND INDICATE ONLY THE GENERAL ARRANGEMENT OF THE ITEMS COMPRISING THE SEVERAL SYSTEMS INCLUDED IN THE HEATING, VENTILATION AND AIR CONDITIONING WORK. ELBOW, RECTANGULAR, SMOOTH RADIUS WITH SPLITTER VANES DO NOT SCALE THE DRAWINGS. BECAUSE OF THE SCALE OF THE DRAWINGS, IT IS NOT POSSIBLE TO INDICATE ALL OFFSETS, FITTINGS, VALVES, OR SIMILAR ITEMS WHICH MAY BE REQUIRED TO MAKE A COMPLETE PIPING COMPONENTS (0.25 R/W DEFAULT) T THERMOSTAT OPERATING SYSTEM. CAREFULLY INVESTIGATE CONDITIONS AFFECTING WORK AND INSTALL WORK IN SUCH A MANNER THAT INTERFERENCES BETWEEN PIPES, CONDUIT, DUCTS, EQUIPMENT, ARCHITECTURAL AND ELBOW, RECTANGULAR, SMOOTH RADIUS WITHOUT VANES (1.5 R/W H HUMIDITY SENSOR STRUCTURAL FEATURES SHALL BE AVOIDED. PROVIDE ITEMS THAT MAY BE REQUIRED TO MEET THE CONDITIONS AT THE BUILDING. DEFAULT) CONTRACTORS SHALL HAVE SUFFICIENT EXPERTISE IN THIS TYPE OF CONSTRUCTION TO REALIZE THE EXTENT OF THE WORK REQUIRED. THEREFORE, IT SHOULD BE OBVIOUS TO ANY PRUDENT FIRM WITH ELBOW, ROUND, SMOOTH RADIUS (1.5 R/W DEFAULT) EXPERIENCE IN THIS FIELD THAT THESE DOCUMENTS MAY NOT EXPLICITLY DISCLOSE FINAL DETAILS; HOWEVER, CONTRACTORS SHALL HAVE THE EXPERTISE NECESSARY TO INCLUDE NECESSARY APPOINTMENTS. ISOLATION VALVE (GENERIC) MITERED ELBOW, RECTANGULAR, WITH TURNING VANES PROTECT FLOORING FROM DAMAGE DURING THE CONSTRUCTION PERIOD. PROVIDE PLYWOOD OR SIMILAR MATERIAL UNDER EQUIPMENT OR MATERIALS STORED ON FLOORS, AND IN AREA WHERE CONSTRUCTION GATE VALVE MAY DAMAGE THE FLOOR SURFACES. FLOOR SURFACES (INCLUDING SEALER) DAMAGED DURING THE CONSTRUCTION SHALL BE REPLACED AT THE COST OF THE CONTRACTOR AT FAULT. RECTANGULAR TO ROUND TRANSITION GLOBE VALVE AD COORDINATE ALL WORK WITH WORK SHOWN ON DRAWINGS FOR OTHER TRADES. COORDINATE EXACT LOCATION OF DIFFUSERS, REGISTERS AND GRILLES WITH ARCHITECTURAL AND ELECTRICAL REFLECTED AD AD DUCT ACCESS DOOR (TOP, SIDE, BOTTOM) CEILING PLANS. CHECK VALVE (GENERIC) FLEXIBLE CONNECTION PROVIDE MAINTENANCE AREAS AROUND ALL EQUIPMENT AS REQUIRED BY CODES AND RECOMMENDED BY THE EQUIPMENT MANUFACTURER. PAY PARTICULAR ATTENTION TO COIL ACCESS AND REMOVAL. FC BALANCING VALVE INDICATED DUCT SIZES ARE CLEAR INSIDE OF DUCT DIMENSIONS, INCLUDING ACOUSTIC DUCT LINER WHERE USED. * NOTE: ALL DUCT SIZES ARE INTERIOR, FREE DIMENSIONS (ALWAYS PRESSURE REDUCING VALVE WIDTH X HEIGHT IN FLOOR PLAN AND SECTION) INDICATED DUCT AND PIPING RUNS ARE DIAGRAMMATIC. CONTRACTOR SHALL DETERMINE ALL REQUIRED OFFSETS AND DIRECTION CHANGES BEFORE FABRICATION AND INSTALLATION TO AVOID INTERFERENCE 2-WAY WITH OTHER TRADES. 2-WAY CONTROL VALVE (GENERIC) BACKDRAFT DAMPER 3-WAY 3-WAY CONTROL VALVE (GENERIC) BDD UNLESS OTHERWISE NOTED, ALL DUCTWORK AND PIPING IS OVERHEAD, TIGHT TO UNDERSIDE OF SLAB/STEEL, WITH SPACE FOR INSULATION IF REQUIRED. MANUAL DAMPER 3-WAY ALL PIPING AND DUCTWORK IN FINISHED ROOMS OR SPACES SHALL BE INSTALLED CONCEALED IN A FURRED CHASE OR ABOVE THE CEILING. PUMP (GENERIC) MOTORIZED DAMPER M INSTALL PIPING AND DUCTWORK SO THAT ALL VALVES, DAMPERS AND ACCESS DOORS ARE ACCESSIBLE. Y STRAINER (GENERIC) FIRE DAMPER NO PIPING OR DUCTWORK SHALL BE LOCATED IN ELECTRICAL ROOMS, ELECTRICAL CLOSETS OR TELECOMMUNICATIONS ROOMS UNLESS THOSE PIPES OR DUCTS SERVE ONLY THAT SPACE AND ARE INDICATED ON PIPE CAP SMOKE DAMPER 3 THE DRAWINGS. PIPE BREAK SMOKE AND FIRE DAMPER FLOOR PLANS SHOW GENERAL PIPE ROUTING. REFER TO PIPING DIAGRAMS AND DETAILS FOR LOCATIONS OF VALVES AT EQUIPMENT. PIPING ELBOW UP DUCT SILENCER INSTALL ALL DRAIN PIPING WITH 2% MINIMUM GRADE UNLESS OTHERWISE NOTED. PIPING ELBOW DOWN X CONTROL DEVICE PROVIDE DRAIN VALVES AT THE BASE OF ALL RISERS AND AT ALL PIPING LOW POINTS ON HOT WATER, GLYCOL WATER AND CHILLED WATER PIPING SYSTEMS. VALVES SHALL BE COMPLETE WITH HOSE CONNECTIONS AND SCREW-ON CAPS. UNION CONNECTION 2 3 PROVIDE MANUAL AIR VENTS ON HOT WATER AND CHILLED WATER PIPING BRANCHES AND AT ALL HIGH POINTS FOR VENTING. PROVIDE SHUT-OFF VALVES AT EQUIPMENT REQUIRING CONNECTION, REGARDLESS OF WHETHER SHOWN ON DRAWINGS. PROVIDE SHUT-OFF VALVES IN UTILITY SHAFTS ON EACH FLOOR FOR ALL PIPING SERVING THE FLOOR. DO NOT PROVIDE VALVES IN WATER PRESSURE RELIEF PIPING. Revision By Appd YYYY.MM.DD PIPING, EXCEPT IN MECHANICAL ROOMS AND ROOMS WITHOUT CEILINGS, SHALL BE LOCATED CONCEALED IN CHASES OR ABOVE THE CEILING UNLESS OTHERWISE NOTED. UNLESS OTHERWISE NOTED, MINIMUM SIZE FOR ALL PIPING SHALL BE 20mm (3/4"). HAZARDOUS STERILE COMPOUNDING ROOM (Pc - CLEAN HAZARDOUS (HD) STERILE PREP ANTE ROOM (Pb) -NAPRA ROOM), NAPRA CRITERIA: CRITERIA: THE MECHANICAL CONTRACTOR SHALL PROVIDE ACCESS PANELS NOT SMALLER THAN 600mmX600mm (24"x24") FOR ACCESS TO CONCEALED TRAPS, VALVES, CLEANOUTS, MOTORS, FIRE DAMPERS, CONTROLS, - ISO CLASS 7 - ISO CLASS 7 DRAIN POINTS, OR SIMILAR ITEMS WHERE NO OTHER MEANS OF ACCESS IS PROVIDED. - 30 AIR CHANGES PER HOUR - 30 AIR CHANGES PER HOUR - RELATIVE PRESSURIZATION: NEGATIVE: PB-PC > 2.5 Pa - RELATIVE PRESSURIZATION: POSITIVE: PB-PA ≥5 Pa COORDINATE ALL DUCTWORK PENETRATIONS IN MASONRY WITH STRUCTURAL ENGINEER PRIOR TO ANY WORK BEING PERFORMED. ALL LINTELS REQUIRED TO BE DETAILED BY STRUCTURAL ENGINEER AND - TEMPERATURE ≤ 20oC - TEMPERATURE ≤20oC PHARMACY WORKROOM. REFER TO M100 SERIES DRAWINGS. ISSUED FOR TENDER NG DB 2021.05.03 PROVIDED BY GENERAL CONTRACTOR. PROVIDE SLEEVES FOR ROUND DUCTWORK. - RELATIVE HUMIDITY 40% (RANGE 30 TO 60) - RELATIVE HUMIDITY 40% (RANGE 30 TO 60) ISSUED FOR 90% CLIENT REVIEW NG DB 2021.01.15 - ALL AIR EXHAUSTED TO THE EXTERIOR - ALL AIR EXHAUSTED TO THE EXTERIOR By Appd YYYY.MM.DD PROVIDE SLEEVES IN STRUCTURE FOR ALL PIPING PENETRATING WALLS OR FLOORS. Issued E-1 PROVIDE APPROVED FIRESAFING AT OPENINGS IN FLOORS, WALLS, ETC. 200x200 2 TS 25 L-1 LOCATE ALL ROOM THERMOSTATS 1500mm (5'-0") (CENTERLINE) ABOVE FINISHED FLOOR ON THE VERTICAL CENTERLINE OF THE ROOM LIGHT SWITCH. NOTIFY THE ARCHITECT OF ANY ROOMS WHERE THE ABOVE ROOM SCHEDULE 300ø LOCATION CANNOT BE MAINTAINED OR WHERE THERE IS A QUESTION ON LOCATION. 165 DIFFUSER, REGISTER AND GRILLE SIZES SHOWN ON FLOOR PLANS ARE NECK SIZES OR AS INDICATED BY SCHEDULE. NAPRA - HD Anteroom (Pb) DPS Pb PRELIMINARY 1-927 Pa PAINT ALL PIPING, SUPPORTS, ETC. THAT WILL BE EXPOSED TO WEATHER. HAZARDOUS COMPOUNDING Pc Pb ++ +- NOT FOR CONSTRUCTION PAINT ALL PIPING, SUPPORTS, ETC. THAT WILL BE EXPOSED IN MECHANICAL ROOMS AND INTERIOR SPACES. NAPRA - HD Sterile ROOM -- ++ 1-925 Not for permits, pricing or other official purposes. Compounding Room (Pc) DPS STORE E-1 TS This document has not been completed or checked and WHERE SPACE IS AVAILABLE, CONTRACTOR, AT HIS OPTION, MAY SUBSTITUTE RADIUS ELBOWS FOR RECTANGULAR ELBOWS WITH TURNING VANES. Pharmacy 200x200 TS TS is for general information or comment only. ARCHITECTURAL, MECHANICAL AND ELECTRICAL ITEMS ARE TO BE SUPPORTED FROM SECONDARY MEMBERS, SUPPLIED AND INSTALLED BY THE CONTRACTOR THAT ARE INDEPENDENT OF THE MAIN STRUCTURAL 25 1-926 MEMBERS. WHERE THE PRIMARY MEMBERS ARE TRUSSES, THE SECONDARY MEMBERS SHOULD BE LOCATED ON THE TOP CHORD NEAR THE INTERSECTION OF THE VERTICAL / DIAGONAL WEB MEMBERS AND THE ANTE ROOM TOP CHORD, OR ATTACHED TO THE VERTICAL MEMBERS. LOADS LESS THAN 25 KG. MAY BE SUPPORTED FROM THE BOTTOM CHORD, PROVIDED NO MATERIAL IS REMOVED FROM THE BOTTOM CHORD AND THE L-1 E-1 SUPPORT IS LOCATED ADJACENT THE INTERSECTION OF THE VERTICAL /DIAGONAL WEB MEMBERS AND THE BOTTOM CHORD OF THE TRUSSES. 300ø 200x200 200 65 ITEMS ARE NOT TO BE SUPPORTED DIRECTLY FROM THE METAL DECK UNLESS APPROVED BY THE CONSULTANT. IN AREAS WITH EXPOSED CEILING SPACE, ROUTE DUCTS AS HIGH AS POSSIBLE TO UNDERSIDE OF FLOOR DECK. DUCTS TO BE ROUTED BETWEEN STRUCTURAL MEMBERS WHEN RUNNING PARALLEL, AND RUN THRU OPEN WEB STEEL JOISTS WHEN RUNNING PERPENDICULAR TO STRUCTURAL MEMBERS. ONLY RUN DUCTS BELOW STRUCTURAL MEMBERS WHEN RUNNING PERPENDICULAR TO SOLID STRUCTURAL MEMBERS SUCH AS BEAMS, WHERE RUNNING THRU IS NOT AN OPTION. NOTE: THE ANTEROOM AND HAZARDOUS COMPOUNDING Queen Charlotte Pharmacy ROOM ARE TO BE PROVIDED WITH NEW LOCAL PRESSURE/HUMIDITY/TEMPERATURE SENSORS AND CONTROLS. WALL MOUNTED PRESSURE MONITORS TO BE QUEEN CHARLOTTE PHARMACY UPGRADE PROVIDED, REFER TO SPECIFICATIONS. INTEGRATE NEW CONTROLS SEQUENCE INTO EXISTING BMS AND PROVIDE UPDATE TO GRAPHICS AS REQUIRED. Title C DRAWING LIST, LEGEND, SCHEDULES, 1 CSA VENTILATION SCHEDULE AND HVAC CONTROLS Room: CSA Space Space Limit CSA Exhaust Specified CSA Minimum Supply Specified Exhaust Design GE Design WE Level Number Room: Name Classification Type Volume Area Offset CSA Pressurization Req. Supply Airflow Airflow (L/s) Airflow Airflow Airflow Project No. Scale LEVEL 1 115602082 As indicated AHU-2 LEVEL 1 1-926 ANTE ROOM NAPRA - HD Anteroom ISO 7 19.6 m³ 7.3 m² 2700 Pos All Air Exhausted 165 L/s 163 L/s 65 L/s 65 L/s 0 L/s Revision Drawing No. (Pb) To The Exterior LEVEL 1 - ENVIRONMENTAL CONTROLS 3/9/2021 1:38:31 PM LEVEL 1 1-927 HAZARDOUS NAPRA - HD Sterile ISO 7 17.8 m³ 6.6 m² 2700 Neg Pb-Pc = 2.5 Pa All Air Exhausted 200 L/s 148 L/s 250 L/s 250 L/s 0 L/s 1 COMPOUNDING ROOM Compounding Room (Pc) To The Exterior M001 1 : 50 M001 ORIGINAL SHEET - ARCH D (24"x36")
G F E D C B A NOTE: THESE DRAWINGS DO NOT SHOW THE SCOPE FOR THE NAPRA UPGRADES. REFER TO 200 SERIES DRAWINGS. Stantec Consulting Ltd. 1100-111 Dunsmuir Street Vancouver, V6B 6A3 Tel: (604) 696-8000 / Fax: (604) 696-8100 www.stantec.com 5 Copyright Reserved The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay. The Copyrights to all designs and drawings are the property of Stantec. Reproduction or use for any purpose other than that authorized by Stantec is forbidden. 4 1 STORES ROOM UPGRADE - KEY PLAN 2 STORES ROOM UPGRADE - DEMOLITION M101 1 : 200 M101 1 : 200 50 3 SEE DETAIL 4 M101 FOR CONTINUATION SEE DETAIL 3 M101 FOR CONTINUATION By Appd YYYY.MM.DD Revision ISSUED FOR TENDER NG DB 2021.05.03 ISSUED FOR 90% CLIENT REVIEW NG DB 2021.01.15 Issued By Appd YYYY.MM.DD 2 PRELIMINARY NOT FOR CONSTRUCTION Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only. Queen Charlotte Pharmacy QUEEN CHARLOTTE PHARMACY UPGRADE 3 STORES ROOM UPGRADE - HVAC - NEW WORK 4 STORES ROOM UPGRADE - HVAC - NEW WORK - CONT'D Title M101 1 : 200 50 M101 1 : 200 50 STORES ROOM UPGRADE - LEVEL 1 1 MECHANICAL Project No. Scale 115602082 1AS SHOWN : 200 Revision Drawing No. 3/9/2021 1:38:32 PM M101 ORIGINAL SHEET - ARCH D (24"x36")
G F E D C B A Stantec Consulting Ltd. 1100-111 Dunsmuir Street Vancouver, V6B 6A3 Tel: (604) 696-8000 / Fax: (604) 696-8100 www.stantec.com 5 Copyright Reserved The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay. The Copyrights to all designs and drawings are the property of Stantec. Reproduction or use for any purpose other than that authorized by Stantec is forbidden. TIE INTO NEW CHILLED WATER CONNECTIONS SHOWN ON NAPRA UPGRADE DWG. TIE INTO CAPPED CONNECTIONS. REFER TO M201. 4 NOTE THIS DRAWING DOES NOT SHOW THE WORK FOR THE NAPRA UPGRADE. REFER TO M201 FOR SCOPE. DEPENDING ON WHICH SCOPE IS TO BE COMPLETED FIRST, PROVIDE 32mm MAIN CONNECTION AND CAPS FOR EITHER THE NAPRA UPGRADE OR FOR THIS PROJECT SCOPE. DRAWING M201 SHOWS THE MAINS AND TIE IN POINT. 1 STORES ROOM UPGRADE - HYDRONICS - NEW WORK M102 1 : 200 50 3 By Appd YYYY.MM.DD Revision ISSUED FOR TENDER NG DB 2021.05.03 ISSUED FOR 90% CLIENT REVIEW NG DB 2021.01.15 Issued By Appd YYYY.MM.DD 2 PRELIMINARY NOT FOR CONSTRUCTION Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only. Queen Charlotte Pharmacy QUEEN CHARLOTTE PHARMACY UPGRADE Title STORES ROOM UPGRADE - LEVEL 1 - 1 MECHANICAL 2 STORES ROOM UPGRADE - SCHEDULES M102 1N.T.S. : 200 Project No. Scale 115602082 AS SHOWN 1 : 200 Revision Drawing No. 3/9/2021 1:38:32 PM M102 ORIGINAL SHEET - ARCH D (24"x36")
G F E D C B A 2 3 2 3 Stantec Consulting Ltd. 1100-111 Dunsmuir Street Vancouver, V6B 6A3 Tel: (604) 696-8000 / Fax: (604) 696-8100 5 B B www.stantec.com Copyright Reserved The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay. The Copyrights to all designs and drawings are the property of Stantec. Reproduction or use for any purpose other than that EXACT CONNECTION POINT authorized by Stantec is forbidden. CAP DUCTWORK FOR TO BE DETERMINED ON SITE. RECONNECTION PROVIDE NEW CONTROLLER EXISTING LAMINAR FLOW EXHAUST DUCT UP FOR EXISTING AIR VALVE AND DIFFUSERS IN ANTE ROOM THROUGH EXISTING SHAFT. INTEGRATE WITH NEW AND HD COMPOUNDING CONFIRM EXACT ROUTING PHARMACY CONTROL ROOM TO BE REMOVED ON SITE. E-1 SEQUENCE. 200x200 TS 25 200x100 EA(SS) 300ø SA E-1 200x200 25 L-1 L-1 300ø 300ø TS 165 200 300ø TS TS 250ø SA 4 200x100 E-1 200x200 65 200x100 EA(SS) 250ø EA(SS) CAP DUCT VAV-114B VAV-113C PERMANENTLY CC-113B VAV-113B 200ø 200ø 250ø EA(SS) C C DUCTWORK COOLING COIL. PROVIDE DRIP PAN AND DRAIN TO NEAREST SINK P-TRAP OR TO HOUSEKEEPING MOP SINK. ROUTING TO FOLLOW EXISTING COOLING COIL DRAINAGE. 3 1 LEVEL 1 - DEMOLITION 2 LEVEL 1 - NEW WORK M201 1 : 50 M201 1 : 50 By Appd YYYY.MM.DD GENERAL DEMOLITION AND NEW WORK NOTES: Revision 2 3 1. ALLOW FOR REMOVING AND RELOCATION OF EXISTING SERVICES TO PROVIDE SPACE FOR NEW SERVICES. ALL DUCTWORK AND PIPING RUNS TO BE COORDINATED WITH SERVICES ON SITE. 2. MODIFY NEW VAV AND COIL TAG NUMBERS TO CONTINUE FROM EXISTING NUMBERING SCHEME. ISSUED FOR TENDER NG DB 2021.05.03 3. OPEN UP CEILING AS REQUIRED TO PERMIT DEMOLITION WORK. NOTE THAT EXISTING ISSUED FOR 90% CLIENT REVIEW NG DB 2021.01.15 CEILING WITHIN THE PHARMACY ROOMS ARE DRYWALL (1-926 AND 1-927). Issued By Appd YYYY.MM.DD 4. MAKE GOOD EXISTING CEILINGS AT COMPLETION OF WORK 2 5. COORDINATE ANY REQUIRED SHUTDOWNS WITH OWNER. ASSUME ANY WORK OUTSIDE OF THE MAIN RENOVATION AREA TO BE COMPLETED AFTER HOURS/OVERNIGHT. COORDINATE WORK INSIDE THE RENOVATION AREA WITH OWNER. 32 CHWR 6. ALL EQUIPMENT TO BE SEISMICALLY SECURED - REFER TO SPECIFICATIONS. 32 CHWS PRELIMINARY TS 7. ALL SERVICE PENETRATIONS THROUGH EXISTING PHARMACY WALLS TO BE CAULKED/OTHERWISE SEALED TO MAINTAIN PRESSURIZATION OF THE SPACE. FOR LINE SIZE VALVE AND CAP FOR FUTURE NOT FOR CONSTRUCTION EXISTING SERVICES BEING DEMOLISHED, PENETRATIONS TO BE PATCHED/SEALED. Not for permits, pricing or other official purposes. CONNECT TO EXISTING 8. AHU S-2 SUPPLY FAN TO BE REBALANCED TO SUIT THE ADDITIONAL 140 L/s REQUIRED FOR 32mm CHILLED WATER LINE. This document has not been completed or checked and THE ANTEROOM AND HEPA DIFFUSERS. COORDINATE SHUTDOWN is for general information or comment only. WITH OWNER AND ASSUME 9. LOW LEVEL EXHAUSTS TO BE MOUNTED 300mm AFF. TIE IN TO OCCUR AFTER HOURS. ASSUME FREEZING 10. EXHAUST DUCTWORK TO BE OF STAINLESS STEEL CONSTRUCTION. TS WILL BE REQUIRED FOR TIE IN TO MINIMIZE IMPACT TO TS TS ADJACENT SPACES. GRILLE, REGISTER, DIFFUSER SCHEDULE NOTE: CC-113B 20 CHWS / CHWR 20 CHWR CONNECTIONS FOR STORES Queen Charlotte Pharmacy NOTES: UPGRADE. REFER TO M201. 1. REFER TO REFLECTED CEILING PLANS EXACT LOCATION. PROVIDE ALL FRAMES AND ACCESSORIES AS REQUIRED FOR PROPER INSTALLATION. 20 CHWS 20mm - 0.063 L/s 2. COLOR TO BE SELECTED BY ARCHITECT FROM STANDARD COLORS. 3. STAINLESS STEEL LAMINAR FLOW NON-ASPIRATING DIFFUSER WITH HEPA FILTER, INLET DIFFUSION BRACKET, STATIC PRESSURE PORT, PRESSURE SWITCH QUEEN CHARLOTTE PHARMACY UPGRADE C/W BUILDING AUTOMATION SYSTEM INTERFACE FOR FILTER STATUS, BALANCING DAMPER ACCESSIBLE FROM DIFFUSER FACE. 4. PROVIDE S.S. DAMPER FOR LOW LEVEL EXHAUST GRILLES. 5. EXCEPT FOR T-BAR INSTALLATION, GRILLES SHALL BE COMPLETE WITH MOUNTING FRAME TYPE D AND 1/4 TURN QUICK RELEASE FASTENERS. Title 6. STAINLESS STEEL LOUVERED RETURN/EXHAUST GRILLE, 45 DEGREE DEFLECTION, 19MM BLADE SPACING. NAPRA UPGRADE - LEVEL 1 - 1 MARK DIFFUSER NECK SIZE (IN) MATERIAL MANUFACTURER MODEL NUMBER NOTES MECHANICAL E-1 200x200 STAINLESS STEEL PRICE 730 RETURN 1,2,4-6 L-1 300ø STAINLESS STEEL PRICE LFDC 1,2,3 Project No. Scale 115602082 1 : 50 Revision Drawing No. LEVEL 1 - PIPING - NEW WORK 3/9/2021 1:38:35 PM 3 M201 1 : 50 M201 ORIGINAL SHEET - ARCH D (24"x36")
G F E D C B A 3 4 Stantec Consulting Ltd. 3 4 1100-111 Dunsmuir Street Vancouver, V6B 6A3 Tel: (604) 696-8000 / Fax: (604) 696-8100 www.stantec.com 5 FD Copyright Reserved The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay. B A 3 _______ M202 The Copyrights to all designs and drawings are the property of Stantec. Reproduction or use for any purpose other than that authorized by Stantec is forbidden. 200mm EXHAUST DUCT UP TO 3M 250ø ABOVE HIGHEST POINT ON ROOF TO MATCH EXISTING STACKS. TIE INTO EXISTING SUPPORT STRUCTURE FOR DUCT. PATCH/SEAL AROUND OPENING AND MAKE WATER TIGHT AS REQUIRED. PROVIDE NOZZLE EXIST TO REACH 3000FPM MINIMUM (APPROX 100mm EXIT) EF-PHARM-1 FD NOTE: DUCT RUN IS IN ACTIVE 3 _______ HOSPITAL SPACE. WORK IN M202 ROUND ELBOW SILENCER EF- 250ø EA(SS) CLINICAL AREAS OUTSIDE OF THE PHARM-1-SIL-1 RENOVATION AREA TO BE ASSUMED TO OCCUR AFTER NEW EXHAUST FAN ON 100mm HOURS. COORDINATE WITH HOUSEKEEPING PAD (REFER TO OWNER. EXACT ROUTING TO BE ARCH FOR HOUSEKEEPING PAD COORDINATED WITH EXISTING DETAIL).. MOUNT VFD IN LOCATION 4 SERVICES ON SITE. WITH ADEQUATE CLEARANCE (1M). PROVIDE UNISTRUT FOR OPEN UP SHAFT TO MOUNTING VSD. CONFIRM EXACT PERMIT DUCTWORK LOCATION ON SITE. INSTALLATION. CONFIRM EXACT RUN PROVIDE OPENINGS AS LOCATION ON SITE. REQUIRED TO RUN PROVIDE FIRE DUCTWORK AS SHOWN. DAMPER AT SHAFT NOTE - THIS DUCTWORK PROVIDE FIRE DAMPER AT EXIT. RUN IS IN LEVEL 2 PENETRATION INTO CEILING (TYP.) MECHANICAL SPACE. RUN DUCT WITHIN THE MECHANICAL SPACE AT HIGH LEVEL TO MAINTAIN ACCESS CLEARANCE. 250ø EA(SS) B C 3 DUCT UP FROM BELOW 1 LEVEL 2 - NEW WORK M202 1 : 50 FD A By Appd YYYY.MM.DD Revision SIZE NOZZLE TO MAINTAIN 3000FPM EXIT VELOCITY PER ASHRAE (APPROX 100MM) EXISTING EXHAUSTS IN THIS AREA. ISSUED FOR TENDER NG DB 2021.05.03 ISSUED FOR 90% CLIENT REVIEW NG DB 2021.01.15 3000 Issued By Appd YYYY.MM.DD 2 C TOP OF ROOF 15300 PRELIMINARY PROVIDE WEATHERPROOF NOT FOR CONSTRUCTION DUCT PENETRATION THROUGH ROOF. Not for permits, pricing or other official purposes. S.S. DUCT STACK This document has not been completed or checked and is for general information or comment only. 200ø EA(SS) NEW EXHAUST STACK. SUPPORT FROM EXISTING SUPPORT STRUCTURE. SUPPORT HORIZONTAL RUNS AS REQUIRED IN PENTHOUSE Queen Charlotte Pharmacy QUEEN CHARLOTTE PHARMACY UPGRADE PROVIDE LOW POINT DRAIN AT BOTTOM OF STACK. ROUTE TO NEAREST DRAIN TO MATCH OTHER STACKS Title ON SITE. NAPRA UPGRADE - LEVEL 2/3 - 1 EF-PHARM-1 NEW EXHAUST FAN ON 2 LEVEL 3 - PENTHOUSE - NEW WORK MECHANICAL - NEW WORK 100mm HOUSEKEEPING PAD. M202 1 : 50 CONFIRM EXACT LOCATION OF FAN ON SITE. Project No. Scale 115602082 1 : 50 LEVEL 3 - PENTHOUSE 9000 Revision Drawing No. 3/9/2021 1:38:37 PM EXHAUST FAN SECTION 3 M202 1 : 50 M202 ORIGINAL SHEET - ARCH D (24"x36")
G F E D C B A SILENCER SCHEDULE UNIT IDENTIFICATION AIRFLOW INFORMATION DYNAMIC INSERTION LOSSES DB OPERATING DEVICE CONNECTION DIMENSIONS CASING DIMENSIONS MODEL AIRFLOW VELOCITY WEIGHT MANUFACTURER NOTES TAG APD CASING GAUGE PERF Media ROUND HEIGHT WIDTH LENGTH 63 125 250 500 1K 2K 4K 8K NUMBER (L/S) (M/S) (KG) (PA) (mm) (mm) (mm) (mm) Stantec Consulting Ltd. EF-PHARM-1-SIL 150 10 3.0 24 GA 304 SS 26 GA 304 SS NONE 250 762 762 2184 (CL) 29 18 43 26 20 19 15 12 - PRICE PECMB86/10 1 1100-111 Dunsmuir Street Vancouver, V6B 6A3 NOTES: Tel: (604) 696-8000 / Fax: (604) 696-8100 1. ROUND ELBOW SILENCER C/W 2" SLIP, EXTENDED WIDTH CASING www.stantec.com 5 Copyright Reserved The Contractor shall verify and be responsible for all dimensions. FAN SCHEDULE DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay. UNIT IDENTIFICATION FAN WHEEL FAN MOTOR (EACH FAN) ELECTRICAL The Copyrights to all designs and drawings are the property of Stantec. Reproduction or use for any purpose other than that MAX NOISE OPERATING ESP authorized by Stantec is forbidden. ASSET AIRFLOW CONTROL SPEED SPEED DRIVE LEVEL WEIGHT MANUFACTURER MODEL NUMBER NOTES MARK SYSTEM (Pa) TYPE BHP HP VOLTS PHASE NUMBER (l/s) (RPM) (RPM) TYPE (dBA) (kg) EF-PHARM-1 HAZARDOUS COMPOUNDING ROOM EXHAUST 150 750 VFD SINGLE WIDTH CENT. BLOWER 3,126 0.67 0.75 3,600 BELT 208 3 73 70 GREENHECK USF-06 ALL NOTES: 1. NEMA PREMIUM EFFICIENT MOTOR, INVERTER DUTY, TEFC, CLASS B OR GREATER INSULATION, CSA APPROVED, SHAFT GROUNDING, 120K HOUR BEARINGS, FACTORY VIBRATION TESTED, MOTOR COVER. 2. VFD MOUNTED AND WIRED 3. HI-PRO POLYESTER COATING AIR VALVE SCHEDULE (AV) COOLING COIL OCCUPIED MODE UNOCCUPIED MODE AIR VALVE No. ASSET NUMBER MANUFACTURER MODEL SIZE BODY CONST'N COOLING. CAP. MIN. MAX. MIN. NOTES ROWS FLOW (L/s) MAX. (L/s) (kW) (L/s) (L/s) (L/s) ANTEC ALUMINUM/COATED VAV-114B PRICE 8 100 50 100 50 1,2,5,6 CONTROLS STAINLESS 4 ANTEC ALUMINUM/COATED VAV-113C PRICE 8 100 65 100 65 1,2,5,6 DUCT CONNECTIONS TO AIR TERMINAL CONTROLS STAINLESS ANTEC ALUMINUM/COATED VAV-113B PRICE 10 2 0.064 0.75 150 150 150 150 1,2,3,4,5,6 1 UNITS CONTROLS STAINLESS M203 N.T.S. E-VAV-114 EXISTING 10 EXISTING 200 200 200 200 1,2,3 NOTES: 1. AIR VALVES TO BE SUPPLIED WITH AIR PRESSURE MONITORS AND COMPONENTS IN DESIGNATED LOCATIONS AS NOTED ON THE PLANS. PRESSURE MONITOR +/- 1%. 2. EACH AIR VALVE TO BE PROVIDED WITH AN ON-BOARD FACTORY INSTALLED CONTROLLER, COMPLETE WITH PROGRAMMING FOR ROOM LEVEL PRESSURE CONTROL (POC). 3. FACTORY CONTROLLERS TO PROVIDE ROOM-LEVEL HUMIDITY AND TEMPERATURE CONTROL. 4. AIR VALVES TO BE SUPPLIED WITH DUCT MOUNTED COOLING COILS, PERFORMANCE AS FOLLOWS: EWT:10C, LWT:16C, EAT: 18/14.6C DB/WB, LAT: 14/12.3C DB/WB 5. AIR VALVES TO BE SUPPLIED WITH ATTENUATORS. 6. PROVIDE LOW PRESSURE MODELS, 0.3" W.G. (75PA) 7. NOTE: MINIMUM AIRFLOWS ARE TO BE USED FOR BALANCING IN CONJUNCTION WITH THE VALUES ON THE DRAWINGS. THE VALVE CAN OPERATE UP TO THE MAXIMUM IF REQUIRED TO MAINTAIN SPACE PRESSURE DIFFERENTIALS. 3 PIPE OR DUCT NOTE: THE DETAILS ON THIS SHEET ARE TO BE USED FOR BOTH THE STORES FLASHING UPGRADE AND NAPRA UPGRADES PROJECTS AS APPLICABLE FIBERGLASS BUILDING Revision By Appd YYYY.MM.DD INSULATION 0.75 PCF DENSITY ACOUSTICAL SEALANT 2 DUCT MOUNTED COOLING COIL INSTALLATION DETAIL 25 GA. (MIN.) METAL SLEEVE M203 N.T.S. (ROOF JACK) ISSUED FOR TENDER NG DB 2021.05.03 ISSUED FOR 90% CLIENT REVIEW NG DB 2021.01.15 Issued By Appd YYYY.MM.DD SHEET 2 METAL 2 LOAD RATED FASTENER (TYP) DUCT PRELIMINARY NOT FOR CONSTRUCTION ROOF CONSTRUCTION Not for permits, pricing or other official purposes. This document has not been completed or checked and is for general information or comment only. 25mm (TYP.) 1 R=1.5D SEISMIC CABLELLING AS Queen Charlotte Pharmacy REQUIRED CL NOTES: QUEEN CHARLOTTE PHARMACY UPGRADE 1. PROVIDE PITCH POCKET CONSTRUCTION, ADDITIONAL FLASHING OR WEATHER CAP AS REQUIRED FOR WATERPROOF CONSTRUCTION. DO NOT RIGIDLY TIE DUCT OR PIPE TO STRUCTURE IN ANY WAY. 2. SPACE BETWEEN DUCT OR PIPE AND METAL SLEEVE SHALL BE FREE OF ANY FOREIGN MATERIALS. Title 3. DUCT OR PIPE SHALL NOT DIRECTLY CONTACT STRUCTURE. WEDGES SHALL NOT BE USED TO MAINTAIN PIPE IN POSITION. NAPRA UPGRADE - HVAC SCHEDULES 1 4. DUCT OR PIPE MUST BE APPROX. CENTERED ON OPENING. PROVIDE ADDITIONAL CLEARANCE FOR POSITIONAL CHANGE OF DUCT AND DETAILS DUE TO LOADING OF DUCT OR OPERATION OF SYSTEM. KEY NOTES: Project No. Scale 5. NEW PIPE TO BE CENTERED BETWEEN STANDING SEAMS ON METAL ROOF. 1 FLEXIBLE DUCT MAXIMUM LENGTH SHALL BE 1'-0". PROVIDE HARD DUCT ELBOW - 115602082 NTS USE OF FLEX IS ONLY PERMITTED FOR THE FINAL STRAIGHT LENGTH. Revision Drawing No. 2 MAXIMUM ALLOWABLE SAG SHALL NOT EXCEED d" PER LINEAR FOOT. 3/9/2021 1:38:39 PM 3 M203 VAV TERMINAL UNIT INSTALLATION DETAIL N.T.S. M203 4 LAMINAR FLOW SUPPLY DIFFUSER NTS M203 5 TYPICAL WATERPROOFED PIPE-DUCT PENETRATION DETAIL - PITCHED ROOF NTS M203 ORIGINAL SHEET - ARCH D (24"x36")
G F E D C B A GENERAL NOTES Stantec 1. Staniec Consulting ltd. ALLOW FOR REM
G F E D C B A 4 5 Stantec ' "'" Staniec Consulting ltd. I I�- , II I I L...___JJ --� I