Installation, Start−Up, and Service Instructions CAS SERIES SPLIT SYSTEM 3 PHASE 6 to 12.5 TON AC CONDENSERS Save This Manual for Future Reference 501 01 3001 00 04/24/09
Installation Instructions Split System Condensers TABLE OF CONTENTS ! WARNING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PAGE SAFE INSTALLATION REQUIREMENTS . . . . . . . . . . . . . 2 ELECTRICAL SHOCK HAZARD INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Failure to follow this warning could result in personal in- Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 jury or death. Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Before performing service or maintenance operations Unit Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 on unit, always turn off main power switch to unit and in- Refrigerant Piping Connections . . . . . . . . . . . . . . . . . . . . 7 stall lockout tag. Unit may have more than one power Installing Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 switch. Typical Thermostat Connections . . . . . . . . . . . . . . . . . . 12 System Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Start−Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Charging Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 ! WARNING Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Operating Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 UNIT OPERATION AND SAFETY HAZARD System Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Failure to follow this warning could cause personal in- LED Status Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 jury, death and/or equipment damage. Cleaning and Maintenance . . . . . . . . . . . . . . . . . . . . . . . 21 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 R−410A systems operate at higher pressures than R−22 Start−Up Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 systems. When working with R−410A systems, use only service equipment and replacement components specif- SAFETY CONSIDERATIONS ically rated or approved for R−410A service. Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, ! WARNING personal injury, or property damage. Consult a qualified PERSONAL INJURY AND ENVIRONMENTAL installer, service agency, or your distributor or branch for HAZARD information or assistance. The qualified installer or agency must use factory−authorized kits or accessories Failure to follow this warning could cause personal injury when modifying this product. Refer to the individual or death. instructions packaged with the kits or accessories when Relieve pressure and recover all refrigerant before sys- installing. tem repair or final unit disposal. Follow all safety codes. Wear safety glasses, protective Wear safety glasses and gloves when handling refriger- clothing, and work gloves. Use quenching cloth for ants. brazing operations. Have fire extinguisher available. Keep torches and other ignition sources away from refri- Read these instructions thoroughly and follow all gerants and oils. warnings or cautions included in literature and attached to the unit. Consult local building codes, the current editions of the National Electrical Code (NEC) NFPA 70. ! CAUTION In Canada refer to the current editions of the Canadian CUT HAZARD Electrical Code CSA C22.1 Recognize safety Failure to follow this caution may result in personal injury. information. Recognize safety information. This is the Sheet metal parts may have sharp edges or burrs. Use safety−alert symbol ! When you see this symbol on the care and war appropriate protective clothing, safety unit and in instructions or manuals, be alert to the glasses and gloves when handling parts and servicing potential for personal injury. Understand these signal units. words; DANGER, WARNING, and CAUTION. These words are used with the safety−alert symbol. DANGER identifies the most serious hazards which will result in ! CAUTION severe personal injury or death. WARNING signifies CUT HAZARD hazards which could result in personal injury or death. Failure to follow this caution may cause equipment dam- CAUTION is used to identify unsafe practices which may age. result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which Ensure voltage listed on unit data plate agrees with elec- will result in enhanced installation, reliability, or trical supply provided for the unit. operation. 2 501 01 3001 00
Split System Condensers Installation Instructions MODEL NOMENCLATURE MODEL SERIES C A S 0 9 1 H A G 0 A 0 0 A Position Number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 C = R-410A Condensing Unit A = Air Conditioning (Cooling Only) H = Heat Pump Type S = Standard ASHRAE 90.1-2010 Efficiency Efficiency 072 = 6 Tons 091 = 7.5 Tons (1 circuit) 121 = 10 Tons (1 circuit) 151 = 12.5 Tons (1 circuit) Nominal Cooling Capacity H = 208/230-3-60 L = 460/208/230-3-60 S = 575-3-50 VOLTAGE A = Single Circuit B = Single Circuit w/ Low Ambient Control Refrigerant System Options G = Al/Al Standard (AC only) K = Al/Al E-Coat (AC only) Outdoor Coil Options 0 = None 1 = UnPowered C.O. Service Options A = None C = Non-Fused Disconnect Electrical Options 0 = Elec-Mechanical Standard Base Unit Controls 0 = Future Use Future Use A = Standard Packaging Packaging Installation Guideline Installation Replacement /Retrofit – R22 to R−410A 1. Remove the existing evaporator coil or fan coil and install the replacement coil when appropriate. Replacement/retrofit installations require change−out of outdoor unit, metering device, and filter driers. Change−out 2. Drain oil from low points and traps in suction line of indoor coil (evaporator) and interconnecting tubing is tubing and hot gas bypass tubing if appropriate) and recommended. evaporator if they were not replaced. Removing oil from evaporator coil may require purging of the Existing evaporator coil – If the existing evaporator coil may tubing with dry nitrogen. be re−used, check with the coil manufacturer to verify the 3. Unless indoor unit is equipped with a R−410A coil construction is suitable for operation with the higher approved metering device, change the metering pressures of R−410A. Also determine if the existing TXV device to a thermal expansion valve (TXV) designed valve is compatible with R−410A, replace if necessary. The for R−410A. minimum factory test pressure rating must be 250 psig (1725 kPa). Existing coil will need to be purged with 4. Remove the existing outdoor unit. Install the new Nitrogen to remove as much mineral oil as possible to outdoor unit according to these installation instructions. eliminate cross contamination of oil. 5. Install a new field−supplied liquid−line filter drier at Acid test – If the existing system is being replaced because the indoor coil just upstream of the TXV or fix orifice of a compressor electrical failure, assume acid is in system. metering device. If system is being replaced for any other reason, use an approved acid test kit to determine acid level. If even low 6. If a suction line filter drier is also to be installed, levels of acid are detected, install a 100 percent activated install suction line drier downstream of suction line service valve at condensing unit. alumina suction−line filter drier in addition to the replacement liquid−line filter drier. Remove the suction line 7. If required, install a 100% activated alumina suction filter drier as soon as possible, with a maximum of 72 hours line filter drier at the outdoor unit. of operation. Recommendation: Install a ball valve in the 8. Evacuate and charge the system according to the liquid line at the filter drier location when installing a suction instructions in this installation manual. filter in the suction line. 501 01 3001 00 3
Installation Instructions Split System Condensers 9. Operate the system for 10 hours. Monitor the NOTE: Do not use a torch to remove filter driers, use tubing pressure drop across the suction line filter drier. If cutters. Excess heat from the torch will drive the moisture pressure drop exceeds 3 psig (21kPa), replace contained within the drier back out into the system. suction−line and liquid−line filter driers. Be sure to purge system with dry nitrogen and evacuate when replacing filter driers. Continue to monitor the pressure drop across suction−line filter drier. Repeat filter changes is necessary. Never leave suction−line filter drier in system longer than 72 hr (actual time). Figure 1 Unit Dimensions CAS151 CAS072 CAS091 CAS121 CAS151 DISCONNECT LOCATION Standard Weight Corner A Corner B Corner C Corner D Center of Gravity Unit Height UNIT lbs. kg. lbs. kg. lbs. kg. lbs. kg. lbs. kg. X Y Z H 19.00 21.00 12.71 072 328 149 128 58 70 32 62 28 68 31 42.36 (1076.0) (482.6) (533.4) (322.8) 22.50 18.50 12.71 091 353 160 138 63 78 35 65 29 72 33 42.36 (1076.0) (571.5) (469.9) (322.8) 19.50 23.00 15.11 121 418 190 165 75 90 41 78 35 85 39 50.36 (1279.2) (495.3) (584.2) (383.3) 23.00 19.25 15.11 151 431 196 162 73 95 43 92 42 82 37 50.6 (1279.2) (584.2) (489.0) (383.3) 4 501 01 3001 00
Split System Condensers Installation Instructions Table 1A Physical Data — 60 Hz English UNIT CAS 072 091 121 151 NOMINAL CAPACITY (tons) 6 7.5 10 12.5 OPERATING WEIGHT (lb) Aluminum−Fin Coils (Standard) 328 353 418 431 REFRIGERANT TYPE * R−410A Operating Charge, Typical (lb){ 8.4 10.2 13.8 18.0 Shipping Charge (lb) 4.4 4.9 6.3 7.3 COMPRESSOR Scroll Qty... Model 1...ZP61 1...ZP83 1...ZP103 1...ZP137 Oil Charge (oz) 56 60 110 110 No. refrigerant circuits 1 Speed (rpm) 3500 CONDENSER FANS Qty...Rpm 2...1100 Motor Hp 1/4 Diameter 22 Nominal Airflow (CFM Total) 6000 Watts (Total) 610 CONDENSER COIL (Qty) 1... Alum Tu/Alum Fin Micro−channel Face Area (sq ft total) 17.5 20.5 25.0 31.8 Rows/Fins per inch (FPI) 1/17 1/17 1/17 1/17 Storage Capacity (lb) ** 5.5 6.0 7.4 8.7 CONTROLS Pressurestat Settings (psig) High Cut−out 630 10 Cut−in 505 20 Low Cut−out 54 3 Cut−in 117 5 PIPING CONNECTIONS (in. ODS) Qty...Suction 1...1 1/8 1...1 1/8 1...1 3/8 1...1 3/8 Qty... Liquid 1... 3/8 1... 1/2 1... 1/2 1... 5/8 LEGEND * Unit is factory−supplied with partial charge only. ODS — Outside Diameter Sweat (socket) † Typical operating charge with 25 ft of interconnecting piping. ** Storage capacity of condenser coil with coil 80% full of liquid R−410A at 95_F. 501 01 3001 00 5
Installation Instructions Split System Condensers Table 1B Physical Data — 60 Hz SI UNIT CAS 072 091 121 151 NOMINAL CAPACITY (kW) 21.1 26.4 35.1 44 OPERATING WEIGHT (kg) Aluminum−Fin Coils (Standard) 149 160 190 196 REFRIGERANT TYPE * R−410A Operating Charge, Typical (kg){ 3.8 4.6 6.3 8.2 Shipping Charge (kg) 2.0 2.2 2.9 3.3 COMPRESSOR Scroll Qty... Model 1...ZP61 1...ZP83 1...ZP103 1...ZP137 Oil Charge (L) 1.7 1.8 3.3 3.3 No. refrigerant circuits 1 Speed (r/s) 58 CONDENSER FANS Qty...Rpm 2...18 Motor Hp NEMA 1/4 Diameter (mm) 560 Nominal Airflow (L/s) 2832 Watts (Total) 610 CONDENSER COIL (Qty) 1... Alum Tu/Alum Fin Micro−channel Face Area (sq m total) 1.6 1.9 2.3 3.0 Rows/Fins per inch (Fins/m) 1...670 1...670 1...670 1...670 Storage Capacity (kg) ** 2.5 2.7 3.4 3.9 CONTROLS Pressurestat Settings (kPa) High Cut−out 4347 70 Cut−in 3482 138 Low Cut−out 372 21 Cut−in 807 34 PIPING CONNECTIONS (in. ODS) Qty...Suction 1...1 1/8 1...1 1/8 1...1 3/8 1...1 3/8 Qty... Liquid 1...3/8 1... 1/2 1... 1/2 1... 5/8 LEGEND * Unit is factory−supplied with partial charge only. NEMA — National Electrical Manufacturers Association † Typical operating charge with 7.62 m of interconnecting piping. ODS — Outside Diameter Sweat (socket) ** Storage capacity of condenser coil with coil 80% full of liquid R−410A at 35_C. Jobsite Survey combustible surfaces, unit performance and service access below, around and above unit as specified in unit Complete the following checks before installation. drawings. See Figure 2. 1. Consult local building codes and the NEC (National NOTE: Consider also the effect of adjacent units on airflow Electrical Code) ANSI/NFPA 70 for special installation requirements. performance and control box safety clearance. 2. Determine unit location (from project plans) or select Do not install the outdoor unit in an area where fresh air unit location. supply to the outdoor coil may be restricted or when recirculation from the condenser fan discharge is possible. 3. Check for possible overhead obstructions which may interfere with unit lifting or rigging. Do not locate the unit in a well or next to high walls. Evaluate the path and required line length for Step 1 — Plan for Unit Location interconnecting refrigeration piping, including suction riser Select a location for the unit and its support system (pad, requirements (outdoor unit above indoor unit), liquid line lift rails or other) that provides for the minimum clearances (outdoor unit below indoor unit) and hot gas bypass line. required for safety. This includes the clearance to 6 501 01 3001 00
Split System Condensers Installation Instructions Relocate sections to minimize the length of interconnecting front of condenser coil air inlet to prevent grass and foliage tubing. from obstructing airflow. Step 4 − Rig and Mount the Unit ! CAUTION UNIT OPERATION HAZARD ! CAUTION Failure to follow this caution may result in improper UNIT OPERATION HAZARD operation. Failure to follow this caution may result in equipment Do not bury refrigerant piping underground. damage. Although unit is weatherproof, avoid locations that permit All panels must be in place when rigging. Unit is not water from higher level runoff and overhangs to fall onto the designed for handling by fork truck. unit. RIGGING — These units are designed for overhead rigging. Refer to the rigging label for preferred rigging Figure 2 Service Clearance Dimensional Drawing method. Spreader bars are not required if top crating is left on the unit. All panels must be in place when rigging. As further protection for coil faces, plywood sheets may be RIGHT: placed against the sides of the unit, behind cables. Run REAR: Min 18” (457 mm) required for service cables to a central suspension point so that the angle from Min 18” (457 mm) required for service the horizontal is not less than 45 degrees. Raise and set the unit down carefully. LEFT: If it is necessary to roll the unit into position, mount the unit Min 18” (457 mm) required for service FRONT: on longitudinal rails, using a minimum of 3 rollers. Apply 42” (1067 mm) force to the rails, not the unit. If the unit is to be skidded into position, place it on a large pad and drag it by the pad. Do Note: Observe requirements for 39” (914 mm) operating clearance not apply any force to the unit. on either Left or Rear coil opening. Raise from above to lift the unit from the rails or pad when Step 2 — Complete Pre−Installation Checks unit is in its final position. CHECK UNIT ELECTRICAL CHARACTERISTIC — After the unit is in position, remove all shipping materials Confirm before installation of unit that voltage, amperage and top crating. and circuit protection requirements listed on unit data plate Step 5 — Complete Refrigerant Piping agree with power supply provided. Connections UNCRATE UNIT — Remove unit packaging except for the top skid assembly, which should be left in place until after the unit is rigged into its final location. ! CAUTION INSPECT SHIPMENT — File a claim with shipping UNIT OPERATION HAZARD company if the shipment is damaged or incomplete. Failure to follow this caution may result in improper CONSIDER SYSTEM REQUIREMENTS operation. S Consult local building codes and National Electrical Do not bury refrigerant piping underground. Code (NEC, U.S.A.) for special installation requirements. S Allow sufficient space for airflow clearance, wiring, ! CAUTION refrigerant piping, and servicing unit. See Figure 1 UNIT OPERATION HAZARD for unit dimensions and weight distribution data. Failure to follow this caution may result in improper S Locate the unit so that the outdoor coil (condenser) operation. airflow is unrestricted on all sides and above. S The unit may be mounted on a level pad directly on A refrigerant receiver is not provided with the unit. Do not the base channels or mounted on raised pads at install a receiver. support points. See Tables 1A and 1B for unit PROVIDE SAFETY RELIEF — The unit is provided with a operating weights. See Figure 1 for weight fusible joint in the suction line in accordance with applicable distribution based on recommended support points. UL standards for pressure relief. If local codes dictate an NOTE: If vibration isolators are required for a particular additional safety relief device, purchase locally and install installation, use the data in Figure 1 to make the proper locally. Installation will require the recovery of the factory selection. shipping charge before the factory tubing can be cut and Step 3 — Prepare Unit Mounting Support the supplemental relief device is installed. Slab Mount — SIZE REFRIGERANT LINES — Consider the linear length (actual tubing length) of piping required between the Provide a level concrete slab that extends a minimum of 6 outdoor unit and indoor unit (evaporator), the amount of in. (150 mm) beyond unit cabinet. Install a gravel apron in liquid lift (indoor section installed above the outdoor 501 01 3001 00 7
Installation Instructions Split System Condensers section), and compressor oil return. Consider and identify 121 1/ 2 13/8 1/ 2 13/8 1/ 2 13/8 1/ 2 13/8 also the arrangement of the tubing path (quantity and type 1/ of elbows in both lines), liquid line solenoid size, filter drier 151 2 13/8 1/ 2 13/8 1/ 2 13/8 1/ 2 13/8 and any other refrigeration specialties located in the liquid LEGEND line. Refer to the indoor unit installation instructions for L — Liquid Line additional details. S — Suction Line Determine equivalent line (linear length plus equivalent *Field−supplied suction accumulator required for pipe length length of elbows) length adjustments for path and 75−100 ft (23−30 m). components and add to linear line lengths. See Table 2 and NOTES: Table 3. Refer to the indoor unit installation instructions for 1. Pipe sizes are based on a 2_F (1_C) saturated additional information temperature loss for liquid and suction lines. Suction line sizing – Select a tube size that produces a 2. Pipe sizes are based on the maximum linear length, suction pressure drop in range of 1.5 to 3.0_F (0.8 to shown for each column, plus a 50% allowance for 1.7_C). (Higher pressure drops are permissible but there fittings. will be a loss in cooling capacity due to the higher pressure 3. Charge unit with R−410A and verify that subcooled drop.) Insulate the suction line. liquid exists at TXV by checking for a full liquid line Liquid line sizing – For linear line lengths up to 50−ft (15 m), sight glass or by calculating subcooling at TXV. select a tube size that produces a liquid pressure drop of INSTALL FILTER DRIER(S) AND MOISTURE approximately 2_F (1.1_C). For linear line lengths greater INDICATOR(S) — Every unit should have a filter drier and than 50−ft (15 m), select a line size that will permit the liquid a liquid−moisture indicator (sight glass). Refer to Table 4. state−point subcooling entering the indoor coil’s TXV to be In some applications, depending on space and a minimum of 2_F (1.1_C). convenience requirements, it may be desirable to install 2 filter driers and sight glasses. One filter drier and sight Note that refrigerant suction piping should be insulated. glass may be installed at A locations in Figure 3; or, 2 filter ! CAUTION driers and sight glasses may be installed at B locations. Select the filter drier for maximum unit capacity and minimum pressure drop. Complete the refrigerant piping UNIT OPERATION HAZARD from the indoor unit to the outdoor unit before opening the Failure to follow this caution may result in equipment liquid and suction lines at the outdoor unit. damage. INSTALL LIQUID LINE SOLENOID VALVE — SOLENOID For applications with liquid lift greater than 20 ft (6m), use DROP — It is recommended that a solenoid valve be 5/8 in liquid line. Maximum lift is 60 ft (18m). placed in the main liquid line (see Figure 3) between the Table 2 Liquid Line Data − 60 Hz condensing unit and the evaporator coil. Refer to Table 4. (A liquid line solenoid valve is required when the liquid line MAXIMUM Maximum Maximum length exceeds 75 ft [23 m]. This valve prevents refrigerant ALLOWABLE Allowable Allowable Temp. migration (which causes oil dilution) to the compressor LIQUID LIFT Pressure Drop Loss during the off cycle, at low outdoor ambient temperatures. ft(m) psig (kPa) _F( _C) Wire the solenoid in parallel with the compressor contactor 60 (18) 7 (48) 2 (1) coil (see Figure 3). This means of electrical control is * Inlet and outlet referred to as solenoid drop control. NOTE: Data shown is for units operating at 45_F (7.2_C) INSTALL LIQUID LINE SOLENOID VALVE (Optional) — saturated suction temperature and 95_F (35_C) entering CAPACITY CONTROL — If 2−step cooling is desired, air temperature. For applications with liquid lift greater than place a solenoid valve in the location shown in Figure 3. 20 ft (6 m), use 5/8−in. liquid line. Maximum lift is 60 ft (18 MAKE PIPING CONNECTIONS — Piping connections at m). the unit are ball valves with stub tube extensions. Do not open the unit service valves until all interconnecting tube Table 3 Refrigerant Piping Sizes − 60 Hz units brazing has been completed and properly evacuated. LINEAR LENGTH OF INTERCONNECTING The stub tube service valve connections include 1/4−in PIPING — FT (m) SAE service fittings with Schrader valve cores (see 0−25 25−50 50−75 75−100 Figure 4). Before making any brazed connections to the UNIT (0−7.5) (7.5−15) (15−23) (23−30)* unit service valves, remove both Schrader valve caps and cores and save for re−installation. Connect a source for Line Size (in. OD) nitrogen to one of these service fittings during tube brazing L S L S L S L S to prevent the formation of copper oxides inside the tubes 3/ at brazed joints. 072 8 11/8 3/ 8 11/8 3/ 8 11/8 3/ 8 11/8 When connecting and then brazing the field tubing to the 091 3/ 11/8 1/ 11/8 1/ 11/8 1/ 13/8 8 2 2 2 service valves, wrap the valves in wet rags to prevent overheating. 8 501 01 3001 00
Split System Condensers Installation Instructions Table 4 Refrigerant Specialties Part Numbers LIQUID LINE LIQUID LINE FILTER SUCTION LINE UNIT SOLENOID LLSV COIL SIGHT GLASS SIZE (in.) DRIER ACCUMULATOR VALVE (LLSV) 072 3/ 1178274 1178270 1178266* 1178265 8 3/ 1178274 1178270 1178266* 1178265 8 091 1/ 2 1178275 1178273 1178271 1178266 1178265 121 1/ 1178276 1178271 1178267* 1178264 2 151 5/ 1178277 1178272 1178267* 1178264 8 * Bushings required. Pressure−test all joints from outdoor unit connections over to the evaporator coil, using nitrogen as pressure and with Figure 3 Location of Sight Glass and Filter Drier soap and−bubbles. When pressure−testing is completed, remove the nitrogen source at the outdoor unit service valves and re−install the two Schrader valve cores. Torque the cores to 2−3 in−lbs (23−34 N−cm). EVACUATION/DEHYDRATION — Evacuate and dehydrate the connected refrigeration system, to 500 microns, using a two−stage vacuum pump attached to the service ports outside the service valves, following description in GTAC II, Module 4, System Dehydration. ! WARNING UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal in- Representative drawing only. jury, death and/or equipment damage. Figure 4 Typical Piping Connection Assembly R−410A systems operate at higher pressures than R−22 systems. When working with R−410A systems, use only service equipment and replacement components specif- ically rated or approved for R−410A service. PRELIMINARY CHARGE — Before starting the unit, charge R−410A liquid refrigerant into the high side of the Field Service Access Port system through the liquid service valve. The amount of Factory (Schrader refrigerant added must be at least 80% of the operating High-Flow Access Port core) charge listed in the Physical Data table (Tables 1A and 1B, pages 4 and 5) LESS the factory charge quantity (if factory shipping charge has not been removed). Allow high and Service Valve low side pressures to equalize. If pressures do not equalize with Stem Cap Sweat readily, charge R−410A vapor (using special service Connection manifold with expansion device) into the suction line service port for the low side of system to assure charge in the evaporator. Refer to GTAC II, Module 5, Charging, Recover, Recycling, and Reclamation for liquid charging procedures. 501 01 3001 00 9
Installation Instructions Split System Condensers Step 6 — Install Accessories Figure 5 Disconnect Switch and Unit Accessories requiring modifications to unit wiring should be completed now. These accessories may include Winter Start controls, Low Ambient controls, phase monitor, Compressor LOCout. Refer to the instructions shipped with the accessory. Step 7 — Complete Electrical Connections SWITCH COPPER ! WARNING WIRE ONLY ELECTRICAL SHOCK HAZARD ALUMINUM WIRE Failure to follow this warning could result in personal injury or death. Units Without Factory−Installed Disconnect — When Do not use gas piping as an electrical ground. Unit installing units, provide a disconnect switch per NEC cabinet must have an uninterrupted, unbroken electrical (National Electrical Code) of adequate size. Disconnect ground to minimize the possibility of personal injury if an sizing data is provided on the unit informative plate. Locate electrical fault should occur. This ground may consist of on unit cabinet or within sight of the unit per national or local electrical wire connected to unit ground lug in control codes. Do not cover unit informative plate if mounting the compartment, or conduit approved for electrical ground disconnect on the unit cabinet. when installed in accordance with NEC (National Electrical Code); ANSI/ NFPA 70, latest edition (in Units with Factory−Installed Disconnect — The Canada, Canadian Electrical Code CSA [Canadian factory−installed option disconnect switch is located in a Standards Association] C22.1), and local electrical weatherproof enclosure located under the main control codes. box. The manual switch handle is accessible through an opening in the access panel. NOTE: Check all factory and field electrical connections for tightness. Field−supplied wiring shall conform with the All units − All field wiring must comply with NEC and all local limitations of 63_F (33_C) rise. codes. Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Figure 6 for power wiring All units except 208/230−v units are factory wired for the connections to the unit power terminal block and voltage shown on the nameplate. If the 208/230−v unit is equipment ground. to be connected to a 208−v power supply, the control transformer located in the unit control box must be rewired Provide a ground−fault and short−circuit over−current by moving the black wire with the 1/4−in. female spade protection device (fuse or breaker) per NEC Article 440 (or connector from the 230−v connection and moving it to the local codes). Refer to unit informative data plate for MOCP 208−v 1/4−in. male terminal on the primary side of the (Maximum Over−current Protection) device size. transformer. Refer to unit label diagram for to line−side information. Field power wires will be connected line−side Figure 6 Power Wiring Connections pressure lugs on the power terminal block or at factory Splice Terminals installed option non−fused disconnect. BLK (field supplied) Field power wires are connected to the unit at the leads to the factory test connection leads (pigtails) in the unit’s main control box (see Figure 6) or at factory−installed option non−fused disconnect switch. Max wire size is #4 AWG YEL (copper only). NOTE: TEST LEADS − Unit may be equipped with short leads (pigtails) on the field line connection points on the optional disconnect switch. These leads are for factory BLU run−test purposes only; remove and discard before connecting field power wires to unit connection points. DISCONNECT ! WARNING Ground Lug FIRE HAZARD Failure to follow this warning could result in intermittent operation or performance satisfaction. LEGEND Do not connect aluminum wire between disconnect Factory Power Connection Lead switch and condensing unit. Use only copper wire. (See Field Power Supply Conductor Figure 5) All field wiring must comply with the NEC and local requirements. 10 501 01 3001 00
Split System Condensers Installation Instructions Affix the crankcase heater warning sticker to the unit shipment, the convenience outlet is covered with a blank disconnect switch. cover plate. Convenience Outlets — The weatherproof cover kit is shipped in the unit’s control box. The kit includes the hinged cover, a backing plate and ! WARNING gasket. DISCONNECT ALL POWER TO UNIT AND ELECTRICAL OPERATION HAZARD CONVENIENCE OUTLET. Failure to follow this warning could result in personal in- Remove the blank cover plate at the convenience outlet; jury or death. discard the blank cover. Units with convenience outlet circuits may use multiple Loosen the two screws at the GFCI duplex outlet, until disconnects. Check convenience outlet for power status approximately 1/2−in (13 mm) of screw heads are before opening unit for service. Locate its disconnect exposed. Press the gasket over the screw heads. Slip the switch, if appropriate, and open it. Tag−out this switch, backing plate over the screw heads at the keyhole slots and if necessary. align with the gasket; tighten the two screws until snug (do not over−tighten). One type of convenience outlet is offered on all models: Non−powered. The outlet provide a 125−volt GFCI Mount the weatherproof cover to the backing plate as (ground−fault circuit−interrupter) duplex receptacle rated shown in Figure 8. Remove two slot fillers in the bottom of at 15−A behind a hinged waterproof access cover, located the cover to permit service tool cords to exit the cover. on the end panel of the unit. See Figure 7. Check for full closing and latching. Figure 7 Convenience Outlet Location Figure 8 Weatherproof Cover Installation COVER WHILE-IN-USE RECEPTACLE Convenience WEATHERPROOF NOT INCLUDED Outlet GFCI CONVENIENCE BASE PLATE FOR OUTLET GFCI Control Box COVER RECEPTACLE Access Panel All Units — Voltage to compressor terminals during operation must be within voltage range indicated on unit Non−powered type: This type requires the field installation nameplate. See Table 5. On 3−phase units, voltages of a general−purpose 125−volt 15−A circuit powered from between phases must be balanced within 2% and the a source elsewhere in the building. Observe national and current within 10%. Use the formula shown in the legend for local codes when selecting wire size, fuse or breaker Table 5, Note 5 (see page 13) to determine the percent of requirements and disconnect switch size and location. voltage imbalance. Operation on improper line voltage or Route 125−v power supply conductors into the bottom of excessive phase imbalance constitutes abuse and may the utility box containing the duplex receptacle. cause damage to electrical components. Such operation Using unit−mounted convenience outlets: Units with unit would invalidate any applicable warranty. mounted convenience outlet circuits will often require that The unit requires an external temperature control device. two disconnects be opened to de−energize all power to the This device can be a thermostat (field−supplied) or a unit. Treat all units as electrically energized until the thermostat emulation device provided as part of a convenience outlet power is also checked and third−party Building Management System. de−energization is confirmed. Observe National Electrical Thermostat — Install an accessory commercial thermostat Code Article 210, Branch Circuits, for use of convenience according to installation instructions included with the outlets. accessory. For complete economizer function, select a Installing Weatherproof Cover – two—stage cooling thermostat. Locate the thermostat A weatherproof while−in−use cover for the accessory on a solid wall in the conditioned space to sense factory−installed convenience outlets is now required by average temperature in accordance with the thermostat UL standards. This cover cannot be factory−mounted due installation instructions. its depth; it must be installed at unit installation. For 501 01 3001 00 11
Installation Instructions Split System Condensers If the thermostat contains a logic circuit requiring 24−v CONTROL CIRCUIT WIRING — Control voltage is 24 v. power, use a thermostat cable or equivalent single leads of See Figure 6 and the unit’s label diagram for field−supplied different colors with minimum of four leads. If the wiring details. Route control wires through the opening in thermostat does not require a 24−v source (no “C” unit’s end panel to the connection in the unit’s control box. connection required), use a thermostat cable or equivalent CONTROL TRANSFORMER WIRING — On multivoltage with minimum of three leads. Check the thermostat units, check the transformer primary wiring connections. installation instructions for additional features which might See Figure 10 or refer to the unit’s label diagram. require additional conductors in the cable. If the unit will be operating at 208−3−60 power, remove the For wire runs up to 50 ft. (15 m), use no. 18 AWG (American black wire (BLK) from the transformer primary connection Wire Gage) insulated wire (35_C minimum). For 50 to 75 labelled “230” and move it to the connection labelled “208”. ft. (15 to 23 m), use no. 16 AWG insulated wire (35_C See Figure 10. minimum). For over 75 ft. (23 m), use no. 14 AWG insulated wire (35_C minimum). All wire sizes larger than no. 18 Figure 10 Control Transformer Wiring AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat. Figure 9 Typical Remote Thermostat Connections X X C C G G W W 2 2 W W 1 1 Y2 Y2 Y1 Y1 R R Thermostat Terminal Board Note 1: Typical multi−function marking. Follow manufacturer’s configuration instructions to select Y2. Note 2: Y2 to economizer required on single−stage cooling units when integrated economizer function is desired Note 3: Connect only if thermostat requires 24−vac power source. Field Wiring 12 501 01 3001 00
Split System Condensers Installation Instructions Table 5 Electrical Data — 60 Hz Units FAN MOTORS UNIT NOMINAL VOLTAGE RANGE* COMPRESSOR POWER SUPPLY (Qty 2) CAS VOLTAGE MIN MAX RLA LRA FLA (ea) LRA (ea) MCA MOCP 208/230-3-60 187 253 19 123 1.5 3.7 25.2 45 072 460-3-60 414 506 9.7 62 0.8 1.9 12.9 20 575-3-60 518 633 7.4 50 0.6 1.6 9.9 15 208/230-3-60 187 253 25 164 1.5 3.7 32.7 50 091 460-3-60 414 506 12.2 100 0.8 1.9 16 25 575-3-60 518 633 9 78 0.6 1.6 11.8 20 208/230-3-60 187 253 30.1 225 1.5 3.7 39.1 60 121 460-3-60 414 506 16.7 114 0.8 1.9 21.7 30 575-3-60 518 633 12.2 80 0.6 1.6 15.8 25 208/230-3-60 187 253 48.1 245 1.5 3.7 61.6 80 151 460-3-60 414 506 18.6 125 0.8 1.9 24 30 575-3-60 518 633 14.7 100 0.6 1.6 19 30 FLA — Full Load Amps LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code RLA — Rated Load Amps *Units are suitable for use on electrical systems where voltage supplied to the unit terminals is not below or above the listed limits. NOTES: 1. The MCA and MOCP values are calculated in accordance with the NEC, Article 440. 2. Motor RLA and LRA values are established in accordance with Underwriters’ Laboratories (UL), Standard 1995. 3. The 575−v units are UL, Canada−listed only. 4. Convenience outlet is available as a factory−installed option and is 115−v, 1 ph, 60 Hz. 5. Unbalanced 3−Phase Supply Voltage Never operate a motor where a phase imbalance in supply Example: Supply voltage is 230-3-60 voltage is greater than 2%. Use the following formula to determine the percentage of voltage imbalance. AB = 224 v BC = 231 v max voltage deviation from average voltage AC = 226 v % Voltage Imbalance = 100 x average voltage (224 + 231 + 226) 681 Average Voltage = = 3 3 = 227 Determine maximum deviation from average voltage. (AB) 227 – 224 = 3 v (BC) 231 – 227 = 4 v (AC) 227 – 226 = 1 v Maximum deviation is 4 v. Determine percent of voltage imbalance. 4 % Voltage Imbalance = 100 x 227 = 1.76% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. 501 01 3001 00 13
Installation Instructions Split System Condensers PRE−START−UP manifold gauge set then the liquid service valve. The amount of refrigerant added must be at least 80% of the ! CAUTION operating charge listed in the Physical Data table (Tables 1A and 1B, pages 4 and 5). Allow high and low side pressures to equalize before starting compressor. If UNIT OPERATION HAZARD pressures do not equalize readily, charge vapor on low side Failure to follow this caution may result in equipment of system to assure charge in the evaporator. Refer to damage. GTAC II, Module 5, Charging, Recover, Recycling, and Before beginning Pre−Start−Up or Start−Up, review Reclamation for liquid charging procedures. Start−Up Checklist at the back of this book. The Checklist assures proper start−up of a unit and provides a record of unit condition, application requirements, ! CAUTION system information, and operation at initial start−up. UNIT DAMAGE HAZARD ! CAUTION Failure to follow this caution may result in equipment damage. Prior to starting compressor, a preliminary charge of UNIT DAMAGE HAZARD refrigerant must be added to avoid possible compressor Failure to follow this caution may result in equipment damage (approximately 80% total refrigerant capacity). damage. Do not attempt to start the condensing unit, even START−UP momentarily, until the following steps have been The compressor crankcase heater must be on for 24 hours completed. Compressor damage may result. before start−up. After the heater has been on for 24 hours, the unit can be started. System Check PRELIMINARY CHECKS 1. Check all air handler(s) and other equipment auxiliary components. Consult the manufacturer’s 1. Check that electric power supply agrees with unit instructions regarding any other equipment nameplate data. connected to the condensing unit. If the unit has 2. Verify that the compressor crankcase heater is field−installed accessories, be sure all are properly securely in place. installed and correctly wired. If used, the airflow 3. Check that the compressor crankcase heater has switch must be properly installed. been on at least 24 hours. 2. Be sure the unit is properly leak checked and 4. Recheck for leaks using the procedure outlined in the dehydrated. Pre−Start−Up section, Leak Test and Dehydration. If any leaks are detected, repair as required. Evacuate 3. Check tightness of all electrical connections. and dehydrate as described in the Leak Test and Dehydration section. 4. Open the liquid line and suction line service valves. 5. Ensure that the preliminary charge has been added 5. Be sure the unit is properly charged. See “Preliminary as described in the Pre−Start−Up section, Charge”, on page 9. Preliminary Charge. 6. The electrical power source must agree with the 6. All internal wiring connections must be tight, and all unit’s nameplate rating. barriers and covers must be in place. NOTE: The units are factory charged with the required 7. The crankcase heater should be firmly attached to amount of oil. If recharging is required, use Emkarate RL the compressor crankcase. Be sure the crankcase is 32−3MAF for the units. warm (heater must be on for 24 hours before starting compressor). COMPRESSOR ROTATION — On 3−phase units with scroll compressors, it is important to be certain that the Energize the Crankcase Heater — Turn on the crankcase compressor is rotating in the proper direction. To determine heater for 24 hours before starting the unit to be sure all the whether or not compressor is rotating in the proper refrigerant is out of the oil. To energize the crankcase direction: heater, proceed as follows: 1. Connect service gages to the suction and liquid 1. Set the space thermostat set point above the space pressure fittings. temperature so there is no demand for cooling. 2. Energize the compressor. 2. Close the field disconnect. 3. The suction pressure should drop and the liquid pressure should rise, as is normal on any start−up. NOTE: Make sure that thermostat leads are isolated If the suction pressure does not drop and the liquid from the Low Voltage terminal block when energizing pressure does not rise to normal levels: Crankcase Heater for 24 hours. This insures compressor will not operate. 1. Turn off power to the unit, tag disconnect. 2. Reverse any two of the unit power leads. Preliminary Charge — Before starting the unit, charge 3. Reapply power to the compressor, verify correct liquid refrigerant into the high side of the system through a pressures. 14 501 01 3001 00
Split System Condensers Installation Instructions The suction and liquid pressure levels should now move to Scroll compressor models (ZP103 and ZP137) that contain their normal start−up levels. this technology. See Figure 12. COMPRESSOR OVERLOAD — This overload interrupts power to the compressor when either the current or internal Advanced Scroll Temperature Figure 12 motor winding temperature becomes excessive, and Protection Label automatically resets when the internal temperature drops to a safe level. This overload may require up to 60 minutes (or longer) to reset. If the internal overload is suspected of being open, disconnect the electrical power to the unit and check the circuit through the overload with an ohmmeter or continuity tester. Temperature Overload Device (TOD) is a thermal disk temperature device embedded into the ZP61 and ZP83 compressor scroll plates. This device once opened will bypass hot gas into the motor windings opening the motor thermal protector. If this device opens, the compressor may operate with some difference in suction and liquid pressures as measured with a manifold gauge set. This START UNIT — The field disconnect is closed, the indoor device is auto−resetting and may take up to 60+ minutes fan circuit breaker is closed, and the space thermostat is to reset. set above ambient so that there is no demand for cooling. ADVANCED SCROLL TEMPERATURE PROTECTION Only the crankcase heater will be energized. (ASTP) — Advanced Scroll Temperature Protection Reset the space thermostat below ambient so that a call for (ASTP) is a form of internal discharge temperature cooling is applied. protection, used in 10 and 12.5 Ton units, that unloads the scroll compressor when the internal temperature reaches approximately 300_F. At this temperature, an internal ! CAUTION bi−metal disk valve opens and causes the scroll elements to separate, which stops compression. Suction and UNIT DAMAGE HAZARD discharge pressures balance while the motor continues to Failure to follow this caution may result in equipment run. The longer the compressor runs unloaded, the longer damage. it must cool before the bi−metal disk resets. See Figure 11. Never charge liquid into the low−pressure side of system. Do not overcharge. During charging or removal Recommended Minimum Cool− of refrigerant, be sure indoor−fan system is operating. Figure 11 Down Time After Compressor is Ensure both outdoor fan motors are running; bypass any Stopped low ambient control function. ADJUST REFRIGERANT CHARGE — The unit must be 120 charged in Cooling mode only. Refer to Cooling Charging 110 Charts, Figure 13 through Figure 16. For applications with Recommended Cool i ng Ti me 100 90 line lengths greater than 100 ft, contact the distributor. Vary 80 refrigerant until the conditions of the chart are met. Note (Mi nutes) 70 60 that the charging charts are different from the type normally 50 used. The charts are based on charging the units to the 40 30 correct subcooling for the various operating conditions. 20 Accurate pressure gage and temperature sensing device 10 0 are required. Connect the pressure gage to the service port 0 10 20 30 40 50 60 70 80 90 on the liquid line service valve. Mount the temperature Compressor Unloaded Run Time (Minutes) sensing device on the liquid line close to the liquid line *Times are approximate. service valve, and insulate it so that outdoor ambient temperature does not affect the reading. Indoor airflow NOTE: Various factors, including high humidity, high must be within the unit’s normal operating range. Operate ambient temperature, and the presence of a sound blanket the unit for a minimum of 15 minutes. Ensure that pressure will increase cool−down times. and temperature readings have stabilized. Plot the liquid To manually reset ASTP, the compressor should be pressure and temperature on chart and add or reduce the stopped and allowed to cool. If the compressor is not charge to meet the curve. Adjust the charge to conform with stopped, the motor will run until the motor protector trips, the charging chart, using the liquid pressure and which occurs up to 90 minutes later. Advanced Scroll temperature to read the chart. Temperature Protection will reset automatically before the FINAL CHECKS — Ensure that all safety controls are motor protector resets, which may take up to 2 hours. A operating, control panel covers are on, and the service label located above the terminal box identifies Copeland panels are in place. 501 01 3001 00 15
Installation Instructions Split System Condensers Figure 13 6 Ton Charging Chart 072 CHARGING CHART R−410A ALL CONDENSER FANS OPERATING 072 Figure 14 7.5 Ton Charging Chart 091 CHARGING CHART R−410A ALL CONDENSER FANS OPERATING 091 Figure 15 10 Ton Charging Chart 121 CHARGING CHART R−410A ALL CONDENSER FANS OPERATING 121 16 501 01 3001 00
Split System Condensers Installation Instructions Figure 16 12.5 Ton Charging Chart 151 CHARGING CHART R−410A ALL CONDENSER FANS OPERATING 151 Figure 17 Wiring Diagram OPTIONAL 501 01 3001 00 17
Installation Instructions Split System Condensers OPERATING SEQUENCE ROUTINE SYSTEM MAINTENANCE Base Unit Controls These items should be part of a routine maintenance Indoor (Supply) Fan program, to be checked every month or two, until a specific schedule for each can be identified for this installation: The indoor fan contactor (IFC) is remotely located at the fan Quarterly Inspection (and 30 days after initial start) coil or fan section. If the thermostat fan operation is selected as Continuous, the IFC is energized and the Indoor section indoor (supply) fan motor runs continuously. If the S Condenser coil cleanliness checked. thermostat fan operation is selected as Automatic, the IFC S Return air filter replacement will be energized on a call for Cooling; indoor (supply) fan motor runs. When thermostat call for Cooling is satisfied, S Outdoor hood inlet filters cleaned the IFC is de−energized and indoor (supply) fan motor S Belt tension checked stops. S Belt condition checked Cooling, Unit Without Economizer S Pulley alignment checked On a thermostat call for Cooling, IFC will be energized and S Fan shaft bearing locking collar tightness checked indoor (supply) fan motor runs. Thermostat contact TC1 S Condensate drain checked closes; terminal Y1 receives 24−v. 24−v received at CADM terminal Y. If anti−recycle time delay period has not expired, Seasonal Maintenance CADM relay will remain open, preventing compressor start. These items should be checked at the beginning of each When safety pressure switches are closed, the liquid line season (or more often if local conditions and usage solenoid valve opens. When CADM time delay expires (3 patterns dictate): minutes), the compressor contactor is energized; both Air Conditioning outdoor fan motors start and compressor starts. When S Condenser fan motor mounting bolts tightness space cooling load is satisfied, thermostat contacts TC1 open, removing 24−v at terminal Y. Compressor and S Compressor mounting bolts outdoor fan motors stop. Liquid line solenoid valve is S Condenser fan blade positioning de−energized and valve closes. CADM begins its S Control box cleanliness and wiring condition three−minute anti−recycle time delay. S Wire terminal tightness If either the Low Pressure Switch or High Pressure Switch S Refrigerant charge level opens while thermostat contact TC1 remains closed, the compressor contactor is de−energized (both fan motors S Evaporator coil cleaning and compressor stop) and liquid line solenoid is S Evaporator blower motor amperage de−energized (valve closes). CADM initiates a TRIP event Heating (cooling demand sensed at CADM terminal Y but no S Power wire connections current is measured at T1, T2, T3 motor sensors); CADM relay opens and RED LED is illuminated. TRIP condition S Fuses ready maintains lockout of compressor operation until CADM is S Manual−reset limit switch is closed manually reset. Reset CADM by cycling unit main power. Economizer or Outside Air Damper Complete system shutdown may be caused by loss of main S Inlet filters condition power, open compressor internal overload, open low−pressure or high−pressure switch, or a fault detected S Check damper travel (economizer) by the CADM logic. Compressor operation without cooling S Check gear and dampers for debris and dirt may indicate the compressor’s TOD or ASTP feature is SERVICE active (unit sizes 12 and 14 only); disconnect unit power and allow compressor to cool. See Service section for Comfort Alert Diagnostic Module further details. The Comfort Alert Diagnostic Module (CADM) monitors Cooling, Unit with Economizer and analyzes data from the Copeland Scrollt three−phase compressor and the thermostat demand. The CADM also Refer to fan coil unit installation instructions and provides a 3−minute anti−recycle time delay to compressor economizer accessory installation instructions for cycling. The CADM detects causes for electrical and operating sequences when system is equipped with system related failures without any sensors. Flashing accessory economizer. LEDs communicate the Alert codes to guide service Heating technicians in accurately and quickly troubleshooting the Refer to fan coil unit installation instructions and accessory system and determining root cause for the failure. Inputs to heating device installation instructions for operating the CADM include 24−vac power, thermostat Y1, sequences in heating mode. 18 501 01 3001 00
Split System Condensers Installation Instructions compressor contactor coil (common side) and compressor The ALERT LED indicates an abnormal condition exists in power leads (from the compressor contactor) the system through a flash code. The ALERT LED will blink a number of times consecutively, pause and the repeat the Input Terminal Voltage process. The number of blinks, defined in Table 6, Control Power R 24V correlates to a particular abnormal condition; troubleshooting tips are provided for each Alert code. Control Common C 24V Reset of the ALERT may be automatic or manual. If the Cooling Y 24V fault condition causing the Alert is self−corrected, the Alert code will be removed and the CADM will automatically Contactor Coil P 24V reset and allow the system to restart normally. Manual Line A T1 Line reset requires that main power to the unit be recycled after Line B T2 Line the cause for the Alert condition has been detected and corrected. Line C T3 Line The TRIP LED indicates either a time−delay period is Control of the compressor contactor coil is through a currently active (RED LED is blinking) or the module has normally−closed (power on the module) contact between locked out the compressor (RED LED is on steady). A terminals P and C. lockout condition will occur when the CADM detects a thermostat demand at input Y but there is no power at the Communications of status and alert conditions is through compressor line terminals T1 or T2 or T3. This lockout can three LEDs located on the top edge of the module housing occur due to a safety switch (LPS or HPS) opening and (see Figure 18): POWER (green), ALERT (yellow), and de−energizing the compressor contactor, the TRIP (red). The POWER LED indicates the presence of compressor−motor internal overload opens, or other control power to the CADM. internal power interruption has occurred. Reset of the TRIP Figure 18 CADM Housing/LED Locations LED requires that unit main power be recycled after the loss of power to the compressor condition has been POWER (GRN) detected and corrected. Simultaneous Blinking of YELLOW and RED LEDs indicates control power input to the CADM is low. Check control circuit transformer and wiring. Troubleshooting the CADM Wiring – Flashing LEDs also indicate wiring problems to the CADM. See Table 7 for discussion of additional LED flash codes and troubleshooting instructions. ALERT (YEL) TRIP (RED) 501 01 3001 00 19
Installation Instructions Split System Condensers Table 6 LED Status Codes Status LED Status LED Description Status LED Troubleshooting Information Green “POWER” Module has power Supply voltage is present at module terminals Red “TRIP” Thermostat demand signal Y 1. Compressor protector is open LED On Solid is present, but the 2. Condensing unit power disconnect is open compressor is not running. 3. Compressor circuit breaker or fuse(s) is open 4. Broken supply wires or connector is not making contact 5. Compressor power wires not routed through Comfort Alert 6. Compressor contactor has failed open Red “TRIP” LED The anti−short cycle timer (3 minutes), in module is preventing compressor restart. Flashing Module locks out compressor when compressor damaging ALERT code appears. Lockout ALERT codes are noted in the Status LED Description. During a compressor lock out, 24VAC power must be removed from module to manually reset. Yellow “ALERT” A short circuit or over current 1. Compressor contactor coil shorted LED On Solid condition exists on PROT 2. Electrical load too high for PROT circuit (max1 Amp) terminal. 3. 24 V AC wired directly to PROT terminal Yellow “ALERT” System Pressure Trip 1. High head pressure Flash Code 2 Discharge pressure out of 2. Condenser coil poor air circulation (dirty, blocked, damaged) limits or compressor 3. Condenser fan is not running overload (if no high pressure 4. If low pressure switch is open: switch in system) Refer to Code 3 for troubleshooting LOCKOUT Yellow “ALERT” Short Cycling 1. If low pressure switch is open: Flash Code 3 Compressor is running only a. Low refrigerant charge briefly LOCKOUT b. Evaporator blower is not running c. Evaporator coil is frozen d. Faulty metering device e. Condenser coil is dirty f. Liquid line restriction (filter drier blocked if present) 2. If high pressure switch is open, go to Flash Code 2 in- formation 3. Intermittent thermostat demand signal 4. System or control board defective Yellow “ALERT” Locked Rotor 1. Low line voltage to compressor Flash Code 4 LOCKOUT 2. Excessive liquid refrigerant in compressor 3. Compressor bearings are seized Yellow “ALERT” Open Circuit 1. Condensing unit power disconnect is open Flash Code 5 2. Compressor circuit breaker or fuses are open 3. Compressor contactor has failed open 4. High pressure switch is open and requires manual reset 5. Broken supply wires or connector is not making contact 6. Unusually long compressor protector reset time due to extreme ambient temperature 7. Compressor windings are damaged Yellow “ALERT” Missing Phase 1. Compressor fuse is open on one phase Flash Code 6 LOCKOUT 2. Broken wire or connector on one phase 3. Compressor motor winding is damaged 4. Utility supply has dropped one phase Yellow “ALERT” Reverse Phase 1. Compressor running backward due to supply Flash Code 7 LOCKOUT phase reversal Yellow “ALERT” Welded Contactor 1. Compressor contactor has failed closed Flash Code 8 Compressor always runs 2. Thermostat demand signal not connected to module Yellow “ALERT” Low Voltage 1. Control circuit transformer is overloaded Flash Code 9 Control circuit < 18VAC 2. Low line voltage to compressor 20 501 01 3001 00