The Gilflo in-line variable area (ILVA) flowmeter ... is a revolutionary development of the well established family of Gilflo flowmeters that has been used in industrial flowmetering applications for more than 30 years. Using the same unique operating principle but incorporating a number of significant design changes, the Gilflo ILVA flowmeter is perfectly suited for use with most industrial fluids including steam and gases. A comprehensive range of associated sensors and electronic instrumentation is available to compliment the Gilflo ILVA flowmeter range and make it one of the most adaptable flowmeters available. Why install flowmeters? The main justifications for installing flowmeters in any industrial plant are: n Product quality: By providing management information, they enable a plant to be operated at peak efficiency thus ensuring product quality is maintained in the most cost effective way. n Direct cost control: They can be used to cost raw materials or energy sources (such as compressed air) directly. How the Gilflo ILVA flowmeter works In common with other differential pressure flowmeters such as orifice plates and venturi meters, the Gilflo ILVA flowmeter primary element uses the theorem for the conservation of energy in fluid flow through a pipe. It operates on the well established spring loaded variable area (SLVA) principle where the area of an annular orifice is continuously varied by a moving cone. A centrally positioned cone is free to move axially against the resistance of a precision compression spring. This produces a variable differential pressure across the annular orifice which is sensed by a transmitter Dp connected to integral tappings on the flowmeter body. The pressure difference can then be used to derive an instantaneous rate of flow based on Bernoulli’s Theorem. The unique design of the Gilflo ILVA flowmeter greatly expands the capabilities of the differential pressure flow measurement. The key to the unique performance of the Gilflo ILVA flowmeter lies in the design of the orifice and cone to minimise upstream velocity profile effects and at the same time provide an exceptionally high turndown flowmeter based on practically achievable line velocities. Installation benefits D Gilflo ILVA The correct installation of any type of flowmeter is of prime importance if the manufacturers claims for accuracy and repeatability are to be achieved in practice. All types of flowmeter require a certain number of straight, uninterrupted lengths of meter size pipework upstream and downstream of the point of installation. 6D 3D In real life, there are often space constraints that severely restrict where and how a flowmeter can be installed. It is therefore very important to look carefully at where the flowmeter is to be fitted as early as possible. The unique wafer design of the Gilflo ILVA flowmeter means that its installed length is much shorter than almost any other flowmeter. A Gilflo ILVA flowmeter can often be fitted into lines which were never designed to accept flowmeters. Gilflo ILVA flowmeter 6 diameters up to Turbine 20 diameters up to Vortex 30 diameters up to Orifice plate 30 diameters 0 10 20 30 2 Number of upstream diameters of straight pipe
The importance of turndown DN150 Gilflo ILVA flowmeter 5 bar g saturated steam Vortex meter Benefit of large turndown at low flows Gilflo ILVA flowmeter 0.6 1 2 2.8 3 Minimum velocity m/s To ensure that the flow information gathered is accurate Turndown ratios with flow velocities limited to 35 m / s whatever the process conditions or demand, it is essential that a flowmeter is capable of meeting its specification over Gilflo ILVA flowmeter 100:1 the full operating range from low standing or weekend loads, right up to the maximum demand of the process. As actual Turbine typically 10:1 demands are often unknown or may vary widely, a flowmeter should have the largest turndown possible based on practical flow conditions. Great care should be taken that Vortex up to 15:1 depending on operating conditions claims for turndown are based on realistic flow velocities. For instance, steam systems should be sized on a maximum Orifice 4:1 flow velocity of about 35 m / s ... higher velocities will possibly cause erosion and noise problems in the system. 0 20 40 60 80 100 1 000 2 000 This graph shows a typical Cumulative error kg Flowrate kg / h Actual flowrate demand curve for a distributed Cumulative error 1 700 steam system with a high 750 1 500 start-up load and variable demand through the day. An orifice plate meter with a 500 1 000 4:1 turndown is sized on the peak load of 1 000 kg / h. Any 250 500 flowrates below 250 kg / h are Threshold at Orifice plate 'lost' or, at best recorded with 4:1 turndown a significant error. In this case 0 0 1 700 kg have been 'lost'. 0 1 2 3 4 5 6 7 8 The Gilflo ILVA flowmeter, with Hours elapsed its 100:1 turndown eliminates Flowrate below minimum of 250 kg / h (i.e. 1 000 kg / h ÷ 4) this type or error. Density compensation 1 000 10 3 500 It is rare for the pressure in Actual flowrate 800 8 3 000 a steam system to remain Cumulative error kg Actual system pressure 2 500 Pressure bar g absolutely constant. Unless Flowrate kg/ h this variation is taken into 600 6 2 000 account, flow measurement errors will occur. The automatic 400 4 1 500 density compensation options 1 000 completely eliminate these 200 2 errors and allow accurate 500 metering whatever the steam Cumulative error 0 0 0 pressure. This is shown in the 0 1 2 3 4 5 6 7 8 adjacent diagram. Hours elapsed In the example above, a simple non-compensated flowmeter is set for 6 bar g. The actual pressure in the system varies through the day and unless this is allowed for, by the end of the day, very significant errors can arise. This is typical of many steam systems. 3
Gilflo ILVA flowmeters ... proven technology in a new package. Thirty years experience and over 10 000 installations worldwide has firmly established the technology that gives Gilflo flowmeters their unequalled turndown and ultra compact installation. Now the Gilflo ILVA flowmeters uses this wealth of experience in a wafer design to give even lower cost of ownership. Designed and supported by Spirax Sarco’s worldwide supported, the Gilflo ILVA flowmeter is the logical choice. Range availability n Sizes DN50 (2") to DN200 (8") n All stainless steel 316L body construction n Pressure rating to match flange specifications n Temperatures up to 450°C Applications n Cost metering for Flow energy management direction n Custody transfer n Process and control applications n Boiler load control Commonly metered fluids n Saturated steam n Superheated steam n Condensate n Natural gas n Nitrogen n Carbon dioxide n Compressed air n Ethylene n Fuel oil 4
User benefits • Suitable for most industrial fluids. • Excellent turndown, up to 100:1. • High pipeline unit accuracy, ±1% of reading. • Ultra compact installation, requires only six pipe diameters upstream and All stainless steel three downstream. construction. • Wafer design for easy installation. Alignment webs for easy installation. • No expensive line size changes required to achieve low flow performance. Precision cone. • Intrinsically safe for use in hazardous areas. • Reliability proven over Wafer design fits between 30 years experience. customer flanges. • Designed and manufactured by Spirax Sarco - a ISO 9001 : 2000 Over-range stop prevents approved company. damage from surges or excessive flows. Precision heavy duty nickel cobalt alloy spring operates up to 450°C without creep. Pressure tappings built into the flowmeter body for easy installation. Gilflo calibration rig, Spirax Sarco, Cheltenham, England 5
Gilflo ILVA flowmeters ... system configurations and associated equipment EL2230 temperature transmitter Gilflo ILVA n M240G (steam) and M250G (gas) flow computers provide complete information on flow, pressure and temperature. n Full density compensation. n Linearisation of Gilflo signal. F50C isolation valves n Wall or panel mounting. EL2600 n Bright, easy to read display. pressure M610 transmitter differential n Alarm facilities for fluid flow, pressure and pressure temperature. transmitter n 4 independent timers. n Analogue, pulse and EIA232C outputs available M200 series flow computer as standard. Gilflo ILVA n M640 steam mass flow transmitter provides density compensated 4 - 20 mA output. n Linearisation of Gilflo signal. n Ideal for applications where density compensation is essential. F50C isolation valves n Suitable for use up to 74 bar g saturated steam. n HART® 5.2 in-built. M640 Steam mass n Optional local display. flow transmitter n Intrinsically safe pipeline unit and mass flow transmitter. M750 display unit Gilflo ILVA n M750 display unit provides local display of total flow and rate of flow. n Suitable for steam and most industrial fluids and gases. F50C isolation n Ideal for applications where valves fluid density is constant. M610 n User configurable. differential pressure transmitter n Linearisation of Gilflo signal. n Retransmission options of rate and / or total flow available. n Bright, easy to read display. M750 display unit n Panel mounting as standard. Note: The illustrations above are schematic only. Refer to Installation and Maintenance Instructions for further details. 6
Calibration of Gilflo ILVA flowmeters All Gilflo ILVA flowmeters are calibrated on a high accuracy flow facility at Spirax Sarco’s manufacturing plant in Cheltenham, England. Designed and built by Spirax Sarco engineers in conjunction with UK National Engineering Laboratories, it ensures that every flowmeter meets the highest possible standard of accuracy. Some basic features of the flow facility are: n Facility size capability: DN50 to DN300. n Reference methods: gravimetric and transfer standard electromagnetic meters. n Flow capacity: up to 19 000 litres/min water. n Pipework: all 316L stainless steel with upstream and downstream pipework straight runs in excess of recommended lengths. n Flowmeter location: clamping arrangements ensure flowmeters are concentric to pipework to ensure accurate calibration. n Fully automatic data collection: archiving of all flow data electronically for future reference / recalibration. n Calibration documentation: full calibration documentation is available with every flowmeter. Sizing and selection of a Gilflo ILVA flowmeter It is important to select the correct size of Gilflo ILVA flowmeter for a particular application. First principles can be used as follows, determine the equivalent water flowrate (litres/min) based on the maximum anticipated actual flow, then select the Gilflo ILVA best suited to the application using the tables below. Alternatively consult Spirax Sarco. Equivalent water flowrate QE Mass flow units Volumetric units Where: QE = Equivalent water flowrate (litres/min) qm qm = Mass flowrate (kg/min) Liquids QE = QE = QLÖ SG QL = Maximum liquid flowrate (litres/min) Ö SG QS = Maximum gas flowrate at standard conditions (litres/min) QF = Maximum gas flowrate at actual flow conditions (litres/min) Gases and SG = Specific gravity steam QE = qm 1 000 QE = QF DF DS = Density of gas at standard conditions (kg /m3) actual flow Ö DF Ö 1 000 DF = Density of gas at actual flow conditions (kg /m3) conditions PS = Standard pressure = 1.013 bar a = 1.033 kg / cm2 a Gases qm = 14.7 psi a QE = QE = QS DS x PS x TF PF = Actual flow pressure in same absolute units as PS standard DS PF TS x x Ö 1 000 PF TS TS = Standard temperature (K) = °C + 273 conditions Ö1 000 PS TF TF = Actual flow temperature (K) = °C + 273 Using the value of QE as determined above, select the correct Gilflo flowmeter from the table below: Table of QE Maximum QE Maximum DP Example: Flowmeter type Determine which Gilflo pipeline unit is required to measure the litres / minute Wg flow of compressed air when: DN50 149 200 1: Estimated maximum rate of flow = 500 s m³/h at 7 bar g and 20°C DN80 585 200 Note: Standard conditions = 1.013 bar a, 0°C giving a standard DN100 1 800 200 density of 1.29 kg / m³ DS P T DN150 2 900 200 2: Calculate QE from QE = QS x S x F Ö 1000 PF TS DN200 5 700 200 QE = (500 x 16.667) x 1.29 1.013 293 x x From the table, it can be seen that a DN50 Gilflo ILVA flowmeter would Ö 1000 8.013 273 be suitable for this application. Note: 1 m³ / h = 16.667 litres/ min. QE = 110 litres / min. Sizing the Gilflo ILVA flowmeter for saturated steam - capacities kg / h Steam pressure bar g 1 3 5 7 10 12 15 20 25 30 40 Maximum flow 300 416 503 577 671 727 804 918 1 020 1 113 1 283 DN50 Minimum flow 3 4 5 6 7 7 8 9 10 11 13 Maximum flow 1 179 1 632 1 976 2 264 2 635 2 855 3 156 3 603 4 003 4 371 5 039 DN80 Minimum flow 12 16 20 23 26 29 32 36 40 44 50 Maximum flow 3 629 5 023 6 080 6 967 8 108 8 784 9 709 11 085 12 317 13 449 15 505 DN100 Minimum flow 36 50 61 70 81 88 97 111 123 134 155 Maximum flow 5 847 8 092 9 795 11 224 13 062 14 152 15 643 17 859 19 843 21 667 24 980 DN150 Minimum flow 58 81 98 112 131 142 156 179 198 217 250 Maximum flow 11 492 15 905 19 252 22 061 25 674 27 816 30 746 35 101 39 002 45 587 49 098 DN200 Minimum flow 115 159 193 221 257 278 307 351 390 426 491 Note: Maximum flowrates are calculated at a differential pressure across the Gilflo ILVA pipeline unit of 498 mbar (200" H20). Minimum measurable flowrate is 1% of maximum. 7
Gilflo spring design The design and manufacture of the spring in the Gilflo ILVA flowmeter is fundamental to its accuracy and long term performance. n Made from 'aerospace' alloy Inconel X750 which is widely used in jet engine turbine components due to its exceptional high temperature performance. n During manufacture, all springs are age hardened at 650°C for 4 hours. n All springs are 'hot set' at 460°C after manufacture to eliminate any possibility of relaxation at high temperatures. n Design stress levels range from 11% to 30% UTS ... most springs are designed to stress levels of around 60%. n In service, all Gilflo ILVA flowmeters incorporate over-range stops to prevent over stressing the spring in overload conditions. n Many thousands of installations have proved the integrity of the design and manufacture of the spring. Specification Operating principle Spring loaded variable area with differential pressure output proportional to rate of flow. Limiting conditions To ANSI 600 (carbon steel) pressure / temperature envelope. Sizes available DN50, DN80, DN100, DN150 and DN200 EN 1092 PN16, PN25, PN40 BS 10 Table H Flange specifications ANSI B 16.5 Class 150, 300, 600 JIS 20 KS 20 Materials of construction Body and internals: Stainless steel 316L Spring: Inconel X750 Installation Normally horizontal. For vertical (flow downwards) applications, consult Spirax Sarco. When used in conjunction with an M200 series flow computer or M750 display unit or M640 steam Accuracy mass flow transmitter, pipeline unit accuracy is better than ± 1% of actual flow from 5% to 100% of maximum rated flow. For flows from 1% to 5% of maximum rated flow, the pipeline unit accuracy will be better than ± 0.1% FSD. Repeatability Better than 0.25%. Unrecovered pressure drop Less than 200 inches water gauge (498 millibar) at maximum flowrate. Dimensions / Weights (approximate in mm and kg) E Size A B C D E Weight Note: Pressure tappings are threaded ¼" NPT. DN50 35.0 63 130 103 17.5 2.0 (2 off located at 180°) DN80 45.0 78 160 138 22.5 3.9 DN100 60.5 103 208 162 37.5 8.3 DN150 75.0 134 300 218 37.5 14.2 DN200 85.0 161 360 273 42.5 23.6 D In addition to the ILVA range, Spirax Sarco can supply Gilflo flowmeters for special requirements in sizes from DN50 to DN400. These are of flanged, pressure vessel type construction and can be manufactured to meet most international standards construction and inspection. Please consult Spirax Sarco for details. A B Some of the products may not be available in certain markets. C Spirax-Sarco Limited, Charlton House, Cheltenham, Gloucestershire, GL53 8ER UK. Tel: +44 (0)1242 521361 Fax: +44 (0)1242 573342 E-mail: Enquiries@SpiraxSarco.com Internet: www.SpiraxSarco.com © Copyright 2003 Spirax Sarco is a registered trademark of Spirax-Sarco Limited 8 SB-P337-07 MI Issue 4