SOLUTION AIR HANDLING UNITS - 2000 TO 100,000 CFM (Indoor & Outdoor Models)
←
→
Page content transcription
If your browser does not render page correctly, please read the page content below
FORM 102.20-QG1 (808) V F D V FPC F D EA DP HF XA FS XA CC XA HC RF MB FE SA RA Split ld08301 FS DI RF XA DP Split VFD EA VC XA HC RF MB FE RA Split ld08302 SOLUTION AIR HANDLING UNITS 2000 TO 100,000 CFM (Indoor & Outdoor Models)
FORM 102.20-QG1 (808) TABLE OF CONTENTS GENERAL INFORMATION STAGGERED COIL OPTIONS Introduction ............................................................3 Angle Wall ............................................................32 A Proud History of Experience & Qualifications .....3 Back-to-Back ........................................................32 Assurance of Johnson Controls Backing ...............3 Multizone (MC) .....................................................33 Computer Selection Programs ...............................4 HEATING SEGMENTS Innovative Engineering & Design ...........................5 Integral Face & Bypass ........................................34 Flexibility of Design ................................................6 Indirect Gas-Fired ................................................35 Superior Casing Performance ................................6 Turndown Examples and Guidelines....................36 Pre-engineered Packaged Controls .......................7 Electric Heat Options & Applications ....................37 Customized Variable Size Openings ......................7 ENERGY RECOVERY Airflow Measurement Performance ........................8 Heat Wheel ..........................................................40 State-of-the-Art Certification & Testing ...................8 FILTER SEGMENTS New Sound Testing Laboratory ..............................8 Applications & Options Table ...............................41 Quality Construction Equals Improved IAQ............9 Mechanical Air Filters ...........................................42 Multi-Sloped Drain Pans ........................................9 MERV Analysis .....................................................43 Raceways...............................................................9 MIXING SEGMENTS & ECONOMIZERS Improve Cost Savings ............................................9 Mixing Box /Economizers .....................................44 A Complete Line of Filters ....................................10 Mixing Box Optimization Chart .............................46 Energy Saving Fan Options .................................10 Typical Economizer Application............................47 Energy Consumption............................................11 Building Pressurization.........................................47 Sound Attenuation ................................................13 Methods of Pressurization Control .......................48 Inertia Base ..........................................................13 Economizer Arrangements ...................................48 Quick Selection ....................................................14 Face Damper .......................................................49 FAN APPLICATION REVIEW Inlet Plenum .........................................................49 Fan Laws .............................................................15 ACCESSORY SEGMENTS Variable Air Volume ..............................................16 Diffuser Segment .................................................50 Component Temperature Margins ........................17 Access Segment ..................................................50 Fan Motor Heat ....................................................17 Vertical Plenum ...................................................51 COIL OPTIONS Discharge Plenum ................................................51 Cooling Coils ........................................................18 Sound Attenuator .................................................52 Heating Coils ........................................................19 Noise and Vibration ..............................................53 Typical Application of AH Coils .............................20 Air Blender - Mixers..............................................54 SOLUTION SEGMENT IDENTIFICATION Face & Bypass Damper Segment ........................55 Segment Listing ...................................................21 Turning Segments ................................................56 Unit & Coil Hand Selection ...................................21 Humidifier Segment..............................................56 FAN SEGMENTS – FS, FR, FE UV Segment .........................................................57 Fan Applications ...................................................22 Pipe Chase Enclosure..........................................58 Dual Fan Considerations......................................22 Roof Curb .............................................................58 Dual Fan Applications ..........................................22 Special Curb Requests ........................................59 Door and Discharge Locations .............................23 CONTROLS Single Fan DWDI Options ....................................24 F. P. Controls & Motor Control Centers ................60 Single Fan SWSI Options ....................................25 Typical FPC Wiring...............................................60 Dual Fan DWDI Options.......................................26 Software Process .................................................61 Dual Fan SWSI Options .......................................27 Field Equipment Controller...................................61 SWSI vs. DWDI ....................................................28 Power Wiring Options ..........................................62 Fan Motor Control Methods .................................29 INDUSTRY FORMULAS COIL SEGMENTS Miscellaneous Industry Formulas.........................63 Cooling (CC) ........................................................30 GUIDE SPECIFICATIONS WITH TIPS Heating (HC) ........................................................30 Part 1 - General....................................................64 Vertical Coil (VC) ..................................................31 Part 2 - Products ..................................................67 Part 3 - Execution.................................................81 2 JOHNSON CONTROLS
FORM 102.20-QG1 (808) GENERAL INFORMATION Introduction Assurance of Johnson Controls Backing This Equipment Guide will provide engineers with With every Solution system, you get the support and a summary of Solution air handling information in the resources that come from dealing with a worldwide most convenient, time-saving manner possible. The manufacturer – JOHNSON CONTROLS. You are not guide will direct you to various sources of data and infor- tied to the limitations of a regional supplier. Instead, you mation helpful in solving questions concerning product get the flexibility being able to design in one part of the options, design application, as well as installation and country, and buy and install in another location. operation. Johnson Controls Factory Service A Proud History of Experience & Qualifications Turn to the experts at Johnson Controls/YORK. Johnson Controls combined with YORK heating, ventila- Johnson Controls/York carries the burden of single- tion, air-conditioning, and refrigeration (HVAC&R) sys- source responsibility since Johnson Controls/YORK tems and solutions creates the largest global provider of packages the total system, including custom air han- integrated products, systems and services for the $200 dlers, chillers, controls, and variable air-volume boxes billion global building environment industry. and building automation systems. For added peace of mind, Johnson Controls/YORK offers Inspection Johnson Controls/YORK is: Only, Preventive Maintenance and Inspection, or Total • A global leader in control systems and services Service Contracts to meet your specific financing and for heating, ventilating, air conditioning (HVAC), management requirements. Johnson Controls service lighting, security and fire management for non- can also provide certified technicians available locally residential buildings, facility management and for factory start-up, drawing from over 700 factory- consulting services. trained service technicians in 100 strategically-located offices nationwide – a capability not offered by indepen- • Represented in over 125 countries, including dent manufacturers. North America, Asia, Europe, the Middle East, Africa and Latin America and in all markets. ® Full Service Support YORK Solution® air-handling units (AHUs) from John- son Controls–the only names you need to know for a line Because JOHNSON CONTROLS factory packaged that has no limits. Johnson Controls/YORK engineers devices and motor controls are an integral part of the have developed an AHU line that is so flexible, and able equipment, who better to troubleshoot and service the to deliver such high standards of performance, that it can system than a professional Johnson Controls Service handle virtually any application. Whatever the air-han- Technician. The Johnson Controls Service technician dling challenge–IAQ, acoustics, energy, controls, you knows not only the equipment and the hardware, but name it–Johnson Controls/YORK can build a Solution also has a working knowledge of equipment applica- AHU that will meet your needs. tion and operation. Every unit is backed by this kind of professional support. Solution® AHU’s from Johnson Controls comprise a complete AHU line to meet commercial, institutional and industrial indoor and outdoor unit Development and Preparation of Service Literature applications. For more than 50 years, YORK air Johnson Controls/YORK produces quality product handling units have been installed in every type of facility to literature to ensure proper installation, operation and handle any type of requirement; manufacturing, education, maintenance. Installation, Operation and Maintenance healthcare, life sciences and process manufacturing. manuals must be followed to realize the full capacity Solution® AHU’s come equipped with industry-leading and life of the units. In addition, literature supplements Metasys® controls that are installed and commissioned of special characteristics and features are distributed as at the factory. Factory installation assures superior required to support regular product enhancements. quality, saves time on the jobsite and delivers accurate performance. Plus, you can count on seamless opera- tion with a Metasys building management system. JOHNSON CONTROLS 3
FORM 102.20-QG1 (808) GENERAL INFORMATION Computer Selection Programs This powerful software tool brings flexibility and com- puting power to the desktop of designers. The software YORKworks™ software is the primary source for the allows you and the customer to make product decisions latest product design and performance data. and view performance data in a user-friendly, step-by- 1. Includes the latest innovations, updates, and ef- step, screen-driven environment. ficiencies of YORK® products YORKworksCE™ software is a necessity for your 2. Includes general functionality used to select customer’s engineering toolbox. YORKworks revolution- equipment factory packaged controls. izes the way you specify HVAC equipment. Johnson Controls/YORK can optimize the selection of any air 3. Sound data for air-handling units handling unit for a specific job requirement with its 4. All screens are interconnected and are continually computer selection programs. updated according to configuration inputs. Quick and Easy selection • Save Time – choose components and complete configurations with a couple of clicks. • Reduce Errors – use pre-programmed rules and guidelines for component selection. Just Click to select and add components Literature Reference — see ‘Sales Guide – YORK works CE’ Form 70.02-SG1 4 JOHNSON CONTROLS
FORM 102.20-QG1 (808) Innovative Engineering & Design 5. Solution’s Variable Aspect Ratio eliminates the need for costly modifications. Solution Air Handlers are not just ‘fans-in-a-box’! 6. Solution fits the specification and the space! 1. Solution is a structure that withstands deflection 2. Solution is a sound/noise barrier Innovative Engineering & Design allows you to choose from a limitless variety of configurations. See con- 3. Solution is a container of clean and conditioned air figurations below for some of the popular applications 4. Solution is an integral part of a building’s fire and designed to meet your particular need. safety plans Configuration 1 (Stacked Unit) – Configuration 2 (Stacked Unit) – Mechanical room favorite. Reduced footprint with tiered Ultra-quiet design with plenum fan and U-shaped supply fan cabinet AT DP FS TN TN VC XA HC FM FS XA EH XA RF MB Configuration 3 – Minimum frills. Maximum IAQ FS CC XA HC FF MB Configuration 4 – Exhaust air flexibility with gas-heat and humidification DP HM XA IG XA FS CC AF EE FE Configuration 5 – Cooling-only lab design with HEPA filtration DP HF XA DI FS CC RF MB Configuration 6 – Classic hospital design with return fan economizer operation. DP RF XA DI FS CC XA HC AF EE FR JOHNSON CONTROLS 5
FORM 102.20-QG1 (808) GENERAL INFORMATION Flexibility of Design Component Flexibility Solution AHUs offer the ultimate in dimensional, mate- AHUs are responsible for providing rial, and component flexibility. Solution AHUs have the the environment with quality indoor same appeal for both “standard” and “custom” markets. air, in an energy efficient and quiet How an air-handling unit is designed and built deter- manner. Solution AHUs help meet mines how well it performs. that responsibility by offering every available component, from energy Engineering Flexibility wheels to air-monitoring stations to specialty-purpose filters. As • Variable cabinet dimensions technology creates new capabilities, Johnson Controls/ • Material and component flexibility YORK will apply these to our Solution line. • Full line of factory packaged controls installed, Superior Casing Performance tested and commissioned by Johnson Controls The foam injected panels of our Solution air handling certified technicians units enhance performance, maximizing the indoor air • Variable sized inlet and discharge openings quality and help to create ASHRAE 62-2000 compliant designs while reducing costs. The direct result of the • Indoor and outdoor constructions foam injection insulation is a rigid panel, low leakage, • Tiered (stacked) and custom configurations high pressure air handler, with increased energy sav- ings, and reduced initial cost. Better IAQ Deflection presents a potential in leaks that form over time from the operational pressure. The foam injected Solution panels are 20% more rigid (L/240 vs. L/200) then the typical fiberglass or foam board construction. In addition the smaller deflections can be achieved using lighter sheet metal gauges then required by fiberglass construction. The result is a lower initial cost unit with greater performance. Lower leakage reduces the infiltration of unfiltered and unconditioned air into the space. The infiltration of un- • Panels are individually removable without affect- conditioned air can lead to condensation in unit walls, ing structural integrity. crevices and/or insulation. When the infiltration occurs in a negative pressure atmosphere downstream of the Dimensional Flexibility filter, it will lead to unfiltered air being supplied to the space. Maintaining a low leakage for positive pressure You can design Solution AHUs to fit the application and segments reduces the loss of conditioned air to a po- the space. Length, height and width can all be varied tentially warm and humid ambient environment, causing to match building constraints. With hundreds of cross- increased condensation. Condensation can lead to sectional possibilities, you choose the best match for the premature corrosion as well as IAQ concerns. application. In addition, all Solution AHU components have been designed with a variable-aspect ratio to meet The Solution foam injected wall panels help to seal and your space and air-velocity requirements. maintain the leakage at maximum of 1% with a minimum +/-8” of static pressure. Options for a maximum leakage Material Flexibility rate of 1/2% at a minimum of +/-10” of static pressure are available for those projects which demand it. A complete line of construction materials are available, including galvanized steel, aluminum, painted steel, Coil carryover, humidification, and periodic wash downs stainless steel, and more. Solution AHUs can handle are all instances where water is present in the unit. a multitude of environments, from the most benign to Foam insulated panels will not absorb, and retain water, the most corrosive. NOTE: All units/unit segments are like a fiberglass insulated panel will. In addition the ther- shrink-wrapped to protect unit from contamination dur- mal properties of foam are not degraded by an incident ing shipping where the insulation comes in contact with water. 6 JOHNSON CONTROLS
FORM 102.20-QG1 (808) Energy Savings Factory Installation The energy savings associated with high performing air Factory installation improves quality and saves time. handler construction is directly associated with leakage While a Solution AHU is being manufactured, Johnson and insulating properties. Controls technicians can easily access all its segments. So there are no accessibility problems to cramp the The infiltration of unconditioned air downstream of a coil, quality of the controls installation, which often occurs or the loss of conditioned air downstream of a coil are on the jobsite. just two examples of reduced energy efficiency in an air handler. The foam injected panel helps to reduce both All sensor probes have been pre-engineered to deter- of these potential losses by creating a more rigid, lower mine the best mounting location, ensuring accurate and leakage air handling over the life of the unit. reliable readings. Another form of energy loss associated with air handlers This improves performance of the unit while eliminat- is the thermal energy that is lost through the cabinet of ing unwanted air leakage common in field-mounted the air handler. The Solution foam injected panels lower solutions. energy consumption with better insulating properties. With the standard R-12.5 and optional R-18.8, or R-25, Factory engineering speeds field connections the Solution can help to reduce the energy usage. The The goal is to provide injected panel provides additional thermal advantages in you with an AHU that that the foam will fill voids, and gaps that aren’t reached simplifies field connec- with fiberglass or foam board type constructions. tion of the controls. For Solution air handler units are capable of being factory example, coil valves tested to prove out both leakage and deflection. With are shipped uninstalled, the Solution product it’s not all about construction, it’s but pre-wired with quick also about performance. connects. If an AHU is too large to ship in one Pre-engineering Packaged Controls piece, you can still count Pre-engineering of sensors ensures the most accurate on fast and easy assem- performance. There are great advantages to selecting bly of Metasys controls factory mounted and wired end devices for your Solution because labeled quick connects come standard on all air handling units. shipping splits. 1. Factory mounting maintains leakage performance Customized variable size openings 2. Factory wiring is plug and play Solution offers the most comprehensive option for facto- 3. Factory testing of each mounted and wired device ry provided openings. Custom size, custom location and custom shapes along with custom sized dampers,are 4. Factory generated control diagrams specifically designed to lower installation costs and risk while dra- for each unit matically improving the quality of the application and performance of the air handler. DP FS EE EE FR IP Literature Reference — see Application Guide ‘Applying VSO Option to Solution Air Handling Units’ - Form 102.20-AG14 JOHNSON CONTROLS 7
FORM 102.20-QG1 (808) GENERAL INFORMATION Airflow Measurement Performance air-flow station offered for air handling units which is in- corporated into mixing box and economizer segments to Solution AMS-60 qualifies to bear the AMCA Ratings meet the most stringent ASHRAE 90.1 requirements Seal for Airflow Measurement Performance. Ventilation air flow can be controlled dynamically with the Solution There are 3 damper options to give various measure- AMS-60 which is tested to AMCA Standard 611-95. ments of air flow. See FIG. 1. The Solution AMS-60 continues to be the best integral NOTE: Dampers are split vertically VIEWED FROM 25% 25% TOP 100% 75% 75% FIG. 1 – DAMPER OPTIONS Literature Reference — see Application Guide ‘AMS60 for use with Solution AHU’ - Form 102.20-AG1 State-of-the-Art Certification & Testing • ASHRAE 90.1 compliant Solution Air Handlers are subject to stringent testing using certified, comprehensive and industry recognized • ASHRAE 62 compliant coil and drain pan design testing laboratories. Testing is in accordance with ARI maximizes indoor air quality Standard 430 which evaluates the performance of the • Outstanding thermal capacity proven through entire unit. This assures that each Certified Solution unit independent testing will indeed perform with certainty and reliability. • HEPA filtration system exceeds the most stringent Solution AHUs have also undergone extensive and rigor- military DOP tests ous testing to verify conformance with all U.S. and Cana- dian safety standards, and they bear the ETL Label. • AMCA 611 certified airflow measurement stations Extensive testing includes: • ISO Quality Certification • ARI 430 certified performance • Seismic certificate of compliance • ARI 260 sound data Labeled Solution units are tested and listed by ETL in accordance with UL 1995, Standard for Safety Heating • Full line of ARI 410 certified coils and Cooling Equipment, and thereby fully complying • ETL listing for product safety per UL 1995 with NFPA 90A material requirements. New Sound Testing Laboratory our customers will continue to obtain the best available Solution sound data in the marketplace. The new AHU laboratory at the Johnson Controls Grantley Park Tech Center includes the capability for This facility will be the largest AHU sound test facility in sound power measurements on Air Handling Units up to the world. Note that in order for a laboratory to measure 100,000 CFM in accordance with ARI 260. The facility ARI 260 sound data, the laboratory must be pure tone will also include the capability for testing unit airflow in qualified to 50 Hz. This facility will be pure tone quali- accordance with AMCA 210 to 100,000 CFM. For fan fied to 50 Hz. Pure tone qualification ensures that the alone testing, the facility will also have AMCA 300 and test facility is capable of accurately measuring a noise AMCA 210 accreditation. All of this capability will be source producing tones – such as a fan. Not qualifying available for product development testing and for cus- the facility for pure tone response could lead to errone- tomer witness testing on critical projects. This facility ous results with a tonal noise source. This is why ARI will allow verification and calibration of sound models requires pure tone qualification of reverberation rooms in used for unique features of Solution units, which will the HVAC industry for anything other than VAV boxes. increase the accuracy of our predictions and ensure that 8 JOHNSON CONTROLS
FORM 102.20-QG1 (808) Quality Construction Equals Improved IAQ states that “The drain pan outlet shall be located at the lowest point(s) of the pan.” Quality construc- tion is a key to a Solution units remove the condensate with a multi-sloped minimum amount of drain pan that ensures positive drainage. Our pan design AHU leakage. Leak- also offers the highest level of accessibility for periodic age is an adversary cleaning, now required by ASHRAE Standard 62. of indoor air quality. It will depreciate the Raceways quality of the supply Raceways are used as the exterior skeletal construction air by allowing dirty, of Solution. unfiltered air to seep into the air-stream • Raceways provide the form and shape as well as downstream of the structural support for panels, base and internal. filters. • Raceway material is Galvanized To prevent this leakage, the rigid, thermally superior Solution is offered with a full-perimeter base-rail with panels of Solution AHUs are matched with a rugged integral lifting lugs. framework to provide an extraordinary casing perfor- mance. • Optional base-rails The maximum allowable air leakage is less than 1% at • Lifting lugs are provided +/- 8" w.g. and a maximum L/240 deflection. as necessary for material handling The Shell of Solution is made up of double wall panels and doors. A ‘Curb Rest’ is provided to direct, guide and indicates align- • Standard liner material is galvanized ment when setting a unit on the • Stainless liners are optional curb. • Perforated aluminum liners are optional • Galvanized steel strip at- tached to the raceway or The floor is a double wall construction, with a galvanized base-rail steel walk-on surface. • ‘Curb Rest’ is not to be • Optional stainless steel considered a flashing • Optional aluminum tread plate receiver for the curb. Multi-Sloped Drain Pans Improve Cost Savings The way to control micro-organisms, which can flourish Solution UV-C light options in drain pans, is to control the moisture of cooling-coil eliminate the potential for a build-up of microbiological condensate which can remain in the pan during “off” or agents. “heating” cycles. 1. Heat exchangers continue to operate at high- Poorly designed drain pans efficiency levels due to sustainable, like-new, are often breeding grounds reduced pressure drop. for mold and poor IAQ. 2. HVAC equipment operates for shorter periods of ASHRAE 62-2001, section time saving cost on electricity. 5.11.1 states that drain pans “...shall be sloped at least 3. Improved IAQ as the first line of defense against 1/8" per foot from the hori- sick building syndrome. zontal toward the drain outlet Installation of UV-C lamps promotes a cleaner, healther, whether the fan is in the on or more productive work environment. off position.” Section 5.11.2 More detailed information on page 57 of this manual. Literature Reference — see Application Guide ‘Solution IAQ Series General AHU Construction’ - Form 102.20- AG3 JOHNSON CONTROLS 9
FORM 102.20-QG1 (808) GENERAL INFORMATION A Complete Line of Filters A complete line of clean air solutions for industrial plants, hospitals, schools, pharmaceutical process, airports and commercial buildings are available to control or remove airborne contaminants from the air stream. Achieving acceptable indoor air quality is more involved than calculating and applying the appropriate ventilation rate. Specific AHU performance and other common sense specification items, tied to ASHRAE 62.1 rec- ommendations, can help achieve the healthy indoor air quality environment desired. Light pre-filtering duty: Stringent filtration requirements: Odor or VOC removal – pleated – HEPA – Activated carbon – extended surface – Ultra-HEPA – 17 to 18 MERV Air purification systems Higher filtration efficient – 0.3 & 0.1 microns respectively High-performance – 60% to 95% – 99.97% & 99.99 % effectiveness – Near-HEPA performance – 11 to 14 MERV – Germicidal capability – rigid & bags – Low-resistance-to-airflow (initial pressure drop equal to a low-end pre-filter). Energy-Saving Fan Options Economizers (EE) provide an exhaust path for return air, allowing the outdoor air conditions, when suitable, In any AHU, the fan is the largest energy consumer. to take advantage of 100% outside air for “free” cooling, Solution fans offer a range allowing the chillers to be turned off a percentage of the of energy-saving options time during the cooling season. Return and exhaust through fan types and con- fans are available to meet the needs of varying building trols. pressurization requirements. – Light aluminum fan wheels – Direct-drive plenum fans, which eliminate belt-and-pulley energy losses To assure the quietest possible operation, fans and motors are common base isolated from the cabinet. Literature Reference — see Application Guide ‘Solution - Reducing AHU Energy Consumption’ - Form 102.20- AG13 10 JOHNSON CONTROLS
FORM 102.20-QG1 (808) Energy Consumption Rearranging Equation 1 to solve for duct leakage class: The HVAC industry has taken a leadership role by creat- Eq. 2 CL = Lmax/P0.65 ing energy-performance guidelines, such as ASHRAE CL = (0.5 cfm/ft2 x 100 ft2)/50.65 90.1. Solution AHUs are designed with ASHRAE 90.1 CL = 17.6 in mind. In extreme ambient conditions, heat transfer through According to this, regardless of unit size or capacity, the casing must be controlled. Solution casing offers this type air-unit is roughly equivalent to a SMACNA maximum thermal performance in the floors, walls and leakage class of 18. roof. To prevent energy-robbing air leaks, Solution units are designed for a maximum casing leakage of less Analyzing Solution units is a little more complex than than 1%. analyzing the other typical unit, since Solution strives for a maximum leakage rate of 1% of the unit design airflow at ± 8 in-w.c. That means that the leakage in cfm/100 ft2 of unit casing varies based on the size and capacity of the unit. A 4,000 cfm Solution unit will have a maximum leakage rate of 40 cfm, whether the unit is 8’ long or 10’ long. Therefore, the 10’ long unit will have an inherently lower cfm/100 ft2 leakage rate than the 8’ long unit, as shown in Table 1. For every 1% of air leakage at the AHU, 1% more air Table 1. Comparative Solution Leakage Rates must be conditioned, and 1% more energy is con- Unit CFM: 4000 4000 16000 16000 32000 32000 sumed. H (Inches) 36 36 66 66 114 114 W (inches) 54 54 96 96 102 102 Comparing Apples-to-Apples L (inches) 98 124 105 132 125 150 Competitors claim “Air leakage rates between 1/2 and Area (ft2) 150 182 324 385 537 612 1 percent” on their AHUs, but they don’t mention at what 1% Leakage (cfm) 40 40 160 160 320 320 pressure this performance is achievable, nor do they Leakage (cfm/ft²) 0.27 0.22 0.49 0.42 0.60 0.52 even specify a leakage rate for the air units. Using the Solution performance at ± 8 in-w.c. we can use This typically makes it difficult to analyze their leakage the SMACNA leakage class as a standard comparator. performance by not qualifying it based on air pressure. By plugging the values from Table 1 into Equation 2, we However, if we reference to SMACNA class 3 air leakage find the leakage class for the various Solution units as this is a good place to begin our analyses. shown in Table 2. SMACNA class 3 refers to a standardized method Table 2. Solution AHU Leakage Classes of classifying duct leakage. While this classification Unit CFM: 4000 4000 16000 16000 32000 32000 doesn’t technically apply to AHUs, it is a useful method of comparing the performance claims of different manu- Leakage (cfm/ft²) 0.27 0.22 0.49 0.42 0.60 0.52 facturers. According to SMACNA Duct Leakage Test Leakage Class 7 6 13 11 15 14 Procedures (1985), duct leakage is calculated using at ± 8 in-w.c the equation: Eq. 1 Lmax = CLP0.65 Even on large AHUs, the leakage class of a Solution unit is lower than that of most competition. Many design where, engineers don’t realize this, because when they compare YORK’s performance to others they aren’t comparing Lmax = maximum permitted leakage in cfm/100ft2 duct surface area; apples-to-apples unless the performance is translated CL = duct leakage class, cfm/100ft2 at 1 in-w.c. into the common language of leakage class. P0.65 = test pressure in in-w.c. Literature Reference — see Application Guide Form 102.20-MG1. See also M-42-06. JOHNSON CONTROLS 11
FORM 102.20-QG1 (808) GENERAL INFORMATION EPAct Efficient Performance Consumption of energy can also be reduced by more efficient motors. Solution AHU motors meet EPAct efficient performance standards for general purpose motors. Standard Solution EPAct efficient and Premium- efficiency motors can be specified and used with fre- quency control as listed by NEMA Standards Publication MG 1-2006 (Motors and Generators): • MG 1-2006 Part 30 Application Considerations for General Purpose Motors used with Adjustable - Voltage OR Adjust- able - Frequency Controls or Both • MG 1-2006 Part 31 Definite-Purpose Inverter-Fed Poly-phase Motors Literature Reference — see Application Guide ‘Solution Air Handling Units AC Induction Motor Data’ - Form 102.20-AG15. Energy Saving Air-Modulator™ 3. Eliminates need for motor When the air system is de- starter panels. signed for variable-air vol- 4. Improved system control ume (VAV), Solution offers and response – DDC the most efficient method of controls with LED digital VAV fan control with our Air- display. Modulator™ drive, which is mounted, wired and tested in 5. Proven reliability. our factory. Fans characteristically require Typically HVAC systems consume much less power as the speed a third of the energy used in com- is reduced. With the Air-Modulator™, any reduction in mercial buildings. Therefore an fan speed results in a cubic reduction in fan horsepower. energy-efficient HVAC system can For example, a 10% speed reduction results in a 27% represent a significant savings in fan horsepower reduction! building operating costs. ASHRAE Air Modulator benefits include: 90.1 provides architects and engi- neers with guidelines for the design 1. Extended Equipment Life – soft start of motor and of energy efficient buildings, with fan. the exception of low-rise residential 2. Quieter Fan Operation – buildings. fan operating at reduced speed and constant line of efficiency. Literature Reference — See Application Guides ‘ASHRAE 90.1 Guidelines’ – Form 102.20-AG2 & ‘Understand- ing AHU Casing Leakage’ – Form M-42-06 12 JOHNSON CONTROLS
FORM 102.20-QG1 (808) Sound Attenuation What little noise is left can be further reduced with direct methods of sound An important component of indoor environmental qual- attenuation. Using ity (IEQ) is acoustics. There are very few constants perforated sound- when it comes to acoustics, however it is always less absorbing walls as expensive to design and install a system correctly the sound traps in the first time than it is to make the system quiet after it is fan and discharge- installed. The best way to reduce noise is not to create plenum sections, it in the first place. Johnson Controls/ ARI 260 requires that the unit be rated across its entire YORK equipment operating range according to the AMCA 300 test method. engineers can help Johnson Controls/YORK has been and continues to be you design units fully engaged in a rigorous ARI 260 testing program. to meet your criti- Solution testing includes a wide variety of fan types, cal sound require- unit sizes and configurations. As a result, Solution can ments. with assurance say sound power levels are reported in accordance with ARI 260. Inertia Base Solution AHU offers a variety of noise-reducing tech- A concrete inertia base, which is inserted between the nologies. fan and its supportive structure, can be quickly and eco- Solution AHUs are available nomically installed in all Solution unit cabinet sizes. with a nearly endless array – Inertia fan bases will accommodate both belt of fan types, all custom driven and direct drive fans selected for the exacting requirements of your project. – The added mass of the inertia base allows for a Direct drive plenum fans softer isolation system and greater isolation ef- can reduce vibration and ficiencies as well as an effective means of damp- drive noise by eliminating ening mechanical noise. the belt-and-pulley mecha- – Concrete fill is furnished by contractor. nism. A range of fan-base construction and isolation techniques are available to help control sound. SOUND ATTENUATION Source attenuation is the first sound-re- duction method that should be consid- ered, and is typical- ly least expensive. Since the fan is the primary moving part in an air-handling system, it’s the first RACEWAY ASY place to look when reducing noise. Application Note - As a rule of thumb the inertia base BULKHEAD ASY should be used when: • Class II & III fans with 40” diameter wheel or larger • All centrifugal fans driven by motors of 75HP or larger JOHNSON CONTROLS 13
FORM 102.20-QG1 (808) GENERAL INFORMATION Quick Selection The Quick Selection Guide for the Solution AHU was developed and intended to aid the Consulting Engineer, Ar- chitect, Design/Build Contractor, and Equipment /Controls Engineer in establishing overall estimates for (minimally) footprint dimensions, unit weight, & max motor horsepower. Contents consist of: – Applications, Features & Benefits – Instructions – Data – Notes – Reference Formulas and Conversions Literature Reference — See Quick Select Tool – Solution Slide Chart – Form 102.20-SC1 14 JOHNSON CONTROLS
FORM 102.20-QG1 (808) FAN APPLICATION REVIEW Fan Laws (Recommended Accepted Practice) System curves will always have a square function slope (parabola) because the SP varies as a square of the The fan laws are used to calculate performance char- CFM. The point where the system curve intersects the acteristics; fan speed (RPM), fan air capacity (CFM), RPM curve is the operating point of the fan (point A). static pressure (SP) and brake horsepower (BHP) of If the system resistance changes (i.e., dirty filters or a particular fan at conditions other than those at which change in ductwork), the operating point will move along the data was taken. the RPM curve to a different operating point and there- By using the fan laws in conjunction with a fan curve, the fore, new system curve (point B). With a fixed system, fan performance can be calculated accurately at various the effects of change in RPM, air density of BHP can operating conditions. Every fan has its own unique fan be calculated and plotted on the system curve by using curve. FIG. 2 shows a fan curve at various RPMs. the following fan laws: The system resistance curve relates the total pres- • The CFM varies directly with the RPM: sure loss in an air handling system to the flow rate of RPM2 air through the system. The system curve is unique to CFM2 = CFM1 x each system because it expresses the pressure losses RPM1 associated with the system. (AHU cabinet, coils, filters, supply and return ductwork, grilles and diffusers).The • The SP varies as a square of the RPM: SP and CFM values are used to create the system curve for the particular system. FIG. 3 represents a fan curve RPM2 2 SP2 = SP1 x with 2 system curves identified. RPM1 PEAK EFFICIENCY LINE 9 75 M • The BHP varies as a cube of the RPM: AX .H P 8 50 15 13 HP 00 00 RP RP RPM2 3 M M 7 40 HP BHP2 = BHP1 x 60 RPM1 HP STATIC PRESS. – (IN. WG) 6 11 30 00 HP RP M 5 900 RP • The SP and BHP are directly proportional to the 25 M HP 4 20 HP air density: 3 10 HP 10 70 HP 0R 7.5 HP PM Density2 RPM2 2 2 SP2 = SP1 x x Density1 RPM1 1 50 0R PM Density2 RPM2 3 BHP2 = BHP1 x x 50 100 150 200 250 300 350 400 450 500 550 600 650 700 Density1 RPM1 AIRFLOW – CFM (100) FIG. 2 – CURVE AT VARIOUS RPMs The fan laws can only be used to project performance PEAK EFFICIENCY LINE along a specific system curve. Referencing FIG. 3, Point 9 1300 A can be used to project the performance of Point C and 1500 similarly, Point B can be used to project the performance 8 75 MAX. HP of Point D. Point A cannot be used to predict any other 7 point on the RPM curve, it can only project performance 1100 on the system curve created by Point A. STATIC PRESS. – (IN. WG) 60 6 50 B 5 40 900 30 4 A 25 20 D 3 2 em st Sy 700 15 1 2 ste m Sy 500 10 1 7.5 50 100 150 200 250 300 350 400 450 500 550 600 650 700 AIRFLOW – CFM (100) FIG. 3 – FAN CURVE WITH TWO SYSTEM CURVES JOHNSON CONTROLS 15
FORM 102.20-QG1 (808) FAN APPLICATION REVIEW Variable Air Volume A common mistake when selecting a fan with variable Select the most efficient fan that can deliver both the air volume is to assume a fan with VAV will follow a design and minimum CFM requirements. If the initial constant design system curve (passing through the point selection does not provide sufficient “turn down”, select 0 CFM and 0 TSP) to maintain control. VAV systems the next smallest fan and re-plot the VAV system for the do not have a constant system line, but rather a range smaller fan and re-evaluate. Typically, the largest fan that of operating points necessary to satisfy the building can supply the required modulation is the most efficient. requirements. In VAV systems, the operating point will Each application should be considered individually and continue to move based on the air modulation and as evaluated to be sure the fan will not be forced into the the CFM and SP change, the fan is modulated to match unstable region at modulated condition. the new requirements, developing its own system curve. For variable speed drive (VSD) applications, the fan This modulation is accomplished by using inlet vanes, drive assembly is selected to operate approximately in variable speed drives or discharge dampers. Before the middle of the VSD’s range. When selecting a fan to finalizing the fan selection, plot the new VAV system be used with a VSD, if the RPM is close to or approach- curve to confirm the modulation range required does ing the Class I limit, select the Class II fan. Selection of not enter into the instability range of operation. a Class I fan may result in premature bearing failure. Example Calculate the minimum CFM and at least 2 arbitrary points which fall within the stable operating range of the curve (using equations below) and plot these points along with the design points to create the new VAV system. (See FIG. 4.) Design CFM = 40,000 CFM = CFMd Design TSP = 4.5 in WG = SPd Static Pressure Control Point = 1.25 in WG = SPd 1st: Calculate the Minimum CFM: SPS 1.25 Min CFM = CFMd x = 40,000 x = 10,517 2 CFMd 40,000 2 √ SP1 x CFM1 + SPS – SPd √ 3 x 15,000 + 1.25 – 4.5 where: CFM1, SP1 = arbitrary point located on surge line Min CFM = 10,517 2nd: Calculate the Arbitrary Points: 30,000 CFM 20,000 CFM where: CFM2 = 30,000 where: CFM3 = 20,000 CFM2 2 CFM3 2 SP2 = x (SPd – SPs) + SPs SP3 = x (SPd – SPs) + SPs CFMd CFMd 2 30,000 2 20,000 SP2 = x (4.5 – 1.25) + 1.25 SP3 = x (4.5 – 1.25) + 1.25 40,000 40,000 SP2 = 3.1 SP3 = 2.1 16 JOHNSON CONTROLS
FORM 102.20-QG1 (808) PEAK EFFICIENCY LINE 9 8 15 13 00 00 R RP PM M 7 1100 RPM STATIC PRESS. – (IN. WG) 6 75 M AX .H P 5 . Pt 30 n HP sig 25 De 300 HP RPM 4 50 60 40 20 HP HP HP HP 3 10 HP 2 Static Pressure Control Point 1 MODULATION RANGE Minimum CFM Design CFM 50 100 150 200 250 300 350 400 450 500 550 600 650 700 AIRFLOW – CFM (100) FIG. 4 – FAN CURVE AT VARIOUS RPMs Solution Component Temperature Margins • Pre-filters - 150°F. • Standard motors (Class B Insulation) -104°F. • High Efficiency Filters - 200°F. • Motors with Class F Insulation -140°F. • Fan Bearings - 120°F (FC), 180°F (AF) • Power Wiring - 140°F. • Gasketing - 200°F • Controls & Control Wiring - 140°F. • Foam - Flash Point: 415°F (213°C) Fan Motor Heat (MBH) HEAT Horsepower 5 7.5 10 15 20 25 30 40 50 60 75 100 Fan Motor 2.8 3.6 4.4 6.2 7.5 8.7 9.4 13.0 16.0 19.0 21.0 25.0 Fan 12.7 19.1 24.5 38.2 51.0 63.6 76.3 102.0 127.0 153.0 191.0 254.0 Fan & Fan Motor 15.5 22.7 28.9 44.4 58.5 72.3 85.7 115.0 143.0 172.0 212.0 279.0 JOHNSON CONTROLS 17
FORM 102.20-QG1 (808) COIL OPTIONS Flexibility and Performance illustrate the variety of coils Coil Performance is certified in accordance with ARI which are available to meet every application. These Standard 410. 1/4" FPT PLUGGED carefully engineered coils are designed for an optimum VENT FITTING Chilled water / Hot water balance between air pressure drop and heat transfer coefficient, to allow the maximum amount of cooling or heating capacity without the added expense of high air-pressure drops. The coil designs are subjected to constant extensive evaluation studies comparing dif- ferent fin corrugations with various tube arrangements. The Johnson Controls/YORK Equipment Engineer in your area will welcome the opportunity to assist you RETURN SUPPLY with your coil applications. Cooling Coils – Water and Direct Expansion Direct expansion (DX) SUPPLY RETURN Solution optimizes coil performance with customized coil options. Solution coils are offered in a wide variety of types, sizes, arrangements and materials. Coil software optimizes capacity and pressure drop requirements. AHU Chilled water cooling coil • Available in CC, VC, MZ segments AHU Hot water heating coil • Available in CC, VC, HC, MZ segments AHU (DX) Direct Expansion cooling coil • Available in CC, VC, MZ segments Notes & Options Hand of Unit determines connection side of coil. See page 21. Header material: Fin Spacing: • Copper • A vast range of fins per inch available • Red Brass Fin Coatings: (Coatings reduce max face velocities) Connector material: • Electro-fin • Red brass • Phenolic • Steel Coil Casing: Connection Type: • Galvanized • MPT • Stainless Steel • Grooved Choice of heat transfer medium: Fin type: • Water, Glycol (Ethylene glycol coils are ARI • 5/8” tube: Sine or Flat certified) • 1/2” tube: Sine corrugated only • DX – (a variety of refrigerants to choose from) Fin Material & Thickness: • Aluminum - 0.006”, 0.008”, 0.010” • Copper - 0.006” 18 JOHNSON CONTROLS
FORM 102.20-QG1 (808) Heating Coils – Integral face and bypass Integral face and bypass coils have alternating channels Steam or Hot Water of heat transfer surface and bypass zones. The air flow is directed over the heat transfer surface or through the by-pass zone by modulating dampers that are integral with the coil construction. Integral face and bypass coil (IFB/VIFB) • Coils are available in the ‘IC’ segment • Tubes either Vertical or Horizontal • Coils for maximum freeze protection INTEGRAL FACE & BYPASS (IFB) COIL • Hot water or Steam coils • Multiple rows deep Notes & Options Coil Style: Rows: Fin Material: • IFB • 1,2,3,4 • Aluminum • VIFB Connection: Fin Spacing: Coil Type: • SCH 40 pipe • A range of fins per inch available • Water (Glycol) Thermostat: Coil Casing: • Steam • None • Galvanized • Electric Heating Coils – Steam Distributing The construction of a Steam Distributing Coil is entirely Steam Distributing - 1” diameter tube different than that of a Standard Steam. • Available in CC, VC, HC, MZ segments Everyplace that you see an outside tube or header, there is an inside tube and header that you can’t see. Steam is • A vast range of fins per inch available distributed through these inside tubes and headers and • Multiple tube wall thickness options slowly released to the outside tubes as the steam turns to condensate. The condensate then flows back down Steam the outside tubes in the same direction that the entering steam comes from. The idea is that all the steam in the inside tubes keeps the condensate in the outside tubes from freezing when air passes across the coil at less than 32ºF. However, under exactly the correct conditions, even steam distributing coils can freeze. JOHNSON CONTROLS 19
FORM 102.20-QG1 (808) COIL OPTIONS Typical Application of Air Handling Coils solenoid valves in the refrigerant liquid lines, which are energized to shut-off the flow of refrigerant to part of the Heating Coils coil. There are several problems with the application of VAV to a direct expansion (DX) coil which require the Heating coils can use steam or hot water to add heat designer to take special precautions when considering to the air stream. In a cooling-only VAV system, the this system. First, the balance point temperature for heating coil is generally placed in the ‘preheat’ position the DX coil will change as the air flow rate changes. between the filters and cooling coil. The preheat coil Assuming constant coil capacity, reducing the CFM will can be omitted in this system if the minimum outside reduce the suction temperature and pressure, making air requirement is low and would not result in a mixed close control of air temperature difficult. In addition, air temperature below 50ºF to 55ºF. compressor unloading at reduced load will cause step Heating coil capacity is controlled by means of a modu- changes in capacity and suction temperature, which lating control valve in the water or steam piping. The can cause hunting in the flow control loop. In short, the control valve position is usually controlled by means of use of variable air flows with a DX coil requires careful a thermostat in the supply air duct in sequence with the consideration of the effect air flow changes make to the cooling coil control valve. system. Balance point temperatures must be carefully considered. Cooling Coils Design Considerations Cooling coils remove both sensible and latent heat from the mixed air and can use chilled water, chilled brine, or In order to insure predicted coil performance, air distri- refrigerant as the cooling source. In the case of chilled bution must be uniform. There are two design checks water, the supply water temperature generally ranges for this: from 42ºF to 50ºF, depending on the latent load to be 1. ‘45 degree rule’ – This rule states that the perfor- removed. Brine or a solution of ethylene or propylene mance of the coil will not be affected as long as the glycol in water is traditionally used at temperatures of diffusion angle from the most restrictive block-off to 32ºF to 40ºF for applications in which piping is exposed the finned portion of the coil is 45 degrees or less. to freezing temperatures. Control of the cooling coil ca- This rule holds true unless there are unusual flow pacity at the air-handling unit is achieved by means of fields, caused by such components as upstream a two-way ‘throttling’ or three-way ‘mixing’ control valve. fans or mixing boxes where not applied properly. In VAV systems, a supply duct thermostat is typically used to modulate the control valve so as to maintain 2. ‘Uniform pressure rule’ – This rule states that the a constant temperature of air leaving the unit, usually performance of the coil will not be affected as long as 55ºF to 60ºF. the maximum difference in upstream, downstream, and combined static pressure due to local velocity When refrigerant is used as the cooling source, it enters pressure at any one point on the coil compared to the coil in liquid form from a condensing unit and pro- another point that does not exceed 10 percent of vides cooling by a process called ‘direct expansion’. The the pressure drop through the coil. The basis for liquid refrigerant evaporates as the warmer air moves this rule is that the flow rate through the coils at any across the coil, removing heat from the air during the one point is a function of the local upstream and process. The evaporated refrigerant is then compressed downstream pressures, and if pressure differences in the condensing unit, which also houses the condens- are small, distribution will be uniform. ing coil where the heat is rejected to the outside. Control of the coil capacity is typically by means of a series of Literature Reference — See “DX Piping Guide” – Form 050.40-ES2 20 JOHNSON CONTROLS
FORM 102.20-QG1 (808) SOLUTION SEGMENT IDENTIFICATION FAN SEGMENTS HEAT SEGMENTS ACCESSORY SEGMENTS • FS – Supply • IC – Integral Face & Bypass Coil • VP – Vertical Plenum • Forward Curved • IG – Indirect Gas Fired Furnace • DP – Discharge Plenum • Airfoil • EH – Electric Heater • TN – Turning Plenum • Industrial Airfoil • DI – Diffuser • SWSI Plenum ENERGY RECOVERY • XA – Access segment (Belt and Direct Drive) • ER – Energy Recovery • AB- Air Blender • FR – Return • EB – External Bypass • Forward Curved FILTER SEGMENTS • IB – Internal Bypass • Airfoil • FF – Flat Filter (2” or 4”) • FD – Face Damper • Industrial Airfoil • AF – Angle Filter (2” & 4”) • AT – Attenuator • SWSI Plenum • RF – High Efficiency Filter • HM - Humidifier (Belt and Direct Drive) • Rigid Filter (12”) • UV - UVC Lamps • FE – Exhaust • Bag Filter (21”) • Forward Curved • Mini-Pleat Filter (4”) • Airfoil • HF – HEPA Filter • Industrial Airfoil INLET SEGMENTS COIL SEGMENTS • MB – Mixing Box • CC – Cooling Coil • FM – Filter/Mixing Box • HC – Heating Coil • EF – Filter/Economizer • VC – Vertical Coil • EE – Economizer • MZ - Multizone • IP – Inlet Plenum • VE – Vertical Economizer • VF – Vertical Filter/Economizer Unit & Coil Hand Identification FAN SECTION RIGHT REAR RIGHT HAND (RH) COIL CONNECTION LEFT HAND (LH) COIL CONNECTION RETURN AIR OUTSIDE AIR LEFT INLET SECTION DRIVE HAND AND COIL HAND DETERMINED BY FACING THE INLET SECTION FRONT JOHNSON CONTROLS 21
FORM 102.20-QG1 (808) SINGLE FAN SEGMENT – FS, FR AND FE Fan Applications Fan segments are available as supply, return and or exhaust applications. Unit configurations have a segment op- tion of utilizing a single fan or a dual fan arrangement. Isolation consists of 1" or 2" springs with a seismic snubber option. Thrust restraints and OSHA belt guards are available as required. Double-width/Double-inlet (DWDI) Bearing options for fans with lubricating bearings: (refer • Forward Curve or Airfoil centrifugal to Notes & Options) • Belt Driven • Extended Lube Line Single-width/Single-inlet (SWSI) • External Lube Line • Airfoil plenum • Belt Drive or Direct Drive In most fan systems a segment with a single fan is adequate for the required system design and rating. Methods of control can vary and may include dampers or variable speed drives. Also included in a single fan design may be the allowance for future expansions. In some situations, there may be a need for a system design using multiple fans in a cabinet. The following are some reasons to consider a dual fan arrangement: Dual Fan Considerations 4. Critical systems are often equipped with redundant or back-up fans in case of a fire or accident or some 1. One fan may be too large and not fit into the desired other emergency that requires a sudden increase in space, or it may weigh too much if supported on flow. Redundant fans are also used to eliminate down- upper levels. time during fan maintenance. 2. The required operating range of the system may 5. Some systems for process applications may require necessitate multiple fans instead of one large fan pressures that are greater than a single fan can pro- controlled over a wide operating range. duce or when noise may be a special concern. 3. Multiple fans for capacity control may be more eco- nomical if cost of operation is critical, especially at very low flow rates for long time intervals. Dual Fan Applications Solution dual fan application methods include 50/50 where both fans operate together to share the load equally or 100/100 where only one fan at a time is in operation. • In a 50/50 application, the failure of one fan will re- sult in a condition where the other fan will continue to operate. The single fan will provide partial load capabilities • In a 100/100 application, the failure of one fan will result in the operation of the other (standby) fan to provide full capacity Literature Reference — see Application Guide ‘AHU Dual Fan Options’ - Form 102.20-AG17 22 JOHNSON CONTROLS
You can also read