Installer's Guide Convertible Air Handlers
←
→
Page content transcription
If your browser does not render page correctly, please read the page content below
18-GJ06D2-2 Installer’s Guide Convertible Air Handlers 2 – 5 Ton TAM7A0A24H21SC TAM7A0C48H41SC Scan to see the TAM7A0B30H21SC TAM7B0C60H51SB TAM7 Trouble- TAM7A0C36H31SC shooting Video Library. TAM7A0C42H31SC ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES Important: This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work. Important: These instructions do not cover all variations in systems nor provide for every possible contingency to be met in connection with the installation. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to your installing dealer or local distributor. See the TAM7 Service Facts document for information on reading the Control Board LEDs, Air Flow Tables and Troubleshooting Flowcharts. Note: The manufacturer recommends installing ONLY A.H.R.I. approved, matched indoor and outdoor systems. Some of the benefits of installing approved matched indoor and outdoor split systems are maximum efficiency, optimum performance, and the best overall system reliability. Note: Condensation may occur on the surface of the air handler when installed in an unconditioned space. When units are installed in unconditioned spaces, verify that all electrical and refrigerant line penetrations on the air handler are sealed completely. The TAM7 air handlers will only use the following internal electric heaters: BAYEVAC05BK1AA BAYEVBC15BK1AA BAYEVAC05LG1AA BAYEVBC20BK1AA BAYEVAC08BK1AA BAYEVCC25BK1AA BAYEVAC08LG1AA BAYEVAC10LG3AA BAYEVAC10BK1AA BAYEVBC15LG3AA BAYEVAC10LG1AA Note: Duct heaters cannot be applied with this air handler.
Table of Contents Section 1. Safety Information........................................................................... 2 Section 2. Unit Design.......................................................................................... 3 Section 3. Unit Preparation............................................................................... 5 Section 4. Optional Cabinet Disassembly................................................. 6 Section 5. Place Unit at Location................................................................. 11 Section 6. Unit Location Considerations................................................. 12 Section 7. Setting the Unit - Vertical Installation.................................. 17 Section 8. Setting the Unit - Horizontal Installation........................... 19 Section 9. Connecting the Duct work........................................................ 20 Section 10. Refrigerant Line........................................................................... 21 Section 11. Refrigerant Line Brazing......................................................... 22 Section 12. Condensate Drain Piping........................................................ 25 Section 13. Electrical - Low Voltage............................................................ 27 Section 14. Electrical - High Voltage........................................................... 37 Section 15. Unit Outline Drawing................................................................. 39 Section 16. Filters................................................................................................. 40 Section 17. Start Up............................................................................................. 40 Section 18. Sequence of Operation............................................................ 42 Section 19. Checkout Procedures............................................................... 44 Section 1. Safety Information ▲! WARNING ▲! CAUTION SAFETY HAZARD! This information is intended for use CORROSION HAZARD! To prevent shortening its service by individuals possessing adequate backgrounds of electrical and life, the air handler should not be used during the finishing phases mechanical experience. Any attempt to repair a central air condition- of construction. The low return air temperatures can lead to the ing product may result in personal injury and/or property damage. formation of condensate. Condensate in the presence of chlorides The manufacturer or seller cannot be responsible for the interpreta- and fluorides from paint, varnish, stains, adhesives, cleaning com- tion of this information, nor can it assume any liability in connection pounds, and cement creates a corrosive condition which may cause with its use. rapid deterioration of the cabinet and internal components. ▲! WARNING ▲! CAUTION LIVE ELECTRICAL COMPONENTS! During instal- SAFETY HAZARD! Sharp Edge Hazard. Be careful of sharp lation, testing, servicing, and troubleshooting of this product, it may edges on equipment or any cuts made on sheet metal while install- be necessary to work with live electrical components. Failure to fol- ing or servicing. Personal injury may result. low all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Important: Panel damage can occur with prolonged exposure to POE lubricants. Air handler front panels ▲! CAUTION that come in contact with POE oil must be washed immediately with soapy water. HAZARDOUS VAPORS! Do not install an air handler with a non-ducted return in the same closet, alcove, or utility room as a fossil fuel device. Hazardous vapors can be distributed throughout the conditioned space and equipment damage can result. Note: Representative illustrations only included in this document. Most illustrations display the upflow configu- ration. 2
Section 2. Unit Design 2.1 Cabinet Penetration Important: Due to the unique design of this unit, which allows the electrical wiring to be routed within the insulation, do not screw, cut, or otherwise punc- Screws for flange kit attachment are allowed ture the unit cabinet in any location other than the along the interior of ones illustrated. the cabinet (see arrows) (Typical all sides) Screws are allowed up to 3- 3/4” Important: Under no conditions should metal strap- from the top of the cabinet (heater compartment). ping be attached to the unit to be used as support (Typical both sides) mechanisms for carrying or suspension purposes. No penetrations allowed. (Typical all sides) Screws, saw cuts, and other penetra- tions are allowed in the blower section for installation of Side Return Kit. (Typical both sides) Screws can be drilled into bottom of unit. Screws allowed only (1/2” max. screw in the first 3/4” of front length) bottom of unit (in (Typical all sides) cross member) 2.2 Panel Removal The unit contains four (4) access panels: Blower/Fil- ter, Coil, Line Set, and Heater. The Blower/Filter panel is removed using thumb screws. 1. Turn thumb screws on Blower/Filter panel. 2. Pull top of panel out, away from cabinet. 3. Lift panel up out of channel. 4. Set aside. 3
The Coil, Line Set, and Heater panels are removed using Phillips head screws. #3 Size Phillips Coil and Heater panels must be removed prior to re- moving the Line Set panel. To remove Coil Panel: 1. Turn screws on Coil panel. 2. Pull bottom of panel out, away from cabinet. 3. Pull panel down and out of channel. 4. Set aside. To remove Heater Panel: 1. Turn screws on Heater panel. 2. Pull panel straight out, away from cabinet. 3. Set aside. Removal of the Line Set panel is required for all refrig- erant line brazing and some condensate line assembly depending on your orientation. To remove Line Set panel: 1. Remove both Heater and Coil panels. 2. Turn screws on Line Set Panel. 2. Pull panel straight out, away from cabinet. 3. Set aside. NOTE: After replacing all panels, loosen the Line Set Panel screws approximately 1/4 - 1/2 turn. This will improve the seal between the Heater Panel and Line Set Panel. 4
Section 3. Unit Preparation 3.1 Prepare The Unit For Installation STEP 1 - Check for damage and report promptly to the carrier any damage found to the unit. Note: If the unit must be transported in a horizontal position, it must be laid on its back (marked “REAR” on carton). Note: After the unit is removed from the carton, depress the Schrader valve to verify coil is pressur- ized. 3.2 Unit Accessories Table 3.2 Accessory Number Description Fits Cabinet Size BAYEVAC05BK1AA Electric Heater, 5kW, Breaker, RS-485 Control, 1 Ph A to C BAYEVAC05LG1AA Electric Heater, 5kW, Lugs, RS-485 Control, 1 Ph A to C BAYEVAC08BK1AA Electric Heater, 8kW, Breaker, RS-485 Control, 1 Ph A to C BAYEVAC08LG1AA Electric Heater, 8kW, Lugs, RS-485 Control, 1 Ph A to C BAYEVAC10BK1AA Electric Heater, 10kW, Breaker, RS-485 Control, 1 Ph A to C BAYEVAC10LG1AA Electric Heater, 10kW, Lugs, RS-485 Control, 1 Ph A to C BAYEVBC15BK1AA Electric Heater, 15kW, Breaker, RS-485 Control, 1 Ph B to C BAYEVBC20BK1AA Electric Heater, 20kW, Breaker, RS-485 Control, 1 Ph C BAYEVCC25BK1AA Electric Heater, 25kW, Breaker, RS-485 Control, 1 Ph C BAYEVAC10LG3AA Electric Heater, 10kW, Lugs, RS-485 Control, 3 Ph A to C BAYEVBC15LG3AA Electric Heater, 15kW, Lugs, RS-485 Control, 3 Ph B to C BAYSUPFLGAA Supply Duct Flange A A BAYSUPFLGBA Supply Duct Flange B B BAYSUPFLGCA Supply Duct Flange C C BAYRETFLGAA Return Duct Flange A A BAYRETFLGBA Return Duct Flange B B BAYRETFLGCA Return Duct Flange C C BAYSRKIT100A Side Return Kit A to C BAYFLR1620A High Velocity Filter Kit, 16” X 20’ X 1” (10 filters) A BAYFLR2020A High Velocity Filter Kit, 20” X 20’ X 1” (10 filters) B BAYFLR2220A High Velocity Filter Kit, 22” X 20’ X 1” (10 filters) C TASB175SB Plenum Stand with integrated sound baffle A A TASB215SB Plenum Stand with integrated sound baffle B B TASB235SB Plenum Stand with integrated sound baffle C C BAYFRKIT175 Front Return Kit for 17.5” Cabinet A BAYFRKIT210 Front Return Kit for 21.0” Cabinet B BAYFRKIT235 Front Return Kit for 23.5” Cabinet C MITISRKIT1620 Side Return Kit with Filter A to C BAYICSKIT01A Internal Condensate Switch Kit A to C BAYHHKIT001A Horizontal Hanger Kit A to C BAYUVCLK001A UVC Lights A to C BAYLVKIT100A Low Voltage Conduit Entry Kit A to C BAYSPEKT200A Single Power Entry Kit A to C BAYWVAA05SC1AA Hydronic Coil - 50,000 BTUH - Slide-in with control A to A BAYWVBB07SC1AA Hydronic Coil - 70,000 BTUH - Slide-in with control B to B BAYWVCC08SC1AA Hydronic Coil - 80,000 BTUH - Slide-in with control C to C BAYWACC11SC1AA Hydronic Coil - 100,000 BTUH - Add-on C to C BAYWVBRD485A RS-485 Control for BAYWACC11SC1AA C to C 5
Section 4. Optional Cabinet Disassembly 4.1 Disassemble cabinet for installation in tight areas or as needed. Note: If the unit must be transported in a horizontal position, it must be laid on its back (marked “REAR” on carton). Note: To reassemble cabinet, follow the steps in reverse order. Ensure electrical connections are secure and the plug clips are engaged. STEP 1 - Remove all four front panels. See Section 2.2. Blower Electrical Connections 6
STEP 2 - Disconnect the two wiring connections routed to the blower assembly. STEP 3 - Slide Blower assembly out of unit using built-in blower support channels and set aside. Wiring Connections Blower Support Channel STEP 4 - Remove airflow diverter from the bottom of coil drain pan by gripping the plastic diverter, using Diverter your thumbs to spread the top of the diverter slightly outwards, and then pulling down and out through the blower opening as illustrated. 7
STEP 5 - Disconnect wires to the EEV motor and sensors. Cut the wire ties on those wire harnesses. Note: If cut, wire ties that held the sensor must be replaced after the coil is placed back into the cabinet. STEP 6 - Slide Coil assembly out of unit using built- in coil support channels and set aside. Coil Support Channel STEP 7 - Use a 5/16 Allen wrench on the locking mechanism on each side of the bottom half of the cabinet to loosen the locking mechanism. The locks loosen by turning counter-clockwise approximately 3/4 of a turn. 8
STEP 8 - Lift the Coil section up and away from the Blower section. Set aside. 2 1 9
STEP 9 - For extremely tight spaces where the cabinet needs to be rotated through a small opening, 2 remove the top panel and all cross members. Use a manual driver to avoid stripping screw holes. Note: Cross Members are removed by rotating them toward the door opening and then lifting up and out 1 of the unit. STEP 10 - Continue preparation by following the proper carrying procedures shown in Section 5. 10
Section 5. Place Unit at Location 5.1 Carry Unit STEP 1 - Carry the unit to the installation location. STEP 2 - Reassemble by reversing the steps listed in Section 4 if disassembly was required. If cut, wire ties that held the sensor wiring must be replaced. Important: Under no conditions should metal strap- ping be attached to the unit to be used as support mechanisms for carrying or suspension purposes. Cross Member Unit Top Plate Approved carrying: 1. Hold by the cross members within the cabinet or unit top plate and use as handles for lifting and carrying the coil and blower sections. Cross Members 11
Section 6. Unit Location Considerations 6.1 Unit Dimensions and Weight Table 7.1 Coil and Heater Unit Model H xW x D Compartment Net Weight Number in. Height * lbs. in. TAM7A0A24H21SC 49.9 x 17.5 x 21.8 28.1 120 TAM7A0B30H21SC 55.7 x 21.3 x 21.8 33.9 133 TAM7A0C36H31SC 56.9 x 23.5 x 21.8 35.1 143 W TAM7A0C42H31SC 56.9 x 23.5 x 21.8 35.1 158 TAM7A0C48H41SC 61.7 x 23.5 x 21.8 39.9 174 TAM7B0C60H51SB 61.7 x 23.5 x 21.8 39.9 178 *Blower compartment height is 21.8 inches. H D 12
6.2 Four-Way Conversion To place the unit in the configuration your application requires (upflow, downflow, horizontal right, or horizontal left), simply turn the unit to that orientation. Note: The air handlers are shipped from the factory suitable for four-way application. Refrigerant Connections Airflow Low Voltage Connections inside unit Low Voltage Connections inside unit Control Control Pocket Pocket Inside unit Inside unit Upflow Refrigerant Condensate Connections Drains Airflow Downflow Condensate Drains Downflow Configuration Upflow Configuration 13
Airflow Horizontal Left Control Refrigerant Low Voltage Condensate Pocket Connections Connections Drains Inside unit inside unit Horizontal Left Configuration Control Low Voltage Pocket Connections Refrigerant Inside unit inside unit Connections Airflow Horizontal Right Condensate Drains Horizontal Right Configuration 14
6.3 Non Ducted Applications ! CAUTION ▲ Supply Duct HAZARDOUS VAPORS! Do not install an air handler with a non-ducted return in the same closet, alcove, or utility room as a fossil fuel device. Hazardous vapors can be distributed throughout the conditioned space and equipment damage can result. Non-Ducted Return Installations: •• Installation in a closet, an alcove, or a utility room without a return duct requires the use of a plenum accessory kit as it uses the area space as a return air plenum. Minimum clear- ances to combustible materials and service access must be observed (see outline draw- ing). •• This area may also be used for other purpos- Plenum es, including an electric hot water heater, but Accessory in no case shall a fossil fuel device be installed with safety guard and/or operated in the same closet, alcove, or utility room. •• Review local codes to determine limitations if Non-Ducted the unit is installed without a return air duct. Return 6.4 Ducted Applications Supply Duct Ducted Return Installations: •• Installation in an attic, garage, or crawl space with ducted supply and return air is appropriate. Minimum clearances to combustible materials and service ac- cess must be observed (see outline drawing). Return Duct Ducted Return 15
6.5 Additional Unit Preparation Considerations For proper installation the following items must be con- •• These units are not approved for outdoor installation. sidered prior to moving the unit to its installation site: •• These units must be installed in the proper air flow •• Pursuant to Florida Building Code 13-610.2.A.2.1, this direction. unit meets the criteria for a factory sealed air handler. •• Any third-party heater accessories or hydronic coils •• If a side return is needed for your application, the side must be downstream of the unit. return MUST be prepared prior to moving the air han- •• Note: No atomizing style humidifier is allowed in the dler to its installation location. See the Side Return Kit return plenum with the use of this unit. # BAYSRKIT100A Installer Guide for detailed instruc- tions. •• Excessive bypass air may cause water blow-off, which will adversely affect system operation and air • When the air handler is located adjacent to the living cleaner performance. To verify bypass airflow, fol- area, the system should be carefully designed with re- low the Bypass Humidifier Pre-Installation Checkout turns which minimize noise transmission through the and Set-Up Procedures available through your local return air grill. Although the air handler is designed distributor. Ask for publication number 18-CH37D1-* with large blowers operating at moderate speeds, any Steam and Flow-through Fan Power Duct-mounted blower moving a high volume of air will produce audi- Humidifiers. Follow the humidifier installation instruc- ble noise which could be objectionable when the unit tions. These should only be installed on the supply is located very close to a living area. It is often advis- air side of the system. able to route the return ducts under the floor through the attic. Such design permits the installation of air •• Note: The air handlers have been evaluated in accor- return remote from the living area (i.e central hall). dance with the Code of Federal Regulations, Chapter XX, Part 3280 or the equivalent. “SUITABLE FOR •• Study the unit’s outline drawing and dimensions prior MOBILE HOME USE.” to selecting the installation site. Note in advance •• Note: This unit is certified to UL 1995. which electrical conduit entry points and condensate The interior cabinet wall meets the following: drain holes are to be used, so that proper clearance - UL94-5VA Flame Class Listed allowances can be made for installation and future - UL723 Steiner Tunnel Listed for 25/50 Flame/ maintenance. Smoke •• Installation of the air handler must be made prior to, - UL746C Listed for Exposure to Ultraviolet Light, or at the same time as, the installation of the outdoor Water Exposure and Immersion unit in order to allow access for refrigerant lines. •• Consider the overall space needed when external accessories are used, additional height and width requirements may exist. 16
Section 7. Setting the Unit - Vertical Installation 7.1 Secure Coil STEP 1 - Remove Coil Panel. STEP 2 - Remove screw from documentation packet. STEP 3 - While the air handler is in the upflow position, use the supplied screw to secure the coil seal plate to cross member as shown. Important: The Coil Seal Plate and screw secure the coil in the center of the air handler. Failure to follow these steps can prevent the Coil Panel from being easily replaced on the unit. 7.2 Considerations Provide a minimum height of 14 inches for proper unrestricted airflow below the unit. Allow a minimum of 21 inches clearance in front of the air handler to permit maintenance and removal of filter. •• Position unit on suitable foundation. If a manu- facturer approved accessory is not used, a frame strong enough to support the total weight of the unit, accessories, and duct work must be provided. •• Isolate unit from the foundation using a suitable isolating material. Typical Closet Installation 7.3 Upflow Installation TASB Installation 1. Install the TASB plenum stand with integrated sound baffle using the TASB instructions. Note: Kit is used for open air applications. TASB175SB for use with 17.5” cabinets TASB215SB for use with 21.5” cabinets TASB235SB for use with 23.5: cabinets MITISRKIT1620 - Side return kit with 16”x20” filter Contact your distributor for more information. Airflow Airflow Ai rfl ow Typical TASB Installation 17
Plenum Installation 1. Assemble the plenum using the plenum’s Installer Guide. On units with sheet metal returns: Return plenum must be flanged. Sheet metal drill point screws must be 1/2” in length or shorter. Airflow Typical Plenum Installation 7.4 Downflow Installation •• Downflow installation must comply with national, state, and local codes. •• The air handlers are rated for zero clearance from combustible materials. STEP 1 - Prepare the location site as appropriate for your application and per national, state, and local code requirements. STEP 2 - Set the unit in position. Representative Illustration Typical Downflow Installation 18
Section 8. Setting the Unit - Horizontal Installations 8.1 Secure Coil STEP 1 - Remove Coil Panel. STEP 2 - Remove screw from documentation packet. STEP 3 - While the air handler is in the upflow posi- tion, use the supplied screw to secure the coil seal plate to cross member as shown. Important: The Coil Seal Plate and screw secure the coil in the center of the air handler. Failure to follow these steps can prevent the Coil Panel from being eas- ily replaced on the unit. 8.2 Considerations Important: Due to the unique design of this unit, which allows the electrical wiring to be routed within the insulation, do not screw, cut, or otherwise puncture the unit cabinet in any location other than the ones Field Supplied illustrated in this Installer Guide or in an approved ac- Isolators cessory’s Installer Guide. Important: Make certain that the unit has been in- stalled in a level position to ensure proper draining. Important: Under no conditions should metal strap- ping be attached to the unit to be used as support mechanisms for carrying or suspension purposes. STEP 1 - Support the unit from the bottom (near both ends). The service access must remain unobstructed. Important: The unit can only be supported from the bottom unless using kit BAYHHKIT001A. Do not drill or screw supports into any area of the cabinet. Note: Do not allow the unit to be used as strain relief. Bottom Support Auxiliary Drain Near Both Ends Pan •• Approved bottom support methods are rails, u- channels (Unistrut®), or other load bearing materi- als. Note: BAYHHKIT001A Hanging Bracket Kit may be ordered separately. •• The unit must be isolated carefully to prevent Important: The BAYHHKIT001A may not be used sound transmission. Field supplied vibration isola- if the cabinet has been altered per Installer Guide tors are recommended. 18-HJ58D1-1. STEP 2 - Install an auxiliary drain pan under the horizontal air handler to prevent possible damage to ceilings. •• Isolate the auxiliary drain pan from the unit and from the structure. •• Connect the auxiliary drain pan to a separate drain line and terminate according to local codes. 19
Section 9. Connecting the Duct work 9.1 Duct Connection Considerations Important: Due to the unique design of this unit, which allows the electrical wiring to be routed within the insulation, do not screw, cut, or otherwise punc- ture the unit cabinet in any location other than the ones illustrated in this Installer Guide or in an ap- proved accessory’s Installer Guide. Important: Under no conditions should metal strap- ping be attached to the unit to be used as support mechanisms for carrying or suspension purposes. Important: On units with sheet metal returns: Return air plenum must be flanged. Sheet metal drill point screws must be 1/2” in length or shorter. •• The supply and return air ducts must be connected to the unit with non flammable duct connectors. •• See the Outline drawing for sizes of the duct con- nections. Screws allowed in •• After the ducts are secured, seal around the sup- first 3/4” of bottom ply and return ducts to prevent air leakage. 3/4” cross member. •• Insulate all duct work that will be outside of condi- tioned spaces. •• Convertible Duct Flange Kits are available to con- nect the supply plenum or for mounting on the discharge opening to provide a “flush fit” for 1‑1/2” duct board applications. •• If front or rear return is required, the air handler must be elevated - placed on a pedestal or plenum and duct must be connected to this pedestal or plenum. •• If side return is required, the Side Return Kit # BAYSRKIT100A accessory must be used. A re- mote filter will be required. •• To ensure maximum efficiency and system perfor- mance, the existing supply and return duct system static pressures must not exceed the total available static pressure of the air handler. Reference ACCA Manual D, Manual S and Manual RS along with the air handler Product Data and Service Facts for additional information. Note: Side return is not approved without Side Return Kit # BAYSRKIT100. More than one Side Return Kit may be necessary depending on the application. Refer to the Installation Guide in BAYSRKIT100 for approved duct connections, sizing, number, transitions, and accessory application. Note: Duct work must be supported as appropriate. See National and local codes for guidelines. Do not depend on the unit to support duct work. 20
Section 10. Refrigerant Line 10.1 Refrigerant Line Connection Sizes Table 10.1 Refrigerant Line Connection Sizes Vapor Line Liquid Line Model Connection Connection TAM7A0A24H21SC 3/4 3/8 TAM7A0B30H21SC 3/4 3/8 TAM7A0C36H31SC 7/8 3/8 TAM7A0C42H31SC 7/8 3/8 TAM7A0C48H41SC 7/8 3/8 TAM7B0C60H51SB 7/8 3/8 Notes: 1. This table indicates the tubing connection diameters at the indoor coil. A field supplied reducing coupling may be required. 2. All AHRI listed systems are tested with 25 feet of refrigeration tubing; the rated tubing diameters are located in the electronic performance data system. 3. If the refrigeration lines exceed 60 feet in linear length and / or if alternate size refrigeration tubing is present at the job, please consult SS-APG006-EN or 32-3312-**(latest version) 10.2 Refrigerant System Layout Check Valve Liquid Line Vapor Line Gas Temperature Strainer Sensor (GT) - located on copper section of manifold (black wires) Evaporator Temperature Sensor (ET) - located on 3/8" Aluminum distributor tube (orange wires) EEV Stepper Motor Note: Some future models may not have external check valve. 21
Section 11. Refrigerant Line Brazing 11.1 Braze The Refrigerant Lines STEP 1 - Remove Heater, Coil, and Line Set panels. 1 Heater (See Section 2.2 Panel Removal) Panel Line Set Panel 3 Coil Panel 2 Important: Do NOT unseal coil refrigerant connec- tion stubs until ready to make connections. Important: Heat Sensitive Sensors. The Gas Temperature Sensor must be removed or a wet rag must be wrapped around the suction line between the Sensor and the braze joint to protect it from failure due to overheating. STEP 2 - Remove the plastic cap and Schrader valve core from the gas line. STEP 3 - Wrap the Gas Temperature Sensor (GT) with a wet rag. Important: Care must be taken during solder cap removal and brazing to avoid damage to unit compo- nents and wiring. STEP 4 - Apply low heat to the solder cap to slowly STEP 5 - Remove the sealing plug from the indoor coil heat the solder. (Do not apply direct heat to the va- liquid connection. por line) Use adjustable pliers to grab the flare fitting and remove the solder cap. STEP 6 - Connect, but do not braze, field line set to indoor coil. Allow a minimum of three (3) inches of refrigerant line set before using an elbow coupling. 3” MIN Important: Service access to the auxiliary heater must remain unobstructed. 22
Important: Heat Sensitive Sensors. The Gas Temperature Sensor must be removed or a wet rag must be wrapped around the suction line between the Sensor and the braze joint to protect it Scan to see a video on Brazing from failure due to overheating. the TAM7 Refrigerant lines. STEP 7 - Braze refrigerant line connections. Wet Rag on Note: The suction line must be insulated prior to Gas Temperature brazing the line set to the air handler stubs. Sensor (GT) 1. Pull back the insulation before brazing the suc- tion line. 2. Wrap the Gas Temperature Sensor (GT) with a wet rag. 3. Braze the refrigerant line connections. Important: Care must be taken during brazing to avoid damage to unit components and wiring. STEP 8 - Pressurize the refrigerant lines and evapo- rator coil to 150 PSIG using dry nitrogen. 150 PSIG STEP 9 - Check for leaks by using a soapy solution or bubbles at each brazed location. 23
Important: Do not open the service valves until the refrigerant lines and indoor coil leak check and evacu- ation are complete. 0350 STEP 10 - Evacuate until the micron gauge reads no Microns higher than 350 microns, then close off the valve to the vacuum pump. ON OFF STEP 11 - Observe the micron gauge. Evacuation is complete if the micron gauge does not rise above 500 microns in one (1) minute. Once evacuation is complete blank off the vacuum pump and micron gauge, and close the valves on the 1 MIN. manifold gauge set. Note: Charge system using Outdoor unit’s Installer Guide or Service Facts. STEP 12 - Replace the Line Set panel. 1. Allow time for tubing to cool. 2. Install grommets to line set piping in orientation shown. Note: A slight amount of dish soap can be used to aid in the installation of the grommets. Remove any excess from the tubing and grommet after the grommet See enlarged is installed. illustration for orientation 3. Slide the bottom of the Line Set panel down over the refrigerant lines and grommets. The grommets will seal the line openings. 4. Tighten screws on the Line Set panel. 24
Section 12. Condensate Drain Piping 12.1 Condensate Drain Piping Considerations •• Condensate drain plumbing must comply with na- •• Do not connect the drain line to a closed drain tional, state, and local codes. system. •• Route condensate drain lines away from air handler •• Do not use a torch or flame near the plastic drain so they do not interfere with access panels. pan coupling. •• Slope the drain lines downward a minimum of 1/4” •• A P-trap is not required for proper drainage due to per foot, support per local codes. the positive pressure of the air handler; however, •• Do not use reducing fittings in the condensate drain it is recommended to prevent efficiency loss of lines. conditioned air. 12.2 Connect Condensate Drain Piping Note: Upflow and horizontal orientations require the Downflow Coil panel to be removed in order to make the drain Condensate connections. Note: Make certain that the unit has been Drains installed in a level position to allow for proper draining. S P Condensate Drains Condensate Drains S P P S Horizontal Right Horizontal Left STEP 1 - Select the drain connections that are ori- ented for your application. STEP 2 - Prepare the condensate drain connections. •• From the factory, the unit comes with plugs in both upflow condensate drains and an additional plug in the documentation packet. •• For upflow applications, remove upflow condensate plug(s) and connect condensate piping. S •• For all other applications, do not remove upflow con- P densate plugs. Remove the cover from the needed Upflow condensate drain connections and connect conden- Condensate sate piping. Air seal Drains over secondary •• If the secondary condensate opening is not used, drain plug the condensate opening with the fitting supplied in the documentation pack. Use scissors to cut the Note: A small amount of sealant must be applied air seal in half and re-install over the unused open- around the drain line(s) passing through the panel ing. to prevent air leakage and possible water drips. •• Dry fit and test clearance for coil panel removal before applying PVC/CPVC cement •• Use Teflon tape on the air handler drain line connections. Do not use pipe joint compound or Teflon Tape PVC/CPVC cement on drain nipple. •• Hand tighten the drain pipe. STEP 3 - For Upflow installations, connect 3/4” PVC pipe to the threaded drain nipple with PVC/CPVC ce- Drain Nipple ment. 3” minimum clearance to the condensate piping is needed for coil panel removal. Thread the assembly into the primary drain connection (repeat for the sec- ondary drain connection if used). Important: For Horizontal and Downflow installations, the following order must be observed: 1) Remove panel and insert the 3/4” nipples. 3/4” PVC pipe 2) Reinstall the panel. 3) Connect the condensate lines to the nipples. Note: A small amount of sealant must be applied PVC CEMENT around the drain line(s) passing through the panel PVC/CPVC Cement to prevent air leakage and possible water drips. 25
STEP 4 - Install a clean-out tee in the primary drain line for future maintenance. It is recom- mended that you install a cap on the top of the Cap tee. 3” min. 3” minimum clearance is recommended from cabinet to Tee inside edge of tubing STEP 5 - Insulate the primary drain line to prevent sweating where dew point temperatures Insulation may be met. (Optional depending on climate and application needs.) Provide a means of drainage to prevent winter freeze-up of condensate line. (Optional depend- ing on climate and application needs.) STEP 6 - Support the condensate piping outside Condensate the unit per local codes for proper drainage and Piping Supports to prevent sagging. Allow 1/4” of downward slope for each foot of pipe. 26
Section 13. Electrical - Low Voltage 13.1 Low Voltage Maximum Wire Length Table 11.1 defines the maximum total length of low Table 11.1 voltage wiring from the outdoor unit, to the indoor unit, and to the thermostat. 24 VOLTS WIRE SIZE MAX. WIRE LENGTH 18 AWG 150 Ft. 16 AWG 225 Ft. 14 AWG 300 Ft. 13.2 Low Voltage Hook-up Instructions STEP 1 - Route control wiring to unit. Remove the external sheathing of the wiring approximately 5”. 5” Note: Optional Low Voltage Conduit Entry Kit number BAYLVKIT100A is available. STEP 2 - Remove Coil panel by turning the Phillips head door fasteners, rotating the door away from the cabinet, and removing. 27
STEP 3 - Remove the control board from the control pocket by sliding the control pocket mounting plate out until the first stop is reached. Control Pocket Inside unit Control Board For Horizontal Right installations Only Remove the control board completely from the con- trol pocket. Rotate the control board 180 degrees. Place the control board 2-3 inches back into the control pocket. Attach wiring per appropriate hook- up diagram or perform service. Important: After wires have been connected or ser- vice performed, the control board MUST be rotated back to the original orientation before inserting into control pocket in the cabinet. 1 2 28
STEP 4 - Make connections per hookup diagrams. Air Conditioner Neatly bundle all low voltage wires behind the service Scan to see a valve cover as shown. video on Field Wiring the TAM7. Single Stage Cooling Air Handler Comfort Control W3 * W2 Blue W White W1 G BK Yellow Y1 Green G O Y2 R Yellow YI (In) B O Y2 Red R Blue B B - Blue Field wiring YO (Out) Y1 - Yellow •• * For multiple stages of electric heat, jumper W1, W2, and W3 together if comfort control has only one stage of heat. •• YI and YO connections must be made as shown for proper operation, freeze protection, and internally mounted condensate overflow circuits to work properly. •• Internally mounted condensate switch is optional and must be ordered separately. •• If 3rd party condensate overflow switches are installed, they should be wired between Y of the thermostat and YI of the Airflow control. Single Stage HP Heat Pump Neatly bundle all low voltage wires behind the service valve cover as shown. Black Air Handler (X2) Comfort Control Orange W3 * Blue Yellow X2 W2 W White W1 W1 - White Red G BK Y1 Green G O Y2 R Yellow YI (In) B Orange O O - Orange Red R R - Red Blue B B - Blue Field wiring YO (Out) Y1 - Yellow •• * For multiple stages of electric heat, jumper W1, W2, and W3 together if comfort control has only one stage of heat. •• YI and YO connections must be made as shown for proper operation, freeze protection and internally mounted condensate overflow circuits to work properly. •• Internally mounted condensate switch is optional and must be ordered separately. •• If 3rd party condensate overflow switches are installed, they should be wired between Y of the thermostat and YI of the Airflow control. 29
Two Stage Cooling Air Conditioner Neatly bundle all low voltage wires behind the service valve cover as shown. Air Handler Comfort Control Yellow/Black W3 * Yellow/Red W2 W White W1 G Green BK Blue Y1 Yellow G O Y2 Y2 - Brown R Red YI (In) B Blue O Y2 Brown R B B - Blue Field wiring YO (Out) Y1 - Yellow •• * For multiple stages of electric heat, jumper W1, W2, and W3 together if comfort control has only one stage of heat. •• YI and YO connections must be made as shown for proper operation, freeze protection and internally mounted condensate overflow circuits to work properly. •• Internally mounted condensate switch is optional and must be ordered separately. •• If 3rd party condensate overflow switches are installed, they should be wired between Y of the thermostat and YI of the Airflow control. Two Stage HP Heat Pump Neatly bundle all low voltage wires behind the service valve cover as shown. Black Air Handler (X2) Yellow Comfort Control Yellow/Red W3 * X2 W2 Red Blue Orange W White W1 W1 - White G Green BK Y1 Yellow G O Orange Y2 Y2 - Brown R Red YI (In) B Blue O O - Orange Y2 Brown R R - Red B B - Blue Field wiring YO (Out) Y1 - Yellow •• * For multiple stages of electric heat, jumper W1, W2, and W3 together if comfort control has only one stage of heat. •• YI and YO connections must be made as shown for proper operation, freeze protection and internally mounted condensate overflow circuits to work properly. •• Internally mounted condensate switch is optional and must be ordered separately. •• If 3rd party condensate overflow switches are installed, they should be wired between Y of the thermostat and YI of the Airflow control. 30
STEP 5 - Secure the sheathed wiring to the control pocket mounting plate using the factory supplied wire ties attached to the tabs to as shown. S1 Dip Switch S2 Dip Switch Airflow Control (AFC) TRANE U.S. INC. HUM OUTDOOR J4 PART NO. LABEL Pb on Wire Ties J1 1 2 3 4 5 } Capacity (Tons) LR V S VD MC D HP AC (System) T1 C7 T2 C3 C37 S R5 D1 R19 1 2 (Stages) J8 R12 D G 1 2 (Compressor) P R7 C C2 G P D2 R4 S1 C6 R2 R8 R3 INDOOR BAR CODE R21 C1 R NET 1 on 1 2 3 4 5 D7 } K1 D4 R42 R34 R NET 2 CFM/Ton R6 D6 D3 Cool Off Delay R1 } Q1 U1 D5 R25 R18 C17 C16 D11 C5 C4 D8 R39 R33 R24 R17 R40 Torque CFM D10 R10 R43 C9 R46 R13 C23 1 R9 U2 S2 R14 R26 R27 R15 D9 C22 R11 C12 C15 C19 R28 R16 R41 16 1 R57 R58 D12 C25 C10 D30 C24 17 64 C45 C44 D31 +12V L1 C11 C14 C18 C21 J9 C8 D13 C36 R22 J3 C31 R23 J13 J7 Y1 R48 C13 C34 C42 R38 R32 R36 R20 PTC1 R85 R82 R84 +12V O C DA .3V D15 C26 D18 32 49 R77 C27 C29 C30 D19 C35 Q3 S 3 D16 33 48 R65 R64 Q5 R44 RX C20 R79 Q2 B L C43 R83 TX R29 S R31 R35 X1 R78 R76 R47 Q4 GND D Yo R45 R49 N R52 R54 R81 G R51 R50 R55 R86 D14 D20 R69 R72 R71 R37 C33 C32 D21 R75 R30 MOTOR R Q6 R53 D17 R61 R91 R98 C28 R63 R89 Q7 R59 D26 C41 D27 D29 C49 R56 R62 R74 C59 R105 C48 R97 R108 Yo Jumper BK Jumper C46 D22 C55 R109 C60 STATUS W2 R103 W1 TZ2 R106 D36 R95 D24 C54 R60 C53 U4 D35 C56 R102 R99 R96 UNIT R66 R68 D33 C52 C47 Q8 C40 D34 R101 C57 D25 R107 FAULT U3 L2 R110 5V R87 K2 R94 C58 C50 R88 R93 R70 R100 R104 MOV1 C39 R67 C38 C51 D32 D23 D28 L3 R80 R73 J6 U5 S3 +13.8V TEST +V GND A/Y B/Z C3 R9 D3 L2 R4 J2 P/N LABEL MH4 MOV1 BAR CODE R10 MH3 L3 R43 C1 R11 D14 C4 R40 J1 STATUS D15 R6 R34 Q5 Distribution Board R87 R5 C37 R44 D16 D4 Q1 R3 UNIT D17 R30 R86 R31 D1 C35 L1 D18 R16 R35 Q6 FAULT R15 R88 D19 +12V R 45 R14 R 37 D7 Q2 R59 3 2 1 D11 D5 R21 U3 R83 J7 R39 R36 Q7 R47 R20 C16 R32 C40 Q3 R19 D20 R 410 R8 R 22 R33 R42 R17 Q8 D8 OVR J6 R25 U4 R38 R27 FLOW X1 R29 EVAP R 46 C15 Q4 R26 R60 C27 C26 D12 TEMP C13 C 12 J4 R57 +5V R48 C36 R74 R70 R56 C41 L4 C14 C30 OPEN R55 L5 D13 R75 C17 R72 TEST C6 R 90 R54 J7 Jumper R28 C 31 R 79 D25 CLOSE R53 R81 C18 R2 R7 GAS C33 D21 TEMP R77 R 82 R52 R76 C2 R49 R12 R73 D26 R 80 C 21 R 91 R51 C34 R84 R78 J3 C29 C32 C28 D22 C5 D24 R71 U1 R85 R22 R 41 C38 D23 MH1 Q9 C42 GND J5 C11 TRANE U.S. INC. MH2 D D PGC S LR VD PG VS C Electronic Expansion Valve Control (EVC) STEP 6 - Set Jumper and Dip Switches Refrigerant Jumper J7 •• Set the system refrigerant to either R-410A or R-22 P/N LABEL using the Refrigerant Jumper located on the Expan- MH4 BAR CODE R10 R11 D14 sion Valve Control board (EVC) in the Control Pocket. STATUS D15 R87 D16 UNIT D17 R30 R R31 C35 D18 •• Factory default is R-410A. FAULT R88 D19 R 45 R 37 3 2 1 D11 R21 U3 J7 R39 R47 •• Note: The power must be shut off and then re-applied R32 C R 410 R8 R 22 R33 R42 R17 in order for the EVC to recognize the change. R25 U4 X1 R29 R 46 C15 R60 C27 C26 C13 C 12 J4 R57 R74 R70 R56 C41 L4 C14 OPEN R55 R75 L5 C17 TEST C R 90 R54 C 31 R 79 D25 R53 C18 CLOSE R81 D21 R 82 R52 R76 D26 R 80 C 21 R 91 R51 C34 R84 J7 Jumper C28 D22 C5 D24 R71 R 41 D23 MH1 Q9 J5 C11 TRA D D PGC S LR VD PG VS C Scan to see a video on setting the TAM7 DIP Electronic Expansion Valve Control (EVC) Switches. 31
Dip Switch S1 •• Set the S1-1 and S1-2 dip switches for the OD multiplier (tonnage) per the chart. S1 OUTDOOR INDOOR MODEL S1-1 S1-2 OD MULTIPLIER on 1 2 3 4 5 OFF OFF 2 } Capacity (Tons) OFF ON 1.5 HP AC (System) TAM7A0A24H21SC 1 2 (Stages) ON OFF 2.5 R4 1 2 (Compressor) ON ON 3 S1 INDOOR 1 R NET 1 R NET 2 on OFF OFF 2 R6 1 2 3 4 5 } R1 CFM/Ton OFF ON 1.5 U1 TAM7A0B30H21SC Cool Off Delay } ON OFF 2.5 R13 ON ON 3 Torque CFM R14 D9 C22 C12 C15 C19 C10 S2 +12V L1 C18 C21 OFF OFF 3 R22 OFF ON 2 TAM7A0C36H31SC Airflow Control (AFC) ON OFF 2.5 ON ON 3.5 OFF OFF 3.5 •• Set the S1-4 dip switch for the number of stages OFF ON 2.5 on the outdoor unit. TAM7A0C42H31SC ON OFF 3 ON ON 4 OD STAGES S1‐4 1 OFF OFF OFF 4 2 ON OFF ON 3 16 SEER = 2 Stages TAM7A0C48H41SC ON OFF 3.5 19 SEER = 2 Stages 20 SEER = 2 Stages ON ON 4.5** •• Note: This dip switch should be changed while the power is off or no demand is present. The power OFF OFF 4.5** must be shut off and then re-applied in order for the OFF ON 3.5 AFC to recognize the change. TAM7B0C60H51SB ON OFF 4 ON ON 5 •• Set the S1-5 dip switch for the number of compressors. NOTE: The OD multiplier in conjunction with the CFM/TON can be used to adjust total airflow for your application. # COMPRESSORS S1‐5 Example: 4.5T x 370 CFM/TON = 1665 CFM 1 OFF 2 ON ** Not an actual OD size 16 SEER = 1 Compressor 19 SEER = 2 Compressors •• Set the S1-3 dip switch for AC or HP. 20 SEER = 2 Compressors OD TYPE S1‐3 HP OFF AC ON 32
OUTDOOR Dip Switch S2 on •• Set the S2-1 and S2-2 dip switches for the 1 2 3 4 5 } Capacity (Tons) Cooling and Heating CFM/Ton. HP AC (System) 1 2 (Stages) R4 1 2 (Compressor) S1 INDOOR 1 R NET 1 R NET 2 on R6 1 2 3 4 5 } R1 CFM/Ton U1 Cool Off Delay } R13 Torque CFM R14 D9 C22 C12 C15 C19 C10 S2 +12V L1 C18 C21 R22 S2 Airflow Control (AFC) INDOOR MODEL S2-1 S2-2 COOLING HEATING CFM/TON CFM/TON OFF OFF 400 430 OFF ON 360 390 TAM7A0A24H21SC ON OFF 380 410 ON ON 420 450 OFF OFF 400 430 OFF ON 360 390 TAM7A0B30H21SC ON OFF 380 410 ON ON 420 450 OFF OFF 370 420 OFF ON 350 400 TAM7A0C36H31SC ON OFF 390 440 ON ON 410 450 OFF OFF 370 400 OFF ON 350 360 TAM7A0C42H31SC ON OFF 350 380 ON ON 390 420 OFF OFF 350 400 OFF ON 330 380 TAM7A0C48H41SC ON OFF 370 420 ON ON 390 440 OFF OFF 370 400 OFF ON 380 410 TAM7B0C60H51SB ON OFF 390 420 ON ON 400 430 33
•• Set the S2-3 and S2-4 dip switches for the OUTDOOR Blower Off Delay. on 1 2 3 4 5 } Capacity (Tons) HP AC (System) BLOWER OFF DELAY S2‐3 S2‐4 1 2 (Stages) R4 1 2 (Compressor) 1.5m @ 100% OFF OFF S1 INDOOR 1 NO DELAY OFF ON R NET 1 R NET 2 on 3m @ 50% ON OFF R6 1 2 3 4 5 } CFM/Ton ENHANCED ON ON R1 U1 Cool Off Delay } R13 Torque CFM R14 D9 Indoor Blower Timing C22 C12 C15 C19 C10 S2 This ENHANCED MODE selection provides a +12V L1 C18 C21 R22 ramping up and ramping down of the blower speed to provide improved comfort, quietness, Airflow Control (AFC) and potential energy savings. The graph on the right shows the ramping process. 100% if necessary Enhanced Mode works in cooling, HP, heating, Torque, and constant CFM modes. 80% FAN OPERATION (CFM) Dehumidify 50% 50% •• Set the S2-5 dip switch for the airflow mode. Fast Coil Cooling Efficiency OFF OFF AIRFLOW MODE S2‐5 *TORQUE OFF as required 1 7.5 3 CONSTANT CFM ON minute minutes minutes COMPRESSOR OPERATION ON OFF * All zoning applications MUST be set to Constant CFM mode. * Torque mode is optional and is recommended for high static applications. High static conditions dramatically increase energy consumption with variable speed motors. Evaluate the blower performance table in relationship to the duct system to determine the benefit of each installation. * For the 2 ton air handler, torque mode will reduce airflow when static is above approximately 0.3" water column. * For the 2-1/2, 3, and 3-1/2 ton air handlers, torque mode will reduce airflow when static is above approximately 0.35” water column. * For the 4 and 5 ton air handlers, torque mode will reduce airflow when static is above approximately 0.4” water column. When selected, Torque Mode is used for cooling operation only. All heating modes default to constant CFM. 34
Indoor Blower Options BK Jumper TRANE U.S. INC. HUM J4 PART NO. LABEL •• Humidity Control for Cooling - This unit is capable Y0 J1 LR V S VD MC D T1 C7 T2 C3 C37 S Jumper D1 of providing additional de-humidification during the R5 R19 J8 R12 D G P R7 C C2 G P D2 R2 R8 C6 cooling mode by reducing the airflow when humidity (Do Not BAR CODE R21 D7 D4 K1 R R42 D6 D3 cut) Q1 is above the set point. A conventional field supplied D5 R25 R18 C17 C16 D11 C5 C4 D8 R39 R33 R24 R17 R40 D10 R10 R43 C23 R46 1 R9 U2 R28 R26 R27 R11 R15 R16 humidistat is required to control this function. R41 16 1 R57 R58 D12 C25 D30 C24 17 64 C45 C44 D31 J9 D13 C36 C31 R23 Y1 C34 R32 R36 R20 1. Cut the BK jumper on the AFC. R85 R82 R84 R38 O L A V 32 49 S SD 3 .3 D15 C27 C26 D18 C29 C30 D19 C35 D16 33 48 R65 R64 B C43 C X1 R78 R76 D 2. Using a field supplied humidistat, wire 24VAC Hot Yo R45 R49 N R52 R54 G R50 R55 R69 R72 R86 D20 R75 R71 C33 C32 D21 R R91 to one side of the humidistat. Wire the other side of R63 D26 C41 D27 R56 R74 D29 C49 R62 C59 R97 C48 Yo Jumper BK Jumper C46 D22 R109 STATUS W2 W1 R106 D36 D24 R60 C53 U4 D35 the humidistat to the BK terminal on the low voltage UNIT R66 R68 R102 D33 C52 C47 Q8 C40 R101 D25 R107 FAULT U3 L2 R110 R87 K2 R94 C58 C5 terminal board. See wiring diagram. R88 R93 R70 R100 R104 MO C39 R67 C38 C51 D32 D23 D28 L3 R80 R73 J6 S3 +13.8V TEST •• Pulse Width Modulation (PWM) - Typically used with A/TCONT402 or zoning control. Airflow Control (AFC) 1. The BK jumper must be cut on the AFC. - Do Not cut the Y0 jumper. •• All zoning applications MUST be set to Constant CFM mode. Comfort Control Air Handler W3 W2 W White W1 G Green BK Y1 Yellow G O Y2 R Red YI (In) B Blue O Y2 R B YO (Out) Field wiring Humidistat 35
STEP 7 - Slide control plate assembly into the control pocket until fully seated. The control plate should be flush with the outer edge of the unit. STEP 8 - Replace Coil panel making sure that the wires are located within the wire pass-through pro- vided in the panel. Pass through notch in coil access door 36
Section 14. Electrical - High Voltage 14.1 High Voltage Power Supply The high voltage power supply must match the equipment nameplate. ▲! WARNING LIVE ELECTRICAL COMPONENTS! Power wiring, including ground wiring, must comply During installation, testing, servicing, and troubleshooting of this with national, state, and local codes. product, it may be necessary to work with live electrical com- ponents. Failure to follow all electrical safety precautions when Field wiring diagrams for supplementary electric exposed to live electrical components could result in death or heaters are shipped with the heater. serious injury. 14.2 Make Electrical Connections STEP 1 - Route High Voltage wiring to unit. Conduit Entry Points STEP 2 - Select a conduit entry point. Drill a hole for the desired conduit size on units without a plug. A locating target is identified on these units. Note: Some models may have a pre-molded conduit connection with plug. If a connection hole is already present, remove the plug from the entry point and use as is. 1. Select the entry point you will use to bring in your high voltage wiring. 2. Remove plug from the entry point. STEP 3 - Route conduit (if used) to the entry point and connect. 1. Use one hand to secure the conduit nut from inside of the heater compartment. 2. Connect a field supplied 3/4" or 1-1/2" conduit to conduit nut. Note: Reducing bushings may be required for your application. 37
STEP 4 - If an electric heater IS NOT being BLACK RED installed, remove the pigtail harness from the GREEN - GROUND documentation pack and connect it to the plug on the inside of the Heater Compartment in the cabinet. If an electric heater IS being installed, see the Installer’s Guide shipped with the electric heater. Connect L1, L2, and ground wiring to pigtail harness in Heater Compartment using wire nuts. The incoming ground wiring will mate up with the green wire shown in the illustration. STEP 5 - If the L1, L2, and ground wires enter the case from the left side, use a field supplied 1/2”-5/8” maximum length screw and wire tie to hold the wires to the top center of the Heater Compartment. STEP 6 - Reinstall all panels before starting the air handler. NOTE: After replacing all panels, loosen the Line Set Panel screws approximately 1/4 - 1/2 turn. This will improve the seal between the Heater Panel and Line Set Panel. 38
Section 15. Unit Outline Drawing MODEL NO. A B C D E F H FLOW GAS LINE LIQ LINE CONTROL BRAZE BRAZE TAM7A0A24H21SC 49.9 17.5 14.5 39.6 14.5 7.3 24.4 EEV 3/4 3/8 TAM7A0B30H21SC 55.7 21.3 18.4 45.5 18.4 9.2 24.8 EEV 3/4 3/8 TAM7A0C36H31SC 56.9 23.5 20.5 46.7 20.5 10.3 24.2 EEV 7/8 3/8 TAM7A0C42H31SC 56.9 23.5 20.5 46.7 20.5 10.3 24.5 EEV 7/8 3/8 TAM7A0C48H41SC 61.7 23.5 20.5 51.5 20.5 10.3 24.9 EEV 7/8 3/8 TAM7B0C60H51SB 61.7 23.5 20.5 51.5 20.5 10.3 24.9 EEV 7/8 3/8 39
Section 16. Filters 16.1 Filter Considerations •• A filter must be installed within the system. •• A filter channel is provided in the unit, at the bot- tom of the Blower/Filter compartment. •• For customer ease of filter maintenance, it is recommended that a properly sized remote filter grill(s) be installed for units that are difficult to access. Airflow should not exceed the maximum rated velocity of the filter being used. Filter in Table 16.1 Filter Sizes air handler cabinet Cabinet Size* A B C (Upflow Application) Filter Size 16 x 20 20 x 20 22 x 20 * Cabinet size is indicated by the 7th digit in model number. Section 17. Start Up 17.1 System Charge Adjustments Sytem Matched with: Indoor Unit Model No. Outdoor Unit Model No. Subcooling 16 SEER HP TAM7A0B30H21SC 4A6H6024E/G, 4TWX6024E/G 9° TAM7A0C36H31SC 4A6H6036E/G, 4TWX6036E/G 10° TAM7A0C48H41SC 4A6H6048E/G, 4TWX6048E/G 8° 16 SEER AC TAM7A0B30H21SC 4A7A6024E/G, 4TTX6024E/G 8° TAM7A0C36H31SC 4A7A6036E/G, 4TTX6036E/G 8° TAM7A0C48H41SC 4A7A6048E/G, 4TTX6048E/G 8° 20 SEER HP TAM7A0B30H21SC 4TWZ0024A, 4A6Z0024A 9° TAM7A0C36H31SC 4TWZ0036A/B, 4A6Z0036A/B 10° TAM7A0C48H41SC 4TWZ0048A/B, 4A6Z0048A/B 12° TAM7B0C60H51SB 4TWZ0060A, 4A6Z0060A 12 ° 20 SEER AC TAM7A0B30H21SC 4TTZ0024A, 4A7Z0024A 9° TAM7A0C36H31SC 4TTZ0036A/B, 4A7Z0036A/B 11° TAM7A0C48H41SC 4TTZ0048A/B, 4A7Z0048A/B 13° All other matches must be charged per the nameplate charging instructions. 40
17.2 System Start Up STEP 1 - Make sure all panels are securely in place and that all wiring has been properly dressed and secured. STEP 2 - Set the system thermostat to OFF. OFF DONE CANCEL STEP 3 - Turn on electrical power disconnect(s) to apply power to the indoor and outdoor units. ON OFF STEP 4 - Set the system thermostat to ON. ON DONE CANCEL 41
Section 18. Sequence of Operation 18.1 Sequence of Operation TAM7 Sequence of Operation 3. R-G contacts close on comfort control sending 24VAC to the G terminal of the AFC. Abbreviations 4. The AFC micro-processor sends a command to the serial • AFC = Airflow Control communicating blower motor to run at 1st stage heating • EVC = Expansion Valve Control cfm. • EEV = Electronic Expansion Valve 5. The HUM contacts close. • EHC = Electric Heat Control 6. R-Y2 contacts close on the comfort control sending 24VAC to Y2 terminal on the AFC. • YI = Y signal from the comfort control 7. The Y2 signal is also passed through to provide power to • YO = Y signal out of the AFC from the comfort control the outdoor unit 2nd stage control circuit. • Y2 = Y2 signal from comfort control 8. The blower motor will now run at 100% of the heating cfm. This unit has unique a feature that receives 24VAC analog inputs from a conventional comfort control and then converts these inputs to serial communicating signals OD Single Stage (cooling mode) between the different controls within the air handler. 1. R-Y contacts close on the comfort control sending 24VAC to Y1 terminal on the AFC. The installing and servicing technician should have an understanding of the sequence of operation to be able 2. Normally closed contacts on the AFC will pass 24VAC to properly setup and diagnose functions of the air to the YO terminal providing power to the outdoor unit handler. control circuit. The dip switch settings on the control boards must be prop- a. Heatpump OD > R-O contacts close on the comfort erly set to obtain the correct sequence of operation. control sending 24VAC to the O terminal of the AFC. Reference the air handler and electric heat wiring dia- The AFC communicates to the EVC that the system is in grams and dip switch configuration chart for additional cooling mode. The O signal is passed through to the OD information. unit. See unit, electric heat, and field wiring diagrams for ad- b. Non heatpump OD > OD dip switch configuration will ditional information. communicate to the EVC to control superheat on a Y only signal. 3. R-G contacts close on comfort control sending 24VAC to Continuous Fan the G terminal of the AFC. IMPORTANT: If the indoor air exceeds 60% relative 4. The AFC micro-processor sends a command to the serial humidity or simply feels uncomfortably humid, it communicating blower motor to run at 100% of the cool- is recommended that the indoor fan only be used ing cfm. in the AUTO mode. 5. The EVC will receive input from the two temperature sen- sors and start to control superheat. 1. R-G contacts close on comfort control sending 24VAC to the G terminal of the AFC. 2. The AFC micro-processor sends a command to the OD Two Stage (cooling mode) serial communicating blower motor to run at 50%. 1. R-Y1 contacts close on the comfort control sending See airflow Dip Switch settings for additional info. 24VAC to Y1 terminal on the AFC. The AFC communi- cates to the EVC to control superheat for 1st stage. 2. Normally closed contacts on the AFC will pass 24VAC to Heatpump OD Single Stage (heating mode) the YO terminal providing power to the outdoor unit 1st 1. R-Y contacts close on the comfort control sending stage control circuit. 24VAC to Y1 terminal on the AFC. a. Heatpump OD > R-O contacts close on the comfort 2. Normally closed contacts on the AFC will pass 24VAC control sending 24VAC to the O terminal of the AFC. to the YO terminal providing power to the outdoor unit The AFC communicates to the EVC that the system is in control circuit. cooling mode. The O signal is passed through to the OD 3. R-G contacts close on comfort control sending 24VAC unit. to the G terminal of the AFC. b. Non heatpump OD > OD dip switch configuration will 4. The AFC micro-processor sends a command to the communicate to the EVC to control superheat on a Y serial communicating blower motor to run at 100%. only signal. 4. The HUM contacts close. 3. R-G contacts close on comfort control sending 24VAC to the G terminal of the AFC. Heatpump OD Two Stage (heating mode) 4. The AFC micro-processor sends a command to the se- 1. R-Y1 contacts close on the comfort control sending rial communicating blower motor to run at the 1st stage 24VAC to Y1 terminal on the AFC. cooling cfm. (1st stage cooling cfm is a multiplier of 2nd 2. Normally closed contacts on the AFC will pass 24VAC stage cfm) to the YO terminal providing power to the outdoor unit 1st stage control circuit. 42
You can also read